Advanced
A Comparative Analysis of Step and Touch Voltages Depending on Two Test Voltage Waveforms
A Comparative Analysis of Step and Touch Voltages Depending on Two Test Voltage Waveforms
Transactions on Electrical and Electronic Materials. 2011. Aug, 12(4): 152-155
Copyright ©2011, The Korean Institute of Electrical and Electronic Material Engineers
This is an open-access article distributed under the terms of the Creative Commons Attribution Non-Commercial License(http://creativecommons.org/licenses/by-nc/3.0)which permits unrestricted noncommercial use, distribution, and reproduction in any medium, provided the original work is properly cited.
  • Received : May 02, 2011
  • Accepted : June 14, 2011
  • Published : August 25, 2011
Download
PDF
e-PUB
PubReader
PPT
Export by style
Article
Author
Metrics
Cited by
TagCloud
About the Authors
Kwang-Seok, Jung
Sang-Wook, Cha
Dae-Won, Park
Gyung-Suk, Kil
kilgs@hhu.ac.kr
Jae-Geun, Oh

Abstract
This paper presents a comparative analysis on step and the touch voltages generated by either a sine and a ring wave voltage generator; this analysis was done as a basic study in order to develop a small and lightweight ground meter.A ring wave generator using pulsed power technology was fabricated; an experimental grounding system specified in Institute of Electrical and Electronics Engineers standards 80 and 81 was installed. The step and the touch voltages,which were measured using comparable a sine and a ring waves in terms of magnitude and frequency, were equal.Using pulsed power technology, the weight of the fabricated ring wave generator could be reduced to one-fifth of that of a sine wave generator. Consequently, if a ground meter adopts the ring wave instead of a sine wave, it will be possible to reduce the weight of a ground meter and improve the efficiency of measurement.
Keywords
1. INTRODUCTION
Grounding provides an electrical connection between electrical installations and the earth. The main functions of grounding is in preventing electric shocks to the human body and to protect electrical installations from a potential rise in current due to breakdown, lightning, or overvoltage by allowing the fault current to flow to the ground [1 - 4] . The performance of the grounding system, especially in regards to electric shock, is evaluated using step and the touch voltages.
Currently, the commercial frequency sine wave is used to measure the step and touch voltages. However, it requires a large approximately 40 kg transformer to make a few amperes of current to flow into the ground, which can cause difficulty in moving the transformer to different sites [5 - 9] .
As a solution to this problem, we fabricated a small and lightweight ring wave generator that uses pulsed power technology and carried out comparative analysis of the step and touch voltages upon the application of sine wave and ring wave voltages.The ring wave generator only consists of a high voltage circuit, a capacitor, and a non-saturation reactor, and therefore its weight can be reduced to one-fifth of that of the sine wave generator. An experimental grounding system was fabricated in accordance with Institute of Electrical and Electronics Engineers standards(IEEE Stds.) 80 and 81 in order to compare the step and the touch voltages on the basis of the test voltage waveforms [10 , 11] .
The results showed that the step and the touch voltages, which were compared using the sine and the ring wave in terms of equal magnitude and frequency, were the same. Additionally, it is possible to measure the step and the touch voltage using currents of different magnitudes at the same time if a ring wave is used.
2. EXPERIMENTS
A comparative analysis of the step and the touch voltage was
Lager Image
The ring wave generator equivalent circuit.
Lager Image
The waveform comparison: (a) simulation and (b) generator.
carried out in a grounding system by applying a sine and a ring wave.
The sine wave was applied using a 300 V and 5.6 A inverter power supply which can vary its frequency over the range of 40 Hz-1 kHz. A ring wave was applied using the fabricated 300 V and 20 A pulsed power generator, which can adjust its frequency over the range of 100 Hz-1 kHz.
- 2.1 Ring wave generator
A ring wave generator consists of a high voltage DC supply(HVDC), a capacitor ( C ), a charging resistor ( RC ), a non-saturation reactor ( L ), and an output resistor ( RL ), as shown in Fig. 1 .
The C is charged up to E through the RC . The VO is generated on both sides of RL when C is discharged by closing the switch gap. The resistance of the switch gap shown in Fig. 1 is ignored,and so the basic equation can be expressed as [12] :
Lager Image
Lager Image
The grounding system configuration.
Lager Image
The step voltage waveform comparison: (a) sine wave and (b)ring wave.
If the switch gap is closed at initial condition t = 0, Eq. (1) can be solved for the following three conditions of R (= RO + RL ).
  • (a) When R > 2 √L / C, the output voltageVOis a non-oscillation waveform which slowly attenuates after a fast rise; its solution is:
Lager Image
  • (b) WhenR= 2√L / C, the output voltageVOis a critical damping waveform; its solution is:
Lager Image
Lager Image
The touch voltage waveform comparison: (a) sine wave and (b)ring wave.
  • (c) WhenR< 2√L / C, the output voltageVOis under a damping waveform; its solution is:
Lager Image
A ring wave can be generated by decreasing R and increasing L as seen in Eq. (4); the frequency is set by the R and L . A ring wave generator to measure the step and the touch voltages was designed through a simulation using PSpice and the above-stated theoretical analysis.
Figure 2 is an example of the output waveform from the fabricated ring wave generator. It shows that the waveforms from the generator and the simulation are almost equivalent.
