In the series hybrid active power filter (SHAPF) with magnetic flux compensation (MFC), the system current oscillate in the experimental results when adding the same phase harmonic current command in current control block. This condition endangers the security of the SHAPF. Taking the digit period average arithmetic as example, this paper explains the inter-harmonics current oscillation in the experiment. The conclusion is that the SHAPF is unstable to the inter-harmonics current in theory. Limited by the capacity of the inverter, the system current and the inverter output current do not increase to infinite. At last, some methods are proposed to solve this problem. From the practical viewpoint, the voltage feed-forward control is easy to achieve. It can suppress the current oscillation problems, and also improve the filtering effect. The feasibility of the methods is validated by both the emulation and experiment results.
1. Introduction
As the wide application of power electronic equipments and nonlinear loads, the harmonic propagation in power distribution systems become a serious problem in the recent decades. In order to suppress harmonics, many methods have been proposed. Shunt passive power filters (PPF) have been widely used to keep harmonic contamination within acceptable limits. However, shunt PPF have many disadvantages in practical application
[1
-
2]
. They may cause resonance and the impedance of the power system strongly affects the filtering effects. To overcome these disadvantages, Active Power Filter (APF) has been proposed
[3
-
8]
. A novel principle of magnetic flux compensation (MFC) is proposed in reference
[7]
, which has been applied in series hybrid APF
[7
-
8]
, controllable reactor
[9]
, and shunt hybrid APF
[10]
. In the series hybrid APF, the series transformer works as a controlled reactor. The series transformer exhibits primary leakage impedance to the fundamental current and magnetizing impedance to the harmonic current with the proper control of pulse-width modulation (PWM) inverters, then the harmonic currents are forced to flow into the passive filter.
Since the series hybrid APF requires the series transformer exhibits low impedance to the fundamental current and high impedance to the harmonic current, a low pass filter (LPF) is needed in the current control block to separate the fundamental current and harmonic current from the system current
I
1
. The properties of the actual LPF algorithm cannot be ideal. Some specific frequency inter-harmonics (Non-integer harmonics) may pass through the LPF and affect the inverter output current. As a result, the series transformer equivalent impedance to inter-harmonics is not equal to the equivalent impedance to harmonics. But in reference
[7
-
8]
and
[11]
, this difference was ignored. All of them do not consider the properties of the LPF. They just simply separate the actual APF circuit to the fundamental equivalent circuit and harmonic (including inter-harmonics) equivalent circuit. In each equivalent circuit, the reference current
I
ref
is proportional to the primary winding current of series transformer
I
1
. The equivalent impedance of the series transformer to the inter-harmonics has not been discussed independently. For this reason, the theoretical analysis and conclusions in reference
[7
-
8]
and
[11]
about the equivalent impedance of transformer are incorrect. In experimental, inter-harmonics oscillation phenomenon occurred when compensate both fundamental and harmonics current. The traditional analytical method cannot explain this inter-harmonics oscillation phenomenon.
This article firstly introduce in basic filtering principle of the series hybrid APF based on MFC, then explain the reason of the inter-harmonics oscillation phenomenon when compensating both fundamental and harmonics current by the inverter. The essence of the inter-harmonics oscillation is that the APF system is unstable to the inter-harmonics. Finally, voltage feed-forward control method is proposed to suppress the inter-harmonics oscillation.
2. Working Principle
Fig. 1
shows the T-type equivalent circuit of a single phase series transformer. Assume all parameters in
Fig. 1
are the equivalent value after winding convert.
r
1σ
,
L
1σ
, and
r
2σ
,
L
2σ
represent the leakage impedance of the primary and secondary winding of the transformer;
r
m
and
L
m
represent the magnetizing impedance;
i
1
is the current in the primary winding;
i
2
, which is generated by a PWM inverter, is also the current in the secondary winding. It contains −
α
times of the fundamental current and
β
times of the harmonic current of
I
1.
That is to say:
Equivalent T-type circuit of series transformer
The leakage inductance can be ignored since
L
m
>>
L
1σ
+
L
2σ
. The resistance of the series transformer can also be ignored since they are very small. Hence the voltage equation of the transformer primary winding is:
where:
ω
– the fundamental angular frequency
In Eq. (2), 0 <
α
≤ 1,
β
> 0. If
α
is equal to 1, the series transformer will established nearly zero impedance to the fundamental, and (1 +
β
) times magnetizing impedance to the harmonics. The primary winding of the series transformer is inserted in series connection between the power grid and passive filter. Then the harmonic current are forced to inflow into the passive filter.
