Fast-Transient Repetitive Control Strategy for a Three-phase LCL Filter-based Shunt Active Power Filter
Fast-Transient Repetitive Control Strategy for a Three-phase LCL Filter-based Shunt Active Power Filter
Journal of Power Electronics. 2014. Mar, 14(2): 392-401
Copyright © 2014, The Korean Institute Of Power Electronics
  • Received : March 28, 2013
  • Accepted : December 30, 2013
  • Published : March 30, 2014
Download
PDF
e-PUB
PubReader
PPT
Export by style
Share
Article
Author
Metrics
Cited by
TagCloud
About the Authors
Zheng Zeng
College of Electrical Engineering, Zhejiang University, Hangzhou, China
Jia-Qiang Yang
College of Electrical Engineering, Zhejiang University, Hangzhou, China
yjq1998@163.com
Shi-Lan Chen
College of Electrical Engineering, Zhejiang University, Hangzhou, China
Jin Huang
College of Electrical Engineering, Zhejiang University, Hangzhou, China

Abstract
A fast-transient repetitive control strategy for a three-phase shunt active power filter is presented in this study to improve dynamic performance without sacrificing steady-state accuracy. The proposed approach requires one-sixth of the fundamental period required by conventional repetitive control methods as the repetitive control time delay in the synchronous reference frames. Therefore, the proposed method allows the system to achieve a fast dynamic response, and the program occupies minimal storage space. A proportional-integral regulator is also added to the current control loop to eliminate arbitrary-order harmonics and ensure system stability under severe harmonic distortion conditions. The design process of the corrector in the fast-transient repetitive controller is also presented in detail. The LCL filter resonance problem is avoided by the appropriately designed corrector, which increases the margin of system stability and maintains the original compensation current tracking accuracy. Finally, experimental results are presented to verify the feasibility of the proposed strategy.
Keywords
I. INTRODUCTION
With the rapid development of power electronics, a variety of power electronic devices and nonlinear loads have been widely used. Numerous problems associated with reactive power and harmonic pollution have emerged in power systems. Harmonic suppression and reactive power compensation have become popular issues in current research. Traditional passive power filters are gradually being replaced by active power filters (APFs) [1] . A novel APF with an LCL filter [2] - [4] can minimize the amount of distortion current in the utility grid and achieve a fast dynamic response with small inductors and filter capacitors.
A key point in the proper implementation of APF is compensation current tracking. Various methods have been proposed in literature to improve APF current tracking performance [5] - [9] . Hysteresis control [5] and proportional-integral (PI) control [6] are conventional methods commonly employed in industrial APF applications although new control methods have also been proposed, such as fuzzy control [7] , sliding mode variable structure control [8] , and adaptive control [9] . Hysteresis control systems are robust although their switch frequency is uncertain; such uncertainty produces harmonics with a continuous spectrum and increases the difficulty of designing an appropriate output filter. PI control has a fast dynamic response and good tracking capability for DC signals. Increasing the PI controller gain helps improve AC signal tracking performance; however, a large controller gain often causes a resonance problem in the LCL filter [10] , [11] . The proportion resonance (PR) control method can eliminate the tracking error of regulation sinusoidal signals [12] . However, to compensate for harmonics in this method, each harmonic frequency must correspond to its specific regulator. Therefore, designing a multi-resonant controller for all harmonic components requires a large amount of resources and is thus unsuitable for practical systems.
Repetitive control from the internal model principle provides a high-performance practical solution [13] - [15] . Repetitive control allows for exact asymptotic output tracking of periodic inputs or rejection of periodic disturbances and is thus widely used in inverter waveform control. This approach can meet the necessary high-gain requirements of current control loops in APF [16] - [19] . However, because the control action is postponed for one fundamental period, conventional repetitive control often fails to eliminate harmonics with satisfactory dynamic response [20] .
