For the digital control of systems such as grid-connected inverters, measuring inverter output currents accurately is essential. However, current measurement offsets are inevitably generated by current measurement paths and cause DC current components in real inverter output currents. Real inverter output currents with DC components cause the DC-link capacitor voltage to oscillate at the frequency of a utility voltage. For these reasons, current measurement offsets deteriorate the overall system performance. A compensation strategy to eliminate the effect of current measurement offsets in grid-connected inverters is proposed in this study. The validity of the proposed compensation strategy is verified through simulations and experiments. Results show that the proposed compensation strategy improves the performance of grid-connected inverters.
I. INTRODUCTION
Environmental pollution and limited fossil fuel have prompted research into distributed generation systems using renewable energy sources (i.e., solar cells, fuel cells, or wind turbines)
[1]
-
[4]
. Power quality problems have also increased the demand for custom power devices
[5]
-
[7]
. These systems are usually operated by grid-connected inverters similar to those shown in
Fig. 1
. In grid-connected inverters, the precise control of inverter output currents must be achieved because electricity supply companies require adequate certification for harmonic distortion, power factor, and DC components for inverter output currents
[8
-
10]
. Accordingly, many methods for the current control of grid-connected inverters have been developed. These methods include the use of the stationary and synchronous frame proportional-integral (PI) regulator
[11]
,
[12]
, stationary frame proportional-resonant (PR) regulator
[13]
-
[15]
, repetitive-based regulator
[16]
, deadbeat regulator
[17]
, and hysteresis regulator
[18]
.
Grid-connected inverters. (a) Single-phase grid-connected inverter. (b) Three-phase grid-connected inverter.
However, the abovementioned studies do not consider current measurement offsets generated by the current measurement path. Generally, the procedure of current measurement is as follows. Inverter output currents are transduced to voltage signals by current sensors and transformed into digital values via low-pass filters and analog-to-digital (A/D) converters. Through this current measurement path, current measurement offsets are inevitably generated and cause DC current components in real inverter output currents. Real inverter output currents with DC current components cause the DC-link capacitor voltage to oscillate at the frequency of the utility voltage. This ripple distorts inverter output current references and deteriorates the overall system performance. This approach is called a first-order ripple component in this study.
Calculating current offsets by reading the A/D converter repeatedly without current flowing is common practice. However, the effect of the thermal drift of analog devices and switching interference in actual operating conditions makes current offsets vary.
The distortion in inverter output current references caused by the first-order ripple component can be prevented with a notch filter whose center frequency is equal to the frequency of utility voltages. However, the DC components of real inverter output currents injected into the utility side are not eliminated. The problem in DC current injection can be simply solved with a utility frequency transformer. However, this transformer increases the cost and size and reduces system efficiency. Bhat and Dewan
[19]
proposed a solution based on a high-frequency transformer to decrease the size. However, this solution does not prevent the DC current components of currents injected into the utility side. For these reasons, different solutions have been proposed to remove DC current components
[20]
-
[22]
, but these solutions require additional elements or sensors.
The solution proposed in this study does not require additional elements and sensors, except for sensors that are necessary to control grid-connected inverters. The proposed solution is thus very cheap and easy to implement. It is also applicable regardless of the topology of grid-connected inverters.
In this study, we analyze how current measurement offsets cause DC current components in real inverter output currents and the first-order ripple component in the DC-link capacitor voltage. A compensation strategy is proposed to eliminate DC current components in real inverter output currents and obtain precise current control.
The remainder of this paper is organized as follows. The effect of current measurement offsets is described in Section II. The proposed compensation strategy is introduced and discussed in Section III. The validity of the proposed strategy is verified by simulations and experiments in Sections IV and V. Finally, the conclusions are presented in Section VI.
II. EFFECT OF CURRENT MEASUREMENT OFFSETS
- A. Single-phase Grid-connected Inverters
Fig. 2
presents the block diagram of the current control in consideration of the measurement offsets of the utility voltage and output current in single-phase grid-connected inverters. In
Fig. 2
,
δvg
and
δig
denote the measurement offsets in the utility voltage and the inverter output current, respectively, whereas
vg
_
m
and
ig
_
m
denote the measured utility voltage and inverter output current, respectively. On the assumption that the utility voltage is a complete sinusoidal wave as expressed in Equation (1), the inverter output current reference is expressed as Equation (2) so that active and reactive power may be regulated at the utility side, the pulse width modulation (PWM) is ideal, and the measurement offsets are constant. The inverter output current at the steady state in the current control using a proportional-integral-resonant (PIR) regulator (as expressed in Equation (3)) is expressed in Equation (4).
Block diagram of the current control in consideration of the measurement offsets in single-phase grid-connected inverters.
As Equation (4) shows, the current measurement offset causes the DC current component injected into the utility side in single-phase grid-connected inverters. At the steady state, using Equations (1) and (4) yields the inverter output voltage as follows:
If no power loss occurs in the inverter, the power supplied from the DC-link to the inverter is similar to the inverter output power and can be expressed as Equation (6).
where
If the DC-link capacitor voltage is maintained at the constant operating point (
Vdc
*
), the power absorbed in the DC-link capacitor can be obtained as follows:
Equation (7) shows that the current measurement offset causes the DC-link capacitor voltage to oscillate at the utility voltage frequency in single-phase grid-connected inverters. This ripple deteriorates the overall system performance because it generates inverter output current reference with harmonics; thus, the real inverter output current also has harmonic components.
- B. Three-phase Grid-connected Inverters
Fig. 3
presents the block diagram of the current control in consideration of the measurement offsets in three-phase grid-connected inverters. In
Fig. 3
, (
δeds
,
δeqs
) and (
δids
,
δiqs
) denote the stationary dq-axis measurement offsets of utility voltages and inverter output current, respectively, whereas (
eds
_
m
,
eqs
_
m
) and (
ids
_
m
,
iqs
_
m
) denote the stationary dq-axis measurement values of utility voltages and inverter output current, respectively. If the utility phase voltages are sinusoidal-balanced voltages, the stationary dq-axis voltages are expressed as Equation (8). The stationary dq-axis reference values of the inverter output phase current can be expressed as Equation (9) to control the active and reactive power at the utility side. Moreover, if the space vector pulse width modulation is ideal and the measurement offsets are constant, the stationary dq-axis output currents at the steady state in the current control system using a PIR regulator are expressed as Equation (10).
Block diagram of the current control in consideration of the measurement offsets in three-phase grid-connected inverters.
Equation (10) shows that the current measurement offsets cause DC current components injected into the utility side in three-phase grid-connected inverters. At the steady state, using Equations (8) and (10) yields stationary dq-axis inverter output voltages as follows:
If no power loss occurs in the inverter, the power supplied from the DC-link to the inverter is similar to the inverter output power and can be expressed as Equation (12).
where
If the DC-link capacitor voltage is maintained at the constant operating point (
Vdc
*
), the power absorbed in the DC-link capacitor can be obtained as follows:
Equation (13) shows that current measurement offsets cause the DC-link capacitor voltage to oscillate at the utility voltage frequency in three-phase grid-connected inverters. This ripple deteriorates the overall system performance because it generates inverter output current references with harmonics. Thus, real inverter output currents also have harmonic components.
III. DESIGN OF THE CURRENT OFFSET COMPENSATOR
- A. Single-phase Grid-connected Inverters
From Equation (7), the equation for the ripple component of the DC-link capacitor voltage can be calculated as follows:
Equation (14) can be approximated as Equation (15) because the magnitude of the utility voltage is much larger than the impedance drop (
vg
≫
ωLi Ide
*
,
ωLi Iqe
*
).
As shown in Equation (15), the second-order ripple component exists in single-phase grid-connected inverters. The band pass filter expressed in Equation (16) is used to detect the first-order ripple component included in the current measurement offset.
where
BW
and
ωBPF
are the bandwidth and the center frequency of the band pass filter, respectively. If
ωBPF
is similar to the utility frequency, the first-order ripple component can be obtained with
The first-order ripple component expressed in Equation (17) is then filtered through the all-pass filter expressed in Equation (18). When
ωAPF
is equal to the utility frequency, the all-pass filter generates a virtual component expressed as Equation (19), which leads the first-order ripple component by 90°.
By substituting Equations (17) and (19) into Equation (20), the magnitude of the first-order ripple component can be established as Equation (21).
The current measurement offset can be calculated with Equation (21), but the real value cannot be determined without exact parameter values. Moreover, the current measurement offset may be altered by external factors. Hence, a current offset controller is used to maintain the calculated first-order component at zero (
Fig. 4
).
Block diagram of a current offset controller in single-phase grid-connected inverters.
Fig. 5
presents the block diagram of a current control system using the proposed current offset compensator in single-phase grid-connected inverters. The current offset compensator is mainly composed of the first-order ripple component detector, the magnitude detector, and the current offset controller. In
Fig. 5
,
io
_
com
is a compensation value for the current measurement offset.
Block diagram of a current control system using the proposed current offset compensator in single-phase grid-connected inverters.
- B. Three-phase grid-connected inverters
From Equation (13), the equation for the ripple component of the DC-link capacitor voltage can be calculated as follows:
Equation (22) can be approximated as Equation (23) because the magnitude of the utility voltage is much larger than the impedance drop (
E
≫
ωLi Ide
*
,
ωLi Iqe
*
).
Using the all-pass filter expressed in Equation (18), the virtual component that leads the first-order ripple component by 90° can be obtained as follows:
The magnitude of the d-axis and q-axis voltage ripple can be obtained with Equation (26) by substituting Equations (23) and (24) into Equation (25).
Similar to single-phase grid-connected inverters, using a current offset controller (
Fig. 6
) is necessary.
Block diagram of a current offset controller in three-phase grid-connected inverters.
Fig. 7
presents the block diagram of a current control system using the proposed current offset compensator in three-phase grid-connected inverters. In
Fig. 7
,
idos
_
com
and
iqos
_
com
are stationary dq-axis compensation values for current measurement offsets.
Block diagram of a current control system using the proposed current offset compensator in three-phase grid-connected inverters.
IV. SIMULATION RESULTS
Simulations and experiments were conducted with a sample distributed generation system (
Fig. 8
) to investigate the effect of offsets in grid-connected inverters and to verify the performance of the proposed current offset compensator. In the sample distributed generation system, a new renewable energy source was modeled as a DC voltage source. The detailed parameters are listed in
Table I
. In the case of single-phase grid-connected inverters, a second-order voltage ripple that distorts the inverter output current inevitably exists in the DC-link capacitor voltage. A notch filter whose center frequency is twice the utility frequency was utilized to eliminate the effect of the ripple component.
Sample distributed generation system for simulations and experiments.
PARAMETERS OF THE SAMPLE DISTRIBUTED GENERATION SYSTEM
PARAMETERS OF THE SAMPLE DISTRIBUTED GENERATION SYSTEM
Fig. 9
shows an output of the current offset compensator in single-phase grid-connected inverters. In the figure, the output of the current offset compensator converges at 1 A at the steady state to eliminate the effect of the current measurement offset.
Output of the current offset compensator in single-phase grid-connected inverters.
Fig. 10
shows the DC-link capacitor voltage waveform in single-phase grid-connected inverters.
Fig. 10
(a) shows characteristics of transient and steady states before and after compensation.
Figs. 10
(b) and
10
(c) show the magnified waveform of the DC-link capacitor voltage at the steady state before and after compensation, respectively. Comparison of
Figs. 10
(b) and
10
(c) shows that the first-order ripple component disappeared after compensation, leaving only the second-order ripple component. This scenario is an inherent characteristic of single-phase grid-connected inverters.