- 2.2 Grounding system
A grounding system, shown in Fig. 3 , was installed in accordance with IEEE Stds. 80 and 81, used to compare the step and the touch voltage depending on test voltage waveforms, the sine and the ring wave. A grounding electrode (E) was buried 10 m away from a current electrode (C) and potential electrodes (P 1 ,P 2 ) were buried at 1 m distance from the grounding electrode.
After applying the ring and the sine wave voltage between the current electrode and the grounding electrode, the step and the touch voltage were calculated by measuring the voltage between E-P 1 (V 1 ) and P 1 -P 2 (V 2 ) [11] . The current flowing to the grounding electrode was also measured.
Lager Image
The comparison between the step and the touch voltage dependingon the frequency and waveform: (a) step voltage and (b)touch voltage.
Lager Image
The comparison between the step and the touch voltage dependingon injected current: (a) step voltage and (b) touch voltage.
3. RESULTS AND DISCUSSION
Figures 4 and 5 show sample waveforms of the step and the touch voltages measured upon the application of sine and ring waves at 1.6 A and 1 kHz to the grounding system. Provided that the sine and the first peak of the ring wave were 1.6 A, the step voltage was consistently 1.86 V.
As can be seen in Fig. 4 (b), the step voltage at three magnitudes of current: 1.6 A, 0.53 A, and 0.18 A, can be measured at the same time when the ring wave is applied. The touch voltage was also equal to the sine and the ring wave, as shown in Fig. 5 .
Figure 6 shows the comparison of the step and the touch voltage when the frequency of the test voltage is varied from 100 Hz to 1 kHz with the current flowing at 1 A. Regardless of the frequency or the test voltage waveform, the step voltage was 1.2 V and the touch voltage was 76 V, showing equivalent results.
Figure 7 shows the comparison between the step and the touch voltages when the current flowing to the grounding electrode varies from 0.1 A to 2.3 A at a frequency of 1 kHz. The step and the touch voltages increase linearly in proportion to the applied current consistently for both waveform types.
In this paper, we carried out a comparative analysis on the step and the touch voltage of a grounding system depending on test voltage waveform at a current far smaller than an actual fault current. However, because an underground arc discharge may occur with a large fault current of several tens or hundreds of amperes flowing to the grounding systems, further studies regarding this phenomenon should be undertaken.
4. CONCLUSIONS
In order to develop a small and lightweight ground meter, we fabricated a ring wave generator and compared the step and the touch voltages of a grounding system when using sine and ring wave voltages. Using pulsed power technology, the weight of the fabricated ring wave generator can be reduced to one-fifth of that needed by a sine wave generator.
The experiment was performed on a grounding system specified in IEEE Stds. 80 and 81. The results showed that the step and the touch voltages, which were measured under comparable sine and the ring wave voltages in terms of the magnitude (0.1 A-2.3 A)and the frequency (100 Hz-1 kHz), were equal. Consequently, it is concluded that the weight of a ground meter can be reduced if the ring wave replaces the sine wave.
Acknowledgements
This research was financially supported by the Ministry of Education,Science Technology (MEST) and the National Research Foundation of Korea (NRF) through the Human Resource Training Project for Regional Innovation and supported by the Electric Power Industry R&D Program (R-2007-1-014-02) of Ministry of Knowledge Economy (MKE).
References
Morrison R , Lewis W. H 1990 Grounding and Shielding in Facilities Wiley New York 44 - 45
Kosztaluk R , Mukhedkar R , Gervais Y 1984 IEEE Trans.Power App. Syst. PAS-103 3286 -    DOI : 10.1109/TPAS.1984.318571
Meliopoulos A. P. S , Cokkinides G , Abdallah H , Duong S , Patel S 1993 IEEE Trans. Power Del. 8 1095 -    DOI : 10.1109/61.252636
Khalifa M 1990 High-Voltage Engineering: Theory and Practice Marcel Dekker New York 331 - 356
Papalexopoulos A. D , Meliopoulos A. P 1987 IEEE Trans. Power Del. 2 1073 -    DOI : 10.1109/TPWRD.1987.4308223
Meliopoulos A. P. S 1988 Power System Grounding and Transients:An Introduction Marcel Dekker New York 5 - 20
IEEE Std 367-1996. IEEERecommended Practice for Determining the Electric Power Station Ground Potential Rise and Induced Voltage From a Power Fault 2 -    DOI : 10.1109/IEEESTD.1997.83838
Geri A 1999 IEEE Trans. Power Del. 14 1008 -    DOI : 10.1109/61.772347
O'Riley R. P 2002 Electrical Grounding: Bringing Grounding Back to Earth 6th ed. Delmar Thomson Learning Albany NY 40 - 43
IEEE Std 80-2000. IEEEGuide for Safety in AC Substation Grounding 114 -    DOI : 10.1109/IEEESTD.2000.91902
IEEE Std 81-1983. IEEEGuide for Measuring Earth ResistivityGround Impedance and Earth Surface Potentials of a Ground System 18 - 26    DOI : 10.1109/IEEESTD.1983.82378
Meliopoulos A. P , Moharam M. G 1983 IEEE Trans. Power App.Syst. PAS-102 389 -    DOI : 10.1109/TPAS.1983.317686