Normally, the conventional repetitive controller provides high gains at all harmonic frequencies. Given that most power electronic systems mainly contain odd harmonics, repetitive control schemes intended to compensate for only odd harmonics have been proposed in [21] and [22] . In these odd-harmonic repetitive controllers, time delay is reduced to one half of the fundamental period, which can be regarded as an improvement of system dynamic response. In three-phase power applications, the harmonic components usually concentrate in multiples of 6 n ± 1 of the fundamental frequency. The authors of [23] presented a six-model repetitive controller that employs a parallel combination of (6 n + i ) ( i = 0, 1, 2, 3, 4, 5) order harmonic internal models with six independent control gains to eliminate (6 n + i )th harmonics. However, this method increases the complexity of the control loop and consumes a large amount of computing resources; as a result, the method is difficult to apply to actual systems. In [24] , the authors presented a repetitive controller in a stationary frame that selects (6 n ±1)th ( n = 0, 1, 2, . . .) harmonics for compensation. The (6 n ±1)th harmonic repetitive controller obtains enhanced frequency selectivity and has low computation complexity. However, this method cannot effectively compensate for even harmonics because the controller gains are not sufficiently high at these harmonic frequencies.
A fast-transient repetitive controller for a three-phase, LCL filter-based shunt APF is proposed in this study. The controller is implemented in a positive-rotating synchronous frame where all the (6 n ±1)th ( n = 0, 1, 2...) harmonics can be well eliminated. The maximum repetitive control delay time is reduced to one-sixth of the fundamental period; therefore, the dynamic response is significantly improved without sacrificing steady-state performance. The PI regulator is also combined with a fast-transient repetitive controller to compensate for even harmonics under unbalanced conditions. Theoretical analysis and deduction of the proposed method are also demonstrated. The design process of the corrector in the proposed fast-transient repetitive controller is presented in detail. The LCL filter resonance problem is avoided by using an appropriately designed corrector that increases the margin of system stability and maintains the original compensation current tracking accuracy. The feasibility of the hybrid current controller is validated by the experimental results.
II. APF CONTROL SYSTEM AND MATHEMATICAL MODEL
- A. APF Structure and Control System
The structure of the proposed LCL filter-based shunt APF is shown in Fig. 1 . The shunt APF is composed of two-level voltage source inverters with a DC capacitor and LCL-type output filter. L 1 denotes the inverter-side filter inductors, L 2 denotes the grid-side filter inductors, C denotes the filter capacitors, and Rd denotes the damping resistors. A three-phase diode rectifier with resistive and inductive load is adopted as a harmonic source to produce the harmonic currents.
PPT Slide
Lager Image
Structure of shunt APF with LCL filter.
A block diagram of the shunt APF control system is presented in Fig. 2 . The control system contains a reference current calculator, a DC voltage regulator, and a compensation current controller. The reference current calculator detects the harmonic components in the load currents. A DC voltage regulator is adopted to maintain DC bus voltage stability. The compensation reference currents are obtained by adding the output current reference of the DC voltage regulator and the harmonic components in the load current. The compensation current controller generates a reference voltage to allow the compensation current to track the reference current accurately. Therefore, the compensation current can offset the harmonic components in the load currents, and the harmonics in the point of common coupling (PCC) current are also eliminated.
PPT Slide
Lager Image
Block diagram of shunt APF control system.
Considering that the inductor resistance and grid inductance are negligible, the transfer function related to input voltage ui and output current ic can be deduced as
PPT Slide
Lager Image
Based on transfer function GLCL ( s ) , the LCL filter can be regarded as a three-order system. An LCL filter is more difficult to control than an L filter.
Fig. 3 shows the voltage-current frequency responses of a first-order L filter (Line 1) and a third-order LCL filter (Line 2). Line 3 shows the frequency responses of an LCL filter with a passive damping resistor. A small damping resistor is usually added to the filter capacitor branch to prevent problems in system resonance. The third-order LCL filter should provide an appropriate resonance frequency below the PWM switching frequency, an acceptable level of current ripples in inverter-side inductor L 1 , and low idle reactive power for the apparatus. The detailed LCL filter exemplary design procedure is provided in [2] . In short, the LCL filter has a much better stop-band attenuation than the L filter. Therefore, the output filter of the LCL filter has much lower equivalent inductance than that of the L filter.
PPT Slide
Lager Image
Frequency response of the L and LCL filters.
- B. Mathematical Model
Fig. 3 shows that the L and LCL filters have similar magnitude–frequency characteristics within the passband of the filters. For this reason, the capacitor branch of the LCL filter can be disregarded. The LCL filter behaves as an L filter with an inductance value of L = L 1 + L 2 . The equations of the output current based on Kirchhoff’s voltage law result in
PPT Slide
Lager Image
where uia , uib , and uic are the inverter voltages; usa , usb , and usc are the grid voltages; ica , icb , and icc are the compensating currents; and R is the equivalent resistance of theica inductor.