The detection block of the reference signals as
Fig. 2
shows
[12]
. sin
ωt
and cos
ωt
are the 50Hz sinusoidal signal and cosine signal.
i
is the current of the primary winding, it contains fundamental and harmonic component:
Calculation of the reference signals
Multiply
i
1
by sinusoidal signal,
If the LPF block has ideal low pass characteristic, only DC signal can through it:
In a similar way, multiply
i
1
by cosine signal, the other DC signal component can obtained:
The fundamental component of
i
1
current is:
The harmonic component can obtain as follow:
Finally, the reference current signals are:
3. Inter-harmonic Oscillation
- 3.1 Oscillation phenomenon
Inter-harmonics oscillation occurred when
β
is not equal to 0 in the experiment.
Fig. 3
shows the system current when the APF is under working condition
α
=1,
β
=1. The system current waveform is “oscillating”. Change the time coordinate to 50ms/div, the system current voltage is shown as the 2
nd
waveform in
Fig. 3
. The “beat” of the waveform indicates that there are inter-harmonics in the system current and the inter-harmonics frequency is close to Chinese power frequency---50Hz.
The experiment system current waveform
- 3.2 Oscillation reason analysis
Fig. 2
shows the reference current calculation algorithm. The fundamental and harmonic current detecting method has been explained in detail in
[12]
. By multiplying of sinusoidal and cosine signal, the 50Hz fundamental current signal was converted to DC current signal. That means this multiplication in fact was a process of “frequency coordinate transformation”. The frequency of fundamental signal in actual coordinate frame is 50Hz, and in fictitious synchronization coordinate frame (after multiplying of sinusoidal and cosine signal), the frequency of fundamental signal is 0Hz.
The accurately mathematical model of this “frequency coordinate transformation” is quite complex
[13]
and it is not necessary for the following theoretical analysis of this manuscript. For this reason, this manuscript does not considering the difference of the inter-harmonics frequency in different coordinate system. The amplitude-frequency and phase-frequency response of the LPF to DC signal in
Fig. 4
represent the amplitude-frequency and phase-frequency response of the reference current signal calculation system to the 50Hz fundamental current signal.
Bode diagram of Eq. (5) with different β
The LPF in
Fig. 2
using digit period average algorithm: Y=X(z
−1
+ z
−2
+ z
−3
… +z
−N
)/N, hence the discrete transfer function of the digit period average algorithm LPF is:
If
α
=1, the discrete transfer function of the
Fig. 2
is:
In the APF, sampling frequency is 12.8 kHz; the sampling number in one fundamental period is N=256. The bode diagram of Eq. (5) is shown as
Fig. 4
. The abscissa of
Fig. 4
is
f
pq
, which is the frequency in fictitious synchronization coordinate system. If
β
≠ 0, to the inter-harmonics,
I
ref
is not the same phase to the inter-harmonics of the system current. That means the series transformer does not establish (1+
β
) times magnetizing impedance to the inter-harmonics.
Then discuss the equivalent inter-harmonics impedance of the series transformer. Considered the inverter as ideal controlled current source, then connect an ideal unit current source to the primary winding of the series transformer, the current of the secondary winding of the series transformer can be known from
Fig. 4
. The vector diagram of the series transformer is shown as
Fig. 5
.
I
1
, which is the ideal unit current source, is also the current of the primary winding;
I
2
is the current of secondary winding.
U
m
and
I
m
are the magnetizing voltage and current. Since the leakage inductance has been ignored,
U
m
is equal to the voltage of the primary winding. The equivalent impedance of the series transformer is:
Vector diagram of the series transformer
where:
ω
f
– the angular frequency of the inter-harmonics
In
Fig. 4
,
θ
f
∈(0°, 180°), so sin
θ
f
>0. The equivalent resistance of the series transformer is a negative value. According to
Fig. 5
,
U
m
lies in the second quadrant, thus the real part of
U
m
is less than 0. That is the reason why the equivalent resistance of the series transformer is a negative value. And
I
m
lie in the first quadrant is the reason why
U
m
lies in the second quadrant.
The amplitude and phase of
I
2
can be known according to
Fig. 4
, so the amplitude and phase of
I
m
with different frequency inter-harmonics can be drawn out.
Fig. 6
shows the envelope curve of the vector
I
m
. The direction of arrow represents the frequency of inter-harmonics
f
pq
increase direction.
Envelope curve of Im with different β
Assume
I
m
=
a
+j
b
,
a
> 0,
b
> 0. Then observing from the primary winding of the series transformer, the equivalent impedance to the inter-harmonic is:
From Eq. (7), the equivalent resistance and inductance of the series transformer to inter-harmonics are:
Eqs. (7) and (8) are equal to (6). From Eq. (8), the “equivalent negative resistance” of series transformer is proportional to the imaginary part of
I
m
. The “equivalent negative resistance” of the series transformer to the interharmonics will weaken the inter-harmonics stability of the APF system, discussed as follow.
The equivalent circuit of a single-phase APF system to both harmonics and inter-harmonics is shown as
Fig. 7
.
R
t
and
L
t
represent the series transformer,
L
5
and
C
5
represent the passive filter,
R
s
represent the system equivalent damping.
I
h
is the load harmonics and inter-harmonics current source;
U
sh
is the power system harmonics and inter-harmonics voltage source. Since there is nearly no inter-harmonic in the system voltage and load current when the APF is not working, the inter-harmonic oscillation phenomenon is not generating by the system voltage source and load current source. To inter-harmonics, the source in
Fig. 7
is 0. That means
I
h
=0,
U
sh
=0. Assume parameters
L
=
L
t
+
L
5
,
R
=
R
t
+
R
s
,
C
=
C
5.
Choosing the capacitor voltage
U
C
as state variable, the second-order differential equations of the circuit in
Fig. 7
can be established:
Single phase equivalent circuit of SHAPF
The characteristic roots of the Eq. (9) are:
The general solution of Eq. (9) depends on the value of Δ, as
Table 1
shows. Each form of the general solution contains exponential function. If |
R
t
| > |
R
s
|,
R
< 0. Thus when t → ∞, the solution of Eq. (9) → ∞. The APF system is unstable in theory. The inter-harmonics stability of the APF system depends on the “equivalent negative resistance” of the series transformer. According to
Fig. 6
and Eq. (8), APF system is unstable if
β
is too large.
General solution of 2ndorder differential equation.
General solution of 2nd order differential equation.
The premise of the above conclusion is that the inverter was considered as ideal controlled current source, and the inverter output current is equal to the reference current
I
ref
all the time. But in practice, limited by the capacity of the actual inverter, the inverter can not track the system current to infinity. According to
Fig. 4
, after APF working, when the system current is increasing because of the “equivalent negative resistance” of the series transformer, the magnetizing voltage
U
m
will also increasing. If the peak value of
U
m
is large than the DC voltage, the inverter is out of control. Hence, with the increase of the system current, the inverter output current is not equal to the reference current. The actual inverter can not be considered as ideal controlled current source. The principle of the “equivalent negative resistance” of the series transformer is broken. So in the experiment, the system current will not increase to the infinity, but inter-harmonics oscillation occurs.
- 3.3 Resolution method
According to the above analysis, the essence of the inter-harmonic oscillation in the APF system based on MFC is that the APF system is unstable to the inter-harmonics. In order to solve this problem, the principle of the “equivalent negative resistance” of the series transformer must be weakening.
- 3.3 Resolution method
According to the above analysis, the essence of the interharmonic oscillation in the APF system based on MFC is that the APF system is unstable to the inter-harmonics. In order to solve this problem, the principle of the “equivalent negative resistance” of the series transformer must be weakening.
- 3.3.1 Only compensate fundamental current
The inverter output current contains no harmonic current when
β
is equal to 0. This is the traditional series hybrid APF based on the fundamental magnetic flux compensation. The stability of this APF has been proved by many literatures such as
[7
-
8
,
11]
.
Compared with the passive power filter, the major defect of active power filter is the high cost. New topologies and control strategies which can reduce the capacity of the inverter have been became the research hotspot of APF. In this series hybrid APF based on MFC, the harmonic component of the system current is very little after filtering. Adding harmonic current reference will not increase the capacity of the inverter but improve the filtering effect. So the harmonic current reference is significative.
- 3.3.2 Voltage feed-forward control
According to
Fig. 5
and
Fig. 6
, the reason why the series establish “equivalent negative resistance” is that the imaginary part of
I
m
is a positive value. If can reduce the imaginary part of
I
m
, make
R
t
in Eq. (8) less than the total system damping, the system will be stable to the inter-harmonics. In order to reduce the imaginary part of
I
m
, voltage feed-forward was proposed in this manuscript.
In this voltage feed-forward method, an additional reference current component
I
2
′ is adding to the current reference.
I
2
′ is proportional to
U
m
and the proportion coefficient is a negative value. Since the leakage inductance can be ignored,
U
m
is equal to the voltage of the series transformer primary winding. The vector diagram of series transformer is shown as
Fig. 8
.
I
2
is the reference current obtained by Eq. (8).
I
2
′ is the voltage feed-forward control reference current. The total reference current is the sum of
I
2
and
I
2
′. Compared with
Fig. 5
, it is very clear that the imaginary part of
I
m
in
Fig. 8
is less. As a result, the inter-harmonics stability of APF system has been enhanced. The inter-harmonics oscillation will be eliminated. Beside
I
2
′, there is not any other change of the series hybrid active power filter.
Vector diagram of the series transformer while adding voltage feed-forward method
4. Simulation and Experiments Verification
- 4.1 Simulation result
The simulation circuit is shown as
Fig. 9.
The circuit parameters are equal to the experiment circuit in our laboratory. The mutual inductance between the primary winding and the secondary winding of the series transformer is 15mH; the turns ratio of the series transformer is 1/1; the leakage inductance of the primary winding is 0.5mH; the passive power filter consists of 5th turned LC filter,
L
5
= 2.13mH,
C
5
= 68uF, the capacitor is Δ connected. The number of 5
th
turned passive filter is 3 (In
Fig. 9
, only 2 LC passive filter is plot out). The output inductance of each inverter is 1mH. The load of the silicon controlled rectifier is 2.8Ω and 10mH. In addition, a 0.5Ω resistance is series connected with each phase inverter in the simulation circuit to represent the total system damping.
Topology of series hybrid active power filter
Fig. 10
shows the simulation system current results with different conditions. The harmonics compensation coefficient
β
is equal to 1 in every condition.
Simulation results
Using three ideal controlled current sources instead of the inverter in
Fig. 9
, system current is shown as
Fig. 10(a)
. The system current shows that the APF system is unstable to the inter-harmonics. This simulation waveform validates the above analysis
Using three phase inverter in simulation, system current is shown as
Fig. 10(b)
. The system current does not go to infinity, inter-harmonics oscillation occurred. The “beat” of the waveform in
Fig. 10(b)
is similar to the system current waveforms in
Fig. 3
. Of course the inter-harmonics oscillation in the experimental is more complex because of the errors in the actual system, such as the detection error and Analog-Digit convert error.
Fig. 10(c)
shows the simulation system current when adding voltage feed-forward control. There is nearly no inter-harmonic oscillation in the system current. This simulation result verifies the validity of the voltage feed-forward control.
A prototype based on the system configuration shown in
Fig. 9
has been built. The main circuit parameters are same to the simulation circuit. The capacitor at the DC side is 6800μF/400V electrolytic capacitor, 4 parallel and 2 series connection. The inverter uses IPM of PM300CLA120. The switching frequency is 12.8 kHz. The CPU chip of the APF system is the digital signal processor (DSP) TMS320F2812 manufactured by Texas Instruments (TI). Experimental waveforms are recorded by the TEK2000 digital oscilloscope.
Fig. 11(a)
shows the system voltage and current waveforms while the 5th turned passive filter is under working. The rms value of the system current is 24.1A. The total harmonic distortion (THD) is 13.97%.
Experiment results
Fig. 11(b)
shows the inverter output current while
α
=1,
β
=1. Compared with
Fig. 11(a)
, the inverter output fundamental current is anti-phase with the system fundamental current, and the inverter output harmonic current is the same phase with the system harmonic current.
Fig. 11(c)
shows the system voltage and current waveforms while the 5th turned passive filter and APF are all working. And voltage feed-forward control has been adding in the control block. The rms value of the system current is 23.1A. THD is 4.41%. This experiment result verifies the validity and feasibility of the voltage feed-forward control.
5. Conclusion
Research in this paper shows that the essence of inter-harmