Applicability of Messenger Wire for Purpose of Lightning Protection
Applicability of Messenger Wire for Purpose of Lightning Protection
Journal of Electrical Engineering and Technology. 2016. Jan, 11(1): 167-174
Copyright © 2016, The Korean Institute of Electrical Engineers
  • Received : December 02, 2014
  • Accepted : July 31, 2015
  • Published : January 01, 2016
Download
PDF
e-PUB
PubReader
PPT
Export by style
Article
Author
Metrics
Cited by
TagCloud
About the Authors
Hun Chul Seo
School of IT Engineering, Yonam Institue of Digital Technolgy, Korea. (hunchul12@yc.ac.kr)
Joon Han
College of Information and Communication Engineering, Sungkyunkwan University, Korea. (j3angh@gmail.com)
Sun Kyu Choi
Power System Laboratory, KEPRI, Korea (skchoi@kepco.co.kr,leebs@kepri.re.kr)
Byung Sung Lee
Power System Laboratory, KEPRI, Korea (skchoi@kepco.co.kr,leebs@kepri.re.kr)
Sang Bong Rhee
Department of Electrical Engineering, Yeungnam University, Korea (rrsd@yu.ac.kr)
Chul Hwan Kim
Corresponding Author: College of Information and Communication Engineering, Sungkyunkwan University, Korea. (hmwkim@hanmail.net)

Abstract
The Korean distribution line currently consists of overhead ground wires (OHGW), overhead distribution lines, neutral wires (NW), and messenger wires (MW). The MW is installed under the NW. The lightning protection system in Korea is focused on OHGW and lightning arrester and the MW are not considered. Therefore, this paper proposes the applicability of MW for purpose of lightning protection. For this, we analyzed the effects of lightning overvoltage according to the existence of OHGW and MW and the grounding conditions of the MW in the Korean distribution system. The grounding conditions of the MW that we took into consideration were the common or separate grounding of the MW and NW. The analysis based on the equivalent circuit of the distribution pole at each condition was performed. The distribution lines and lightning were modeled using the Electromagnetic Transients Program (EMTP). For each of the installation conditions of the OHGW and MW, the various lightning conditions were simulated and analyzed for both direct and indirect lightning. The simulation results showed that, if the OHGW was not installed in the Korean distribution system, the lightning overvoltage could be reduced by the common grounding of the MW and NW.
Keywords
1. Introduction
The Korea Electric Power Corporation (KEPCO) distribution system uses 22.9 [kV] Y-connected, three-phase, four-wire, high-tension lines. Fig. 1 shows the structures of one-step type (single circuit pole) and two-step type poles (double circuit pole) [1] . As shown in Fig. 1 , the distribution line consists of the overhead ground wire (OHGW), overhead distribution line, neutral wire (NW), and messenger wire (MW). The MW is a wire or cable that is used solely for the physical support of another element, typically communication wire in KEPCO’s distribution line. The MW is installed under the NW.
PPT Slide
Lager Image
Structural diagram of pole types
Lightning may cause flashovers on the distribution lines from both direct strikes and the induced voltage from nearby strikes. Direct lightning strikes to distribution lines mostly cause flashovers. Lightning-induced voltages are a major issue for the electromagnetic compatibility and power quality due to the widespread use of sensitive devices connected to the distribution lines. The lightning performance for lightning protection has been studied by many researchers [2 - 9] . These are mainly focused on the calculation of overvoltage or flashover rate at various configurations of lightning protection system, such as ground wire, lightning arrester, grounding resistance, and etc. However, the previous study considering the existence of MW under NW has not been performed.
The Korean distribution line includes various types of equipment, such as the OHGW and lightning arrester, to protect against lightning. However, the lightning protection system of Korea does not take into consideration the existence of MW under NW.
Therefore, this paper proposes the applicability of MW for purpose of lightning protection. To verify the applicability of MW, we analyzed the effects of lightning overvoltage according to the installation conditions of the OHGW and MW in the Korean distribution system. The conditions taken into consideration were the existence of the OHGW and MW as well as the common or separate grounding of the MW and NW. In Section 2, when the MW is considered for lightning protection, the equivalent circuit analysis was performed to describe the differences between the common and separate grounding of the MW and NW. The modeling of distribution line and lightning using the Electromagnetic Transients Program (EMTP) is discussed in Section 3. In Section 4, the simulation of the various lightning magnitudes, ground resistivity, and lightning locations for each installation condition of the OHGW and MW for both direct and indirect lightning is discussed. Based on the simulation results, the lightning overvoltage according to the installation conditions of the OHGW and MW was analyzed. Finally, the conclusions are discussed.
2. Theoretical Analysis of Lightning Overvoltage Considering MW
The previous study to consider the MW for lightning protection has not been performed. Therefore, firstly, to discuss the applicability as a new purpose of MW, a theoretical analysis to calculate the lightning overvoltage is required.
This paper performs the theoretical analysis of overvoltage using equivalent circuit when both MW and NW exist. Specially, grounding conditions of the MW is discussed because the lightning overvoltage is affected from grounding conditions. We assume that first reflection wave is only considered because the magnitude of surge is damped by resistance of line as time elapses and the mutual coupling between two wires is neglected.
Fig. 2 shows the equivalent circuit of the distribution pole when the common grounding of MW and NW was used. The meaning of each parameter used in Fig. 2 is presented in Table 1 .
PPT Slide
Lager Image
Equivalent circuit when the messenger wire and neutral wire were commonly grounded
Meaning of each parameter inFig. 2
PPT Slide
Lager Image
Meaning of each parameter in Fig. 2
The phase conductor to the neutral wire voltage, V com, can be written as follows:
PPT Slide
Lager Image
In (1), V ncom is the sum of the voltage drop between NW and MW and the voltage drop between MW and the ground, which can be written as follows:
PPT Slide
Lager Image
In (2), voltage drop considering reflection wave is calculated. If we apply Kirchhoff’s current law at the common node of NW and MW, then I g1 = I g2 + 2I g3 and, therefore, I g2 , can be written as follows:
PPT Slide
Lager Image
By substituting (3) to (2), V ncom can be written as follows:
PPT Slide
Lager Image
In the case of separate grounding, the phase conductor to the neutral wire voltage can be derived by equivalent analysis of the distribution pole. Fig. 3 shows the equivalent circuit of the distribution pole when the MW and NW were grounded separately. In addition, the meaning of each parameter in Fig. 3 is presented in Table 2 .
PPT Slide
Lager Image
Equivalent circuit when the messenger wire and neutral wire were grounded separately
Meaning of each parameter inFig. 3
PPT Slide
Lager Image
Meaning of each parameter in Fig. 3
Similar to (1), the phase conductor to neutral wire voltage V sep can be written as follows:
PPT Slide
Lager Image
where V nsep is the voltage drop between NW and the ground and can be written as:
PPT Slide
Lager Image
For comparison of (4) and (6), we need some assumptions. Regardless of the grounding of the MW and NW, the type and length of the down conductor were the same, as was the grounding resistance. Therefore, (7) can be derived from (4) and (6) as follows:
PPT Slide
Lager Image
Also, when lightning occurred, the current toward the down conductor for grounding was the same and, therefore, (8) can be derived from (4) and (6) as follows:
PPT Slide
Lager Image
We can assume Z g1 ≒0 in (4) because the line length between NW and MW is much shorter than between MW and ground. This derives Z g2 = Z sep1 from (7).
Then, if we apply above assumptions and then subtract (6) from (4), (9) can be derived
PPT Slide
Lager Image
In other words, the magnitude of V ncom was smaller than V nsep . Also, V p is smaller than V ncom and V nsep . Finally, we compared the absolute values of (1) and (5) as follows:
PPT Slide
Lager Image
From (10), we can conclude that the overvoltage with the common grounding of MW and NW is smaller than that with separate grounding. This result means that the MW connected with common grounding with NW is applicable as new purpose for lightning protection.
3. Modeling of Distribution Line and Lightning
- 3.1 Modeling of distribution line
The modeling of the Korean distribution line using EMTP is discussed. Fig. 4 shows the configuration of pole in Korean distribution line. The geometrical arrangement of phase conductors, OHGW, NW, and MW is represented in Fig. 4 . The meaning of number in brackets of Fig. 4 is the horizontal and vertical distance of wires from ground.
PPT Slide
Lager Image
Configuration of pole in Korean distribution line
The types of overhead distribution line, OHGW, and NW modeled in this study were the Aluminum Conductor Steel-Reinforced (ACSR) 95[mm 2 ], WO 32[mm 2 ], and ACSR 60[mm 2 ], respectively. The type of MW was the FS 38[mm 2 ]. The installation height of the MW was 10.5m [10 - 11] . Fig. 5 shows the EMTP modeling of the distribution line not including the OHGW but including the MW.