Using Park transformation, Equation (3) can be obtained by converting the stationary reference frame systematic formulas [Equation (2)] into d–q synchronous reference frame formulas as
PPT Slide
Lager Image
Obviously, cross-coupling items exist between the d-axis and q-axis currents.
- C. Decoupling Method with PI Controller
A controller with feedback cross-decoupling can eliminate the coupling between the d and q axes. A grid voltage feed-forward path is added to the controller to eliminate the influence of grid voltage fluctuation. A PI controller with grid voltage feed-forward and output current feedback cross decoupling is shown in Fig. 4 .
PPT Slide
Lager Image
Current control block diagram of APF in the dq frame.
The decoupling items and the feed-forward voltage can be regarded as disturbances in the above mentioned approaches. The current control block diagram of APF can be simplified as shown in Fig. 5 .
PPT Slide
Lager Image
Simplified current control block diagram.
The controller requires a wide bandwidth to obtain satisfactory compensation current tracking performance. Owing to the limited sampling frequency and calculation delay time in digital systems, the control variable output is usually retarded by one control period. This condition results in further phase delay. The system phase delay can be reduced by increasing the gain of the PI controller and the sampling and switching frequencies. However, all these methods cannot improve harmonic compensation. Furthermore, the phase delay may cause instability in the LCL filter-based shunt APF. Therefore, a current controller with high stability and high-precision tracking performance is required.
III. FAST-TRANSIENT REPETITIVE STRATEGY
- A. Review of Conventional Repetitive Controller Structure
The basic idea behind repetitive control is based on the internal-model principle of control theory. The general structure of a conventional repetitive controller is shown below.
The core of the repetitive controller is a modified internal model denoted by the positive feedback loop in Fig. 6 . The original internal model incorporates the unity gain in the positive feedback path so that the tracking error is converged based on its repetition period. However, in practice, the internal model is often modified by incorporating an attenuation coefficient ( Q ) instead of the unity gain. Although this manipulation results in reduced reference tracking accuracy, it also increases the margin of system stability.
PPT Slide
Lager Image
Conventional repetitive controller structure.
From Fig. 6 , the transfer function of the conventional repetitive controller is
PPT Slide
Lager Image
where S ( z ) is a corrector designed to compensate for the controlled object according to its characteristic. The period delay part Z -N in the forward channel causes a delay of one fundamental period. Thus, the control effect has a certain foresight of the next period. Owing to a long time delay, the conventional repetitive controller has a very slow transient response speed. For this reason, harmonic current compensation is difficult under conditions of rapid load fluctuations .
- B. Proposed Fast-transient Repetitive Controller Structure
Generally speaking, a balanced three-phase system only contains (6 n ±1)th ( n = 0, 1, 2...) harmonics because many power conversion processes (i.e., diode rectifier loads) involved in industrial applications produce harmonic components at these frequencies. In the synchronous frame with + ω rotation speed, the positive sequences of the 7 ω , 13 ω , 19 ω … signals are transformed to +6 ω , +12 ω , +18 ω … signals, whereas the negative sequences of the 5 ω , 11 ω , 17 ω … signals are transformed to -6 ω , -12 ω , -18 ω … signals. The (6 n ±1) ω ( n =0, 1, 2...) harmonic components transform into 6 ( n =0, 1, 2, 3…) signals in the positive synchronous frame. This useful feature simplifies the synchronous frame controller design because only the 6 n th ( n = 0, 1, 2...) harmonics are compensated. Thus, a fast-transient repetitive control strategy is proposed in this study. The strategy aims to compensate for 6 n th harmonics in a three-phase shunt APF.
The structure of the proposed fast-transient repetitive controller is shown in Fig. 7 .
PPT Slide
Lager Image
Fast-transient repetitive controller structure.
The transfer function of the fast-transient repetitive controller is
PPT Slide
Lager Image
Conventional repetitive controllers are designed to eliminate all odd and even harmonics at the cost of introducing a fundamental period delay. However, from the previous discussions, the time delay required for a fast-transient repetitive controller can be significantly reduced from one fundamental T period to T /6. For this reason, a fast-transient repetitive controller provides faster dynamic performance than the conventional one. In addition, by considering only (6 n ±1)th harmonics, the proposed repetitive controller can avoid the amplification of other harmonics to the PCC currents.
Fig. 8 shows the open-loop frequency responses of the PI controller (Line 1), conventional repetitive controller (Line 2), and proposed fast-transient repetitive controller (Line 3). The PI controller is implemented with parameters kp = 2 and ki = 2000. The gain of the PI controller for the DC signal is above 50 dB, but its gain in the harmonic-frequency range cannot satisfy the harmonic compensation requirements. The conventional repetitive controller is implemented with a delay of one fundamental period, where N = 300 and Q = 0.99. Fig. 8 shows that the conventional repetitive controller provides high gain (40 dB) at each harmonic frequency, whereas the corresponding resonant frequencies of the fast-transient repetitive controller ( N = 300, Q = 0.99) are only in the 6 n th harmonics.
PPT Slide
Lager Image
Frequency response of PI and repetitive control.
Given that the repetitive control strategy contains a necessary delay section, satisfying the requirement of fast dynamic response and stability of APF is difficult. Thus, a hybrid current controller that consists of PI and repetitive controllers is implemented in the current loop. The PI controller improves the dynamic performance and maintains system stability, whereas the repetitive controller provides high gain in harmonics to ensure that the PCC current remains sinusoidal.
To achieve a hybrid output control, the PI and repetitive controllers are connected in parallel in the forward path of the current control loop as shown in Fig. 9 .
PPT Slide
Lager Image
Hybrid controller scheme for APF with an LCL filter.
The PI controller exports a thin control quantity in the steady-state condition because of a few tracking errors. As a result, the hybrid control parameter is principally determined by the repetitive controller. However, when the system undergoes a severe dynamic load fluctuation, the PI controller plays the major role in the hybrid control system and the repetitive controller output quantity cannot adjust promptly. After the delay, the repetitive controller gradually decreases the tracking error and thus weakens the influence of the PI controller. Eventually, the system achieves a new steady state.
When the grid voltage or load condition is unbalanced, each (6n±1)th harmonic component contains both positive and negative sequences. Therefore, the 6nth harmonics as well as other orders of harmonics are visible in the positive synchronous frame. However, in most cases, the unbalanced condition of the grid voltage or load is not severe (mostly below 10%). In such cases, the PI controller inside the hybrid control strategy provides additional gain for the negative sequence harmonics.
- C. Compensation Current Tracking Accuracy Analysis
The repetitive control method introduced to the hybrid current controller improves the tracking accuracy and eliminates the steady state error. By analyzing the error transfer function, the tracking accuracy of the repetitive control method can be compared with that of other methods. As shown in Fig. 5 , the error transfer function with a PI controller is as follows:
PPT Slide
Lager Image
The error transfer function with a hybrid controller is as follows:
PPT Slide
Lager Image
By comparing the error transfer function gain in different strategies, the increased GREP ( z ) in the denominator of the hybrid control system can reduce the ei gain significantly after adding repetitive control. Considering the resonant characteristics in the LCL filter, the gain of the PI controller cannot be extremely large; thus, the current tracking results of the PI controller are subject to certain restrictions. As long as the corrector of the repetitive controller is designed appropriately, the repetitive controller can improve the accuracy of current tracking without the influence of the PI controller gain.
- D. System Stability Analysis and Corrector Design
To analyze the stability of the proposed fast-transient repetitive controller, the current closed loop transfer function of the hybrid controller is described as
PPT Slide
Lager Image
P ( z ) can be considered the equivalent controlled object of the repetitive controller. According to the small gain theorem, a sufficient condition [13 , 25] for system stability can be provided as
PPT Slide
Lager Image
where Ts denotes the sampling period. Given that the equivalent controlled object contains resonant instability and phase delay, it must be corrected with an appropriately designed corrector S ( z ) . Furthermore, the corrector requires zero gain offset frequency response in a low-frequency band range; this condition does not affect the compensation current tracking performance.
In this study, a second-order low-pass filter and a zero phase-shift notch filter cascade connection S ( z ) prevent the system stability condition from breaking at high frequencies [14] - [16] . The second-order low pass filter is required for high frequency attenuation, which greatly simplifies the controller design. A second-order filter with the transfer function (10) is selected to prevent the amplitude–frequency response within the current controller bandwidth from being affected. When crossover frequency ωn = 2 π ・ 3750 rad / s , damping coefficient ξ = 0.8 .
PPT Slide
Lager Image
Through Tustin transform( fs =15 kHz ) , the discrete transfer function can be described as follows:
PPT Slide
Lager Image
Although the peak resonance of GLCL ( s ) shown in Fig. 3 is partly suppressed by passive damping in the branch of the filter capacitor, it does not satisfy the requirements for the stability of the overall system. Fig. 3 shows that the gain of resonant frequency still exceeds 0 dB. Moreover, considering the addition gain of the current controller, system instability is easily caused. For this reason, an additional suppression method is required in the control algorithm. In this study, a zero phase-shift notch filter (denoted as F 2 ( z ) ) is adopted in the corrector to avoid the LCL filter resonance problem without degrading the steady-state performance of the repetitive controller. F 2 ( z ) is expressed as
PPT Slide
Lager Image
where a 0 and m are constants related to the shape and location of the notch filter, respectively [26] . Furthermore, the zero phase notch filter does not produce additional phase shift. The notch filter with a small value of a 0 causes a narrow stop band and allows a large amount of harmonic components to pass through the filter, which in turn results in better steady-state compensation performance of the repetitive controller. As shown in Fig. 3 , the LCL filter resonant frequency is located around 5 kHz; thus, F 2 ( z ) can select parameters with a 0 = 2, m = 1 , which has a notch peak point near the corresponding LCL filter resonant frequency. The transfer function of 2 F 2 ( z ) is expressed as
PPT Slide
Lager Image
Even with the corrector filter, the repetitive controller still provides high gains in a low-frequency range and the magnitudes of the harmonic peaks in high-frequency regions are reduced to ensure system stability. However, the corrector filter can enhance system stability without causing much impact on the steady-state performance because the magnitude of the high-frequency harmonics is usually very small.
Phase lag must also be compensated for to maintain system stability and steady-state performance. Therefore, a leading element, zk , is adopted to compensate for the delay caused by the calculation time in the digital control and to minimize the phase displacement of S ( z ) P ( z ) . The designed corrector of the fast-transient repetitive controller is
PPT Slide
Lager Image
The frequency characteristics of S ( z ) P ( z ) with different values of k are shown in Fig. 10 . Minimum phase displacement is attained with k = 2. In a low-frequency band, the gain and phase lag of S ( z ) P ( z ) are close to 0 dB and 0°, respectively, to ensure a small steady-state error. In addition, in consideration of the one beat delay in the digital control implementation, k =3 is selected.
PPT Slide
Lager Image
Bode diagram of S(z)P(z) with different values of k.
The role of Q in Equation (5) is to improve the system stability margin by reducing the peak gains of the repetitive controller in high-frequency ranges. In this study, Q is selected as a close-to-unity constant 0.95 to guarantee a sufficient stability margin.
Using the aforementioned design results, the locus of H ( z ) is plotted in Fig. 11 .
PPT Slide
Lager Image
Nyquist diagram of H(z).
In Fig. 11 , H ( z ) is always located inside the unity circle. Therefore, the proposed fast-transient repetitive controller with an appropriate designed corrector satisfies the stability condition.
IV. EXPERIMENTAL RESULTS AND ANALYSIS
To verify the aforementioned analysis, experiments are implemented on a three-phase LCL filter-based shunt APF prototype, which is depicted in Fig. 1 . The key parameters of the prototype are listed in Table 1 . The control platform is implemented on a TMS320F28335 DSP control board. The insulated gate bipolar transistor (IGBT) module FF300R12MS4 from Infineon is used in the main circuit power inverter.
PARAMETERS OF THE SHUNT APF PROTOTYPE
PPT Slide
Lager Image
PARAMETERS OF THE SHUNT APF PROTOTYPE
- A. Steady-state Performance of PCC Current
Fig. 12 (a) shows the waveform of the grid current with nonlinear RL load before the shunt APF is operated. The frequency spectrum of the grid current is shown in Fig. 12 (b). The total harmonic distortion (THD) of the grid current is approximately 26.1%
PPT Slide
Lager Image
Waveform of the grid current without shunt APF.
Fig. 13 shows the experimental results of the steady-state grid current with a traditional PI current controller. As shown in Figs. 12 and 13 , reducing the THD of the grid current from 26.1% to 8.5% is possible by means of a traditional PI controller. The components of the 5th, 7th, 11th, and 13th harmonic currents are greatly suppressed, and the shunt APF with a traditional PI controller allows some other harmonic currents into the grid current. The traditional PI controller is unable to effectively compensate for the harmonic currents because of its control bandwidth limitation.