Fig. 10
shows that the DC component in the real inverter output current also disappeared.
DC-link capacitor voltage in single-phase grid-connected inverters (a) before and after compensation of current measurement offset. (b) Steady state characteristic before compensation. (c) Steady state characteristic after compensation.
Fig. 11
shows the fast Fourier transform (FFT) analysis of the inverter output current at the steady state before and after compensation.
Fig. 11
(a) shows the DC and second-order harmonic components before compensation. The second-order harmonic component is caused by the first-order ripple component of the DC-link capacitor voltage. After compensation by the proposed method, the DC component and the second-order harmonic of the inverter output current are almost eliminated as shown in
Fig. 11
(b).
FFT analysis result of inverter output current at the steady state in single-phase grid-connected inverters (a) before compensation and (b) after compensation.
Fig. 12
shows the output of the current offset compensator in three-phase grid-connected inverters. Similar to single-phase grid-connected inverters, the current offset compensator calculates the compensation values at the steady state. The effect of the current measurement offset is thus eliminated.
Output of the current offset compensator in three-phase grid-connected inverters.
Fig. 13
shows the DC-link capacitor voltage waveform in three-phase grid-connected inverters.
Fig. 13
(a) shows the characteristics of transient and steady states before and after compensation.
Figs. 13
(b) and
13
(c) show the magnified waveform of the DC-link capacitor voltage at the steady state before and after compensation, respectively. Comparison of
Figs. 13
(b) and
13
(c) shows that the first-order ripple component disappeared after compensation.
Fig. 13
shows that the DC component in the real inverter output currents also disappeared.
DC-link capacitor voltage in three-phase grid-connected inverters (a) before and after compensation of current measurement offset. (b) Steady state characteristic before compensation. (c) Steady state characteristic after compensation.
Fig. 14
shows the FFT analysis of the inverter output current at the steady state before and after compensation.
Fig. 14
(a) shows the DC and second-order harmonic components before compensation. The second-order harmonic component is caused by the first-order ripple component of the DC-link capacitor voltage. After compensation by the proposed method, the DC component and the second-order harmonic of the inverter output current are almost eliminated as shown in
Fig. 14
(b).
FFT analysis result of inverter output current at the steady state in three-phase grid-connected inverters (a) before compensation and (b) after compensation.
V. EXPERIMENTAL RESULTS
The configuration of the experimental system is shown in
Fig. 8
, and the parameters are listed in
Table 1
. TMS320F2812 was employed as a digital signal processor (DSP) in the experiment, and LA25-NP was utilized as a current sensor. The range of the current input was designed to be between –15 A and 15 A. The transduced current signals were converted to digital values by 12-bit A/D converters, and all internal data in the DSP were displayed on an oscilloscope through a 12-bit D/A converter.
Fig. 15
shows the output of the current offset compensator in single-phase grid-connected inverters. The current measurement offset in the experiment is approximately –0.75 A. The result is similar to the simulation result in
Fig. 9
.
Output of the current offset compensator in single-phase grid-connected inverters.
The ripple component of the DC-link capacitor voltage in single-phase grid-connected inverters before and after compensation is shown in
Fig. 16
. The figure also shows that the results similar to those of the simulation (
Fig. 10
).
Ripple component of DC-link capacitor voltage in single-phase grid-connected inverters (a) before compensation and (b) after compensation.
An experiment for three-phase grid-connected inverters was also performed. The output of the current offset compensator is shown in
Fig. 17
. The current measurement offsets of the experimental systems are approximately –0.3 A and 0.3 A in the stationary d-axis and q-axis, respectively, similar to the simulation in
Fig. 12
.
Output of the current offset compensator in three-phase grid-connected inverters.
Fig. 18
shows the ripple component of the DC-link capacitor voltage in three-phase grid-connected inverters. As shown in
Fig. 18
, the first-order ripple component present before compensation is almost eliminated after compensation.