PPT Slide
Lager Image
Modeling of the distribution line using EMTP/ATPDraw
- 3.2 Modeling of down conductor for grounding
The down conductor for grounding was also modeled using the EMTP. It was modeled by the transmission line in order to take into consideration the propagation and reflection of the lightning current at the ground. The model was characterized by the characteristic impedances and propagation velocity. The following expression is introduced to represent the characteristic impedance of a vertical conductor [12 - 13] :
PPT Slide
Lager Image
where h is the height of the vertical conductor, and r is the radius of the vertical conductor.
The type of down conductor modeled in this study was the OW 25[mm 2 ]. In this type of conductor, r was 3.21 [mm] and h was varied by the length of the down conductor. At each condition, the characteristic impedance was calculated using (10). The propagation velocity was considered as a light velocity.
For the case of direct lightning, the surge characteristics of the concrete pole were added. The radius and height of the concrete pole were 0.138m and 13.5m, respectively. The surge impedance was calculated by (10). Also, the propagation velocity was inputted as the light velocity.
- 3.3 Modeling of lightning arrester
The modeling of lightning arrester using EMTP is discussed. The type of lightning arrester modeled is Gapless ZnO for distribution line. The rated and discharge voltage of ZnO lightning arrester for distribution line is 18[kV] and below 66[kV], respectively. The NLRES Type 92 component provided by EMTP is used to model the lightning arrester in this paper. Fig. 6 shows the input screen of V-I characteristics of ZnO lightning arrester using EMTP.
PPT Slide
Lager Image
Modeling of the lightning arrester using EMTP/ATPDraw
- 3.4 Modeling of direct and indirect lightning
Direct and indirect lightning are classified by the striking distance based on IEEE Std. 1410 [14] .
The waveform of direct lightning is modeled by EMTP/ MODELS based on the analytical formulation of the Heidler type [15] . The modeled waveform was 2/70[μs] and was connected to the overhead ground wire or phase conductor by a type 60 TACS source in the EMTP.
There have been many studies conducted on the overvoltage due to indirect lightning [2 - 8 , 16] . This paper calculates the lightning-induced voltage on the overhead line using the method proposed by H. K. Hoidalen [16] , which has been implemented using the EMTP/MODELS.
4. Simulation and Discussion
- 4.1 Simulation model
This paper models the standard distribution system with a total length of 2[km] in Korea as shown in Fig. 7 . The spacing between the two adjacent groundings of the OHGW was 200[m], and the grounding resistance of the OHGW was 50[Ω]. A lightning arrester was installed every 500[m], and the grounding resistance of each lightning arrester was 25[Ω]. These values of interval and resistance are the standard value of KEPCO’s distribution line in Korea. Some part of modeling of this standard distribution system using EMTP is represented in Fig. 8 .
PPT Slide
Lager Image
Standard configuration of Korean distribution system
PPT Slide
Lager Image
Modeling of standard distribution system in Korea using EMTP
- 4.2 Simulation conditions
The lightning protection system in Korea does not currently account for the MW. If the effect of the MW is taken into consideration, then the lightning protection system in relation to the economics can be established. Therefore, we set the simulation conditions in this paper as described in Table 3 in order to analyze the effects of the MW in the distribution line without OHGW.
Simulation conditions
PPT Slide
Lager Image
Simulation conditions
In case 2, 3 and 5 and 6, the common or separate groundings of the MW and NW were compared in order to determine the grounding method of the MW and NW. For each case in Table 3 , direct and indirect lightning strikes were simulated. In the case of direct lightning, lightning magnitudes of 4.4[kA], 10[kA], and 30[kA] were simulated, while lightning magnitudes of 20[kA], 50[kA], and 100 [kA] were simulated in the case of indirect lightning. The flashover by direct lightning may be occurred by low discharge current, while the possibility of flashover by indirect lightning is high at high discharge current. Therefore, the lightning magnitudes are set differently according to the lightning type. The 100[kA] is applied as maximum lightning magnitude to simulate the flashover by indirect lightning as worst case. Ground resistivity values of 100[Ω·m] and 300 [Ω·m] were simulated for both direct and indirect lightning.
The lightning locations are marked in Fig. 7 . The meanings of lightning locations taken into consideration were as follows:
① Pole where the grounding resistance of OHGW was 50 [Ω] and a lightning arrester was installed;
② Pole where the grounding resistance of OHGW was 300 [Ω] and a lightning arrester was not installed; and
③ Pole where the grounding resistance of OHGW was 50 [Ω] and a lightning arrester was not installed.
In simulation of direct lightning, we did not consider the shielding effect for worst case simulation. In case of indirect lightning, the distance between distribution line and lightning location is determined by striking distance ymin calculated by (12) [14] . Because each lightning event has a different magnitudes, the striking distance is different in each lightning event.
PPT Slide
Lager Image
where
rs : striking distance to overhead line( rs = 10 IP 0.65 )[m]
rg : striking distance to ground( rg = 0.9 rs )[m]
h : height of distribution line [m]
The flashover voltages of line post insulator and suspension insulator are 180[kV] and 230[kV], respectively. The low flashover voltage, i.e. 180[kV], is used at analysis of simulation results for worst case.
- 4.3 Simulation results of direct lightning
Fig. 9 shows the simulation results of direct lightning when the lightning magnitude was 4.4[kA] and the ground resistivity was 100[Ω‧ m]. Case 1 and Case 2 had the smallest overvoltage regardless of the lightning location. The overvoltage values of case 1 and 2 are very similar. In lightning location ② and ③ of case 4 and 6, the flashover is occurred, but it does not occurred at case 1, 2, 3, and 5. Figs. 10 and 11 show the simulation results of direct lightning when the lightning magnitude was 10[kA] and 30 [kA], respectively. Except for lightning location ①, the flashover is occurred at all of cases due to high lightning current. When the installation conditions of the OHGW and MW were equal, lightning location ① had the smallest overvoltage. This result was due to the existence of the lightning arrester at lightning location ①. If we compared the lightning at the pole without the lightning arrester, i.e., lightning locations ② and ③, the lower grounding resistance of the OHGW led to the smaller overvoltage.
PPT Slide
Lager Image
Simulation results for direct lightning when the lightning magnitude was 4.4kA and the ground resistivity was 100Ω·m
PPT Slide
Lager Image
Simulation results for direct lightning when the lightning magnitude was 10kA and the ground resistivity was 100Ω·m
PPT Slide
Lager Image
Simulation results for direct lightning when the lightning magnitude was 30kA and the ground resistivity was 100Ω·m
Although this paper does not include the simulation results when the ground resistivity was 300[Ω‧ m], the tendency of the simulation results indicates that it would be equal to that when the ground resistivity was 100[Ω·m].
- 4.4 Simulation results of indirect lightning
Figs. 12 , 13 , and 14 show the simulation results for indirect lightning when the lightning magnitude was 20 [kA], 50[kA], and 100[kA], respectively, and the ground resistivity was 100[Ω·m]. From Fig. 12 and 13 , we can find that the induced voltage in case 1, 2, 3 and 5 is lower than the one in case 4 and 6 at all of lightning locations. In Fig. 14 , the flashover is occurred except for lightning location ①.
PPT Slide
Lager Image
Simulation results for indirect lightning when the lightning magnitude was 20kA and the ground resistivity was 100Ω·m
PPT Slide
Lager Image
Simulation results for indirect lightning when the lightning magnitude was 50kA and the ground resistivity was 100Ω·m
PPT Slide
Lager Image
Simulation results for indirect lightning when the lightning magnitude was 100kA and the ground resistivity was 100Ω·m
- 4.5 Discussion
We simulated both direct and indirect lightning. Regardless of the lightning magnitude, lightning location, and ground resistivity, the ascending order of the lightning overvoltage by direct and indirect lightning according to the installation conditions of the OHGW and MW was as follows:
① Case 1: With OHGW / Without MW, = Case 2: With OHGW / With MW (common grounding of MW and NW),
② Case 3: With OHGW / With MW (separate grounding of MW and NW),
③ Case 5: Without OHGW / With MW (common grounding of MW and NW),
④ Case 4: Without OHGW / Without MW, and
⑤ Case 6: Without OHGW / With MW (separate grounding of MW and NW).
The overvoltage values in cases with OHGW are lower than cases without OHGW. The difference of overvoltage between case 1, 2, and 3 is very small. Here, we focus on case 5. From Figs. 9 , 12 , and 13 , we can find that the difference of overvoltage between case 3 and 5 is small. However, the one between case 5 and 4 is over 15[kV] in Fig. 12 and 30[kV] in Fig. 13 .
Table 4 and 5 show the occurrence of flashover at all of simulation cases. ‘○’ means that flashover is occurred, while ‘X’ means that flashover is not occurred. In case of direct lightning with 4.4[kA], the flashover is not occurred at case 1, 2, 3, and 5, however, the flashover is occurred at case 4 and 6. At another simulation cases, the occurrence or not of flashover is equal.
Occurrence of flashover at each case in case of direct lightning
PPT Slide
Lager Image
Occurrence of flashover at each case in case of direct lightning
Occurrence of flashover at each case in case of indirect lightning
PPT Slide
Lager Image
Occurrence of flashover at each case in case of indirect lightning
From these discussions, we can find that if the MW with common grounding with NW is installed in distribution line without OHGW, the lightning overvoltage is nearly equal in case of distribution line with OHGW. In other words, although the OHGW does not exist, the lightning performance can be maintained by installation of MW with common grounding with NW.
Therefore, we can conclude that the MW can be applicable as purpose of lightning protection as well as natural purpose.
5. Conclusion
The MW is a wire or cable used for the physical support of another element. This paper proposes the applicability of MW as a purpose of lightning protection. To verify this possibility, we perform the theoretical analysis of overvoltage considering MW and simulate the lightning overvoltage according to the installation conditions of OHGW and MW in the Korean distribution system. From the simulation results, we can find that when the OHGW was not installed but the MW with common grounding with NW was installed, the overvoltage could be reduced due to the common grounding and hence the occurrence possibility of flashover can be reduced. Therefore, this paper can conclude that if the MW was installed and the OHGW was removed from the distribution line for which the probability of direct lightning was low, the lightning protection system could be maintained by the common grounding of the MW and NW, i.e. the MW can be applicable as a new purpose of lightning protection.
GW has a function of reducing electromagnetic field besides lightning protection function. This paper proposes the applicability of MW only focusing on lightning protection function of OHGW. To perfectly replace the OHGW to MW, the several points of view such as reducing electromagnetic field, economics, and etc. must be considered.
BIO
Hun-Chul Seo He received his B.S, M.S, and Ph. D. degrees from Sungkyunkwan University, Korea, 2004, 2006, and 2013, respectively. He worked for Korea Electrical Engineering & Science Institute, Seoul, Korea, as a researcher in power system division from 2006 to 2009. He was a postdoctoral fellow in the dept. of electrical engineering, Yeungnam University, Korea, from Sep. 2013 to Jan. 2014. From Mar. 2014, he is an assistant professor with the School of IT Engineering at Yonam Institute of Digital Technology, Korea. His research interests include power system transients, protection and stability.
Joon Han He received his B.S degree in School of Electrical Engineering from Soonchunhyang University, Korea, 2011 and M.S degree in College of Information and Communication Engineering from Sungkyunkwan University, Korea, 2013. At present, he is working on his Ph. D thesis at Sungkyunkwan University. His research interests include power system transients, protection and DC distribution system.
Sun-Kyu Choi He received his B.S and M.S degrees in School of Electrical Engineering from Korea University, Korea, 2000 and 2002. He has been with KEPRI, KEPCO, as a member of the researcher since 2003. His special fields of interest are a grounding method, lightning protection and power quality of distribution system.
Byung-Sung Lee He received his Ph.D from Chungnam National University in 2006 in high voltage engineering. He has been with KEPRI, KEPCO, as a member of the researcher since 1995. His special fields of interest are the intelligent distribution automation system, RCM of distribution facilities and lightning protection, and the lifetime estimation of distribution equipments.
Sang-Bong Rhee He received his B.S, M.S, and Ph.D. degrees from Hanyang University, Korea, in 1994, 1999, and 2004, respectively. He was a research professor in the School of Electrical and Computer Engineering, Sungkyunkwan University, Korea. Currently, he is an assistant professor with the dept. of electrical engineering at Yeungnam University, Korea. His research interests include a distribution system control and operation, and artificial intelligence applications to power system protection.
Chul-Hwan Kim In 1990 he joined Cheju National University, Cheju, Korea, as a full-time Lecturer. He has been a visiting academic at the University of BATH, UK, in 1996, 1998, and 1999. Since March 1992, he has been a professor in the School of Electrical and Computer Engineering, Sungkyunkwan University, Korea. His research interests include power system protection, artificial intelligence application for protection and control, the modeling / protection of underground cable and EMTP software. He received his B.S and M.S degrees in Electrical Engineering from Sungkyunkwan University, Korea, 1982 and 1984, respectively. He received a Ph.D in Electrical Engineering from Sungkyunkwan University in 1990. Currently, he is a director of Center for Power IT(CPIT) in Sungkyunkwan University.
References
Park Keon Woo , Seo Hun Chul , Kim Chul Hwan , Jung Chang Soo , Yoo Yeon Pyo , Lim Yong Hoon 2009 “Analysis of the Neutral Current for Two-Step-Type Poles in Distribution Lines” IEEE Transactions on Power Delivery 24 (3) 1483 - 1489    DOI : 10.1109/TPWRD.2009.2021031
Chisholm W. A. , Cummins K.L. “Lightning protection of Smart Grid components” International Symposium on Lightning Protection 2011 October 3-7, 2011
Paolone Mario , Nucci Carlo Alberto , Petrache Emanuel , Rachidi Farhad 2004 “Mitigation of Lightning-Induced Overvoltages in Medium Voltage Distribution Lines by Means of Periodical Grounding of Shielding Wires and of Surge Arresters: Modeling and Experimental Validation” IEEE Trans. On Power Delivery 19 (1) 423 - 431    DOI : 10.1109/TPWRD.2003.820196
Borghetti Alberto , Nucci Carlo Alberto , Paolone Mario 2007 “An Improved Procedure for the Assessment of Overhead Line Indirect Lightning Performance and Its Comparison with the IEEE Std. 1410 Method” IEEE Transactions on Power Delivery 22 (1) 684 - 692    DOI : 10.1109/TPWRD.2006.881463
Yokoyama S. , Yamamoto K. , Kinoshita H. 1985 “Analogue simulation of lightning induced voltages and its application for analysis of overhead-ground-wire effects,” Proc. Inst. Elect. Eng 132 (C- 4) 208 - 216
Rakov V. , Rachidi F. 2009 “Overview of recent progress in lightning research and lightning protection” IEEE Trans. on Electromagnetic Compatibility 51 (3) 428 - 442    DOI : 10.1109/TEMC.2009.2019267
CRIEPI 2002 “Guide of Lightning Protection Design for Power Distribution Lines” JAPAN
Ametani , Kawamura T. 2005 “A Method of a Lightning Surge Analysis Recommended in Japan using EMTP” IEEE Trans. On Power Delivery 20 (2) 867 - 875
Motoyama H. , Kinoshita Y. , Nonaka K. 2008 “Experimental study on lightning surge response of 500-kV transmission tower with overhead lines” IEEE Trans. Power Delivery 23 (4) 2488 - 2495    DOI : 10.1109/TPWRD.2008.921138
Seo Hun Chul , Kim Chul Hwan 2012 “Analysis of Stability of PV System using the Eigenvalue according to the Frequency Variation and Requirements of Frequency Protection” Journal of Electrical Engineering & Technology 7 (4) 480 - 485    DOI : 10.5370/JEET.2012.7.4.480
Kim In Soo , Han Woong , Yeo Sang Min , Kim Chul Hwan , Weon Bong Ju , Lim Yong Hun 2009 “A Study on Shielding Effect of the Messenger Wires in Distribution Lines” Trans. KIEE 58 (3) 431 - 436
Jordan C. A. 1934 “Lightning computations for transmission lines with overhead ground wires, Part II,” Gen. Electr. Rev 37 (4) 180 - 186
De Conti Alberto , Visacro Silvério , Soares Amilton , Schroeder Marco Aurélio 2006 “Revision, Extension, and Validation of Jordan’s Formula to Calculate the Surge Impedance of Vertical Conductor” IEEE Trans. on Electromagnetic Compatibility 48 (3)
“Guide for improving the lightning performance of electric power overhead distribution lines”, IEEE Std 1410, 2010, IEEE Working Group on the lightning performance of distribution lines
Heidler F. , Cvetic J. M. , Stantic B. V. 1999 “Calculation of lightning current parameters” IEEE Trans. On Power Delivery 14 (2) 399 - 404    DOI : 10.1109/61.754080
Hoidalen Hans Kristian 2003 “Analytical Formulation of Lightning-Induced Voltages on Multiconductor Overhead Lines Above Lossy Ground” IEEE Transactions on Electromagnetic Compatibility 45 (1) 92 - 100    DOI : 10.1109/TEMC.2002.804772