PPT Slide
Lager Image
Steady-state performance with a traditional PI controller.
The experimental results of the PR controller [12] whose regulators tuned on resonance frequencies 6th, 12th, and 18th are shown in Fig. 14 . When the PR controller is employed, the grid current exhibits better steady-state performance and THD is reduced to 4.8%. However, the PR controller does not generate high gains in harmonics above the 18th. The high-order harmonic current compensation performance is thus ineffective.
PPT Slide
Lager Image
Steady-state performance with a PR controller.
An experimental test with a conventional repetitive control algorithm under the same condition is shown in Fig. 15 . The harmonic currents are effectively compensated, and the grid current is almost sinusoidal with a low THD of approximately 3.7%. This result proves that the repetitive controller has a better steady filtering capability compared with the traditional PI controller.
PPT Slide
Lager Image
Steady-state performance with a conventional repetitive controller.
Fig. 16 (a) shows the waveforms of the grid current when a hybrid current controller is employed. The PI and fast-transient repetitive controllers are connected in parallel when the shunt APF operates. As shown in Fig. 16 (b), the THD of the grid current is 3.6% when the APF filter with a fast-transient repetitive controller is used. This result confirms that the performance of the proposed controllers is similar to that of the conventional one in steady state conditions.
PPT Slide
Lager Image
Steady-state performance with the proposed fast-transient repetitive controller.
- B. Dynamic Responses under Load Step Change
Fig. 17 illustrates the experimental waveforms of the dynamic response when a conventional repetitive controller is employed and when the load varies from light to heavy. The compensation current tracks the load harmonic current within nearly two fundamental cycles.
PPT Slide
Lager Image
Transient responses when a conventional repetitive controller is used.
Fig. 18 shows the dynamic response of the fast-transient repetitive controller. The filter current quickly responds to compensate for the harmonic currents in the load and to ensure that the supply current is sinusoidal. As shown in Figs. 17 and 18 , the current tracking error recovers to its steady-state value in approximately 10 ms, which is much shorter than that in the conventional controller. As a result, the fast transient responses of the proposed controller are verified.
PPT Slide
Lager Image
Transient responses when a fast-transient repetitive controller is used.
- C. Performance of PCC Current under Unbalanced Supply Voltage
The majority of previous studies assumed that the supply voltage is ideally balanced; however, this voltage condition is rare in practical grid conditions. To verify the effectiveness of the proposed control algorithm under unbalanced conditions, experiments are conducted where the supply voltages are injected with negative components that are 10% of the magnitude of the fundamental component.
The waveform of the unbalanced three-phase grid voltage is shown in Fig. 19 .
PPT Slide
Lager Image
Waveform of unbalanced three-phase grid voltages.
As shown in Fig. 20 , the harmonic compensation performance of APF does not diminish under the unbalanced grid voltage condition. The grid current is nearly sinusoidal, which is similar to the results shown in Fig. 20 where an ideal balanced voltage is provided. Only small increases were observed in the THD factors, that is, approximately 4.0% for the same case of nonlinear RL load.
PPT Slide
Lager Image
Steady-state performance with the fast-transient repetitive controller under an unbalanced grid condition.
PPT Slide
Lager Image
Implemented LCL filter-based shunt APF system.
As a result, the proposed fast-transient repetitive controller obtains a remarkably fast transient response and a satisfactory steady filtering capability.
V. CONCLUSIONS
A fast-transient repetitive controller for a three-phase LCL filter-based shunt APF was proposed in this study. This controller minimizes the repetitive control time delay to one-sixth of the fundamental period and improves the dynamic responses without sacrificing high steady-state performance. In the hybrid control scheme, the repetitive controller improves the tracking accuracy and eliminates the steady state error. The PI controller guarantees the dynamic response and current tracking speed of APF. Furthermore, the strategy suppresses the resonance problem of the LCL filter by using an appropriately designed corrector. The experimental results verify the feasibility and validity of the proposed strategy. Owing to its fast transient response and high tracking accuracy, this strategy is also appropriate for three-phase grid-connected inverters, such as static synchronous compensators or uninterruptible power supplies.