Ripple component of the DC-link capacitor voltage in three-phase grid-connected inverters (a) before compensation and (b) after compensation.
VI. CONCLUSIONS
In grid-connected inverters, current measurement offsets that are inevitably generated by the current measurement path cause DC current components in real inverter output currents. Real inverter output currents with DC components cause the DC-link capacitor voltage to oscillate at the frequency of the utility voltage. In this study, a compensation strategy to eliminate the effect of these current measurement offsets was proposed. The validity of the strategy was demonstrated through both simulations and experiments. The experimental results show that the DC components disappeared from inverter output currents after compensation. By changing the current regulator, the proposed compensation strategy can be applied to inverter output current references that include harmonics components, although only the fundamental component was considered in this study. If DC voltage components exist in real utility voltages, the proposed compensation strategy eliminates DC current components in real inverter output currents. The proposed compensation strategy can thus improve the overall system performance of grid-connected inverters.
BIO
Chang-Hee Lee received his B.S. and M.S. degrees in electrical engineering from Kyungpook National University, Daegu, Korea, in 2008 and 2012, respectively. His current research interests include power-electronic control of electric machines, systems that use renewable energy sources, and custom power devices.
Jong-Woo Choi received his B.S., M.S., and Ph.D. degrees in electrical engineering from Seoul National University, Seoul, Korea, in 1991, 1993, and 1996, respectively. He worked as a research engineer at LG Industrial Systems Company from 1996 to 2000. Since 2001, he has been a faculty member of the Department of Electrical Engineering, Kyungpook National University, Daegu, Korea, where he is currently a professor. His current research interests include static power conversion and electric machine drives.
Carrasco J. M.
,
Franquelo L. G.
,
Bialasiewicz J. T.
,
Galvan E.
,
Guisado R. C. P.
,
Prats Mz. A. M.
,
Leon J. I.
,
Moreno-Alfonso N.
2006
“Power-Electronic systems for the grid integration of renewable energy sources: A survey,”
IEEE Trans. Ind. Electron.
53
(4)
1002 -
1016
DOI : 10.1109/TIE.2006.878356
Min B. D.
,
Lee J. P.
,
Kim J. H.
,
Kim T. J.
,
Yoo D. W.
,
Ryu K. R.
,
Kim J. J.
,
Song E. H.
2008
“A novel grid-connected PV PCS with new high efficiency converter,”
Journal of Power Electronics
8
(4)
309 -
316
Jeong J. K.
,
Han B. M.
,
Lee J. Y.
,
Choi N. S.
2011
“High-efficiency grid-tied power conditioning system for fuel cell power generation,”
Journal of Power Electronics
11
(4)
551 -
560
DOI : 10.6113/JPE.2011.11.4.551
Kirubakaran K.
,
Jain S.
,
Nema R. K.
2011
“DSP-controlled power electronic interface for fuel-cell-based distributed generation,”
IEEE Trans. Power Electron.
26
(12)
3853 -
3864
DOI : 10.1109/TPEL.2011.2138162
Singh B.
,
Al-Haddad K.
,
Chandra A.
1999
“A review of active filters for power quality improvement,”
IEEE Trans. Ind. Electron.
46
(5)
960 -
971
DOI : 10.1109/41.793345
Adel Mohamed
,
Zaid Sherif
,
Mahgoub Osama
2011
“Improved active power filter performance based on an indirect current control technique,”
Journal of Power Electronics
11
(6)
931 -
937
DOI : 10.6113/JPE.2011.11.6.931
Kwan K. H.
,
So P. L.
,
Chu Y. C.
2012
“An output regulation-based unified power quality conditioner with Kalman filters,”
IEEE Trans. Ind. Electron.
59
(11)
4248 -
4262
DOI : 10.1109/TIE.2012.2193852
IEEE Standard for Interconnecting Distributed Resources with Electric Power Systems, IEEE Standard 1547-2003
Infield D. G.
,
Onions P.
,
Simmons A. D.
,
Smith G. A.
2004
“Power quality from multiple grid-connected single-phase inverters,”
IEEE Trans. Power Del.
19
(4)
1983 -
1989
DOI : 10.1109/TPWRD.2004.829950
Gertmar L.
,
Karlsson P.
,
Samuelsson O.
2005
“On DC injection to AC grids from distributed generation,”
in Proc. Eur. Conf. Power Electron. Appl.
10 -
Kazmierkowski M. P.
,
Malesani L.
1998
“Current control techniques for three-phase voltage-source PWM converters: a survey,”
IEEE Trans. Ind. Electron.
45
(5)
691 -
703
DOI : 10.1109/41.720325
Kim R. Y.
,
Choi S. Y.
,
Suh I. Y.
2004
“Instantaneous control of average power for grid tie inverter using single phase D-Q rotating frame with all pass filter,”
in Proc. IEEE 30th Annu. IEEE IECON
Vol. 1
274 -
279
Zmood D. N.
,
Holmes D. G.
,
Bode G. H.
2001
“Frequency-domain analysis of three-phase linear current regulators,”
IEEE Trans. Ind. Appl.
37
(2)
601 -
610
DOI : 10.1109/28.913727
Zmood D. N.
,
Holmes D. G.
2003
“Stationary frame current regulation of PWM inverters with zero steady-state error,”
IEEE Trans. Power Electron.
18
(3)
814 -
822
DOI : 10.1109/TPEL.2003.810852
Teodorescu R.
,
Blaabjerg F.
,
Liserre M.
,
Loh P. C.
2006
“Proportional-resonant controllers and filters for grid-connected voltage-source converters,”
IEE Proc.-Electr. Power Appl.
153
(5)
750 -
762
DOI : 10.1049/ip-epa:20060008
Jiang S.
,
Cao D.
,
Li Y.
,
Peng F. Z.
2012
“Grid-connected boost-half-bridge photovoltaic microinverter system using repetitive current control and maximum power point tracking,”
IEEE Trans. Power Electron.
27
(11)
4711 -
4722
DOI : 10.1109/TPEL.2012.2183389
Hang L.
,
Liu S.
,
Yan G.
,
Qu B.
,
Lu Z.
2011
“An improved deadbeat scheme with fuzzy controller for the grid-side three-phase PWM boost rectifier,”
IEEE Trans. Power Electron.
26
(4)
1184 -
1191
DOI : 10.1109/TPEL.2010.2089645
Suul J. A.
,
Ljokelsoy K.
,
Midtsund T.
,
Undeland T.
2011
“Synchronous reference frame hysteresis current control for grid converter applications,”
IEEE Trans. Ind. Appl.
47
(5)
2183 -
2194
DOI : 10.1109/TIA.2011.2161738
Bhat A. K. S.
,
Dewan S. B.
1988
“A novel utility interfaced high-frequency link photovoltaic power conditioning system,”
IEEE Trans. Ind. Electron.
35
(1)
153 -
159
DOI : 10.1109/41.3079
Blewitt W. M.
,
Atkinson D. J.
,
Kelly J.
,
Lakin R. A.
2010
“Approach to low-cost prevention of DC injection in transformerless grid connected inverters,”
IET Power Electron.
3
(1)
111 -
119
DOI : 10.1049/iet-pel.2008.0319
Bowtell L.
,
Ahfock A.
2010
“Direct current offset controller for transformerless single-phase photovoltaic grid-connected inverters,”
IET Renew. Power Gen.
4
(5)
428 -
437
DOI : 10.1049/iet-rpg.2009.0043
Buticchi G.
,
Lorenzani E.
,
Franceschini G.
2011
“A DC offset current compensation strategy in transformerless grid-connected power converters,”
IEEE Trans. Power Del.
26
(4)
2743 -
2751
DOI : 10.1109/TPWRD.2011.2167160