Acknowledgements
This work was supported in part by the National Natural Science Foundation of China (Project no. 51177150) and the National Key Basic Research Program of China (Project no. 973) under Grant no. 2013CB035604.
BIO
Zheng Zeng was born in Hunan, China, in 1987. He received his B.S. degree from Central South University, Changsha, China, in 2009. He is pursuing his Ph.D. degree in electrical engineering at Zhejiang University, Hangzhou, China. His research interests include power quality and control technology, power electronics and electric drives, and renewable energy generation.
Jia-Qiang Yang was born in Jiangsu, China, in 1970. He received his Ph.D. degree in electrical engineering from Zhejiang University, Hangzhou, China, in 2004. He has been an associate professor at the College of Electrical Engineering, Zhejiang University, Hangzhou, China, since 2006. He was a research fellow at the NationalUniversity of Singapore, Singapore, from March 2011 to April 2012. His research interests include power electronics, electric machine drives, and control strategies.
Shi-Lan Chen was born in Jiangxi, China, in 1990. He received his B.S. degree in electrical engineering from North University of China, Taiyuan, China, in 2011. He is pursuing his M.S. degree in electrical engineering at Zhejiang University, Hangzhou, China. His current research interests include harmonic and reactive power compensation in power grids.
Jin Huang received his B.Sc. degree from Zhejiang University, Hangzhou, China, in 1982 and his Ph.D. degree in electrical engineering from the National Polytechnic Institute of Toulouse, Toulouse, France, in 1987. He worked as an associate professor at the College of Electrical Engineering, Zhejiang University, Hangzhou, China, from 1987 to 1994. He has been a professor in Zhejiang University since 1994. He is engaged in research on electrical machines, AC drives, multiphase machines, and control strategies.
References
Akagi H. 2005 “Active harmonic filters,” inProc. the IEEE 93 (12) 2128 - 2141    DOI : 10.1109/JPROC.2005.859603
Liserre M. , Blaabjerg F. , Hansen S. 2005 “Design and control of an LCL-filter-based three-phase active rectifier,” IEEE Trans. Ind. Appl. 41 (5) 1281 - 1291    DOI : 10.1109/TIA.2005.853373
Yi T. , Poh C. L. , Peng W. , Fook H. C. , Feng G. , Blaabjerg F. 2012 “Generalized design of high performance shunt active power filter with output LCL filter,” IEEE Trans. Ind. Electron. 59 (3) 1443 - 1452    DOI : 10.1109/TIE.2011.2167117
Wojciechowski D. , Strzelecki R. 2010 “High power, zero ripples active filtering system with power modules operating in parallel,” in Electronics Conference (BEC) 305 - 308
Vodyakho O. , Mi C. C. 2009 “Three-level inverter-based shunt active power filter in three-Phase three-wire and four-wire systems,” IEEE Trans. Power Electron. 24 (5) 1350 - 1363    DOI : 10.1109/TPEL.2009.2016663
Montero M. I. M. , Cadaval E. R. , Gonzalez F. B. 2007 “Comparison of control strategies for shunt active power filters in three-phase four-wire systems,” IEEE Trans. Power Electron. 22 (1) 229 - 236    DOI : 10.1109/TPEL.2006.886616
Luo A. , Shuai Z. , Zhu W. , Fan R. , Tu C. 2009 “Development of hybrid active power filter based on the adaptive fuzzy dividing frequency-control method,” IEEE Trans. Power Del. 24 (1) 424 - 432    DOI : 10.1109/TPWRD.2008.2005877
Matas J. , de Vicuna L. G. , Miret J. , Guerrero J. M. , Castilla M. 2008 “Feedback linearization of a single-phase active power filter via sliding mode control,” IEEE Trans. Power Electron. 23 (1) 116 - 125    DOI : 10.1109/TPEL.2007.911790
Singh B. , Solanki J. 2009 “An implementation of an adaptive control algorithm for a three-phase shunt active filter,” IEEE Trans. Ind. Electron. 56 (8) 2811 - 2820    DOI : 10.1109/TIE.2009.2014367
Gabe I. J. , Montagner V. F. , Pinheiro H. 2009 “Design and implementation of a robust current controller for VSI connected to the grid through an LCL filter,” IEEE Trans. Power Electron. 24 (6) 1444 - 1452    DOI : 10.1109/TPEL.2009.2016097
Wang Z. , Xie C. , He C. , Chen G. 2010 “A waveform control technique for high power shunt active power filter based on repetitive control algorithm,” in Proc. IEEE APEC 361 - 366
Bojoi R. I. , Griva G. , Bostan V. , Guerriero M. , Farina F. , Profumo F. 2005 “Current control strategy for power conditioners using sinusoidal signal integrators in synchronous reference frame,” IEEE Trans. Power Electron. 20 (6) 1402 - 1412    DOI : 10.1109/TPEL.2005.857558
Zhang B. , Wang D. , Zhou K. , Wang Y. 2008 “Linear phase lead compensation repetitive control of a CVCF PWM inverter,” IEEE Trans. Ind. Electron. 55 (4) 1595 - 1602    DOI : 10.1109/TIE.2008.917105
Escobar G. , Valdez A. A. , Leyva-Ramos J. , Mattavelli P. 2007 “Repetitive-based controller for a UPS inverter to compensate unbalance and harmonic distortion,” IEEE Trans. Ind. Electron. 54 (1) 504 - 510    DOI : 10.1109/TIE.2006.888803
Xin T. , Tsang K. M. , Chan W. L. 2012 “A power quality compensator with DG interface capability using repetitive control,” IEEE Trans. Energy Convers. 27 (2) 213 - 219    DOI : 10.1109/TEC.2012.2183874
Garcia-Cerrada A. , Pinzon-Ardila O. , Feliu-Batlle V. , Roncero-Sanchez P. , Garcia-Gonzalez P. 2007 “Application of a repetitive controller for a three-phase active power filter,” IEEE Trans. Power Electron. 22 (1) 237 - 246    DOI : 10.1109/TPEL.2006.886609
Costa Castello R. , Grino R. , Cardoner Parpal R. , Fossas E. 2009 “High-performance control of a single-phase shunt active filter,” IEEE Trans. Control Syst. Technol. 17 (6) 1318 - 1329    DOI : 10.1109/TCST.2008.2007494
Miret J. , Castilla M. , Matas J. , Guerrero J. M. , Vasquez J. C. 2009 “Selective harmonic-compensation control for single-phase active power filter with high harmonic rejection,” IEEE Trans. Power Electron. 56 (8) 3117 - 3127
Zou Z. , Wang Z. , Cheng M. , Yang Y. 2012 “Active power filter for harmonic compensation using a digital dual-mode-structure repetitive control approach,” in Proc. IEEE PEDG 161 - 166
Zeng Z. , Yang J. , Yu N. 2012 “Research on PI and repetitive control strategy for shunt active power filter with LCL filter,” in Proc. IEEE IPEMC 2833 - 2837
Costa-Castello R. , Grino R. , Fossas E. 2004 “Odd-harmonic digital repetitive control of a single-phase current active filter,” IEEE Trans. Power Electron. 19 (4) 1060 - 1068    DOI : 10.1109/TPEL.2004.830045
Grino R. , Cardoner R. , Costa-Castello R. , Fossas E. 2007 “Digital repetitive control of a three-phase four-wire shunt active filter,” IEEE Trans. Ind. Electron. 54 (3) 1495 - 1503    DOI : 10.1109/TIE.2007.894790
Lu W. , Zhou K. , Cheng M. , Yang Y. , Fan S. 2012 “Parallel structure repetitive controller for CVCF three-phase PWM inverter,” in Proc. IEEE APEC 207 - 210
Escobar G. , Hernandez-Briones P. G. , Martinez P. R. , Hernandez-Gomez M. , Torres-Olguin R. E. 2008 “A repetitive-based controller for the compensation of 6l±1 harmonic components,” IEEE Trans. Ind. Electron. 55 (8) 3150 - 3158    DOI : 10.1109/TIE.2008.921200
Jiang S. , Cao D. , Li Y. , Liu J. , Peng F. Z. 2012 “Low-THD, fast-transient, and cost-effective synchronous-frame repetitive controller for three-phase UPS inverters,” IEEE Trans. Power Electron. 27 (6) 2994 - 3005    DOI : 10.1109/TPEL.2011.2178266
Teng G. F. , Xiao G. C. , Hu L. L. , Lu Y. , Kafle Y. R. 2012 “Control Strategy Based on Equivalent Fundamental and Odd Harmonic Resonators for Single-Phase DVRs,” Journal of Power Electronics 12 (4) 654 - 663    DOI : 10.6113/JPE.2012.12.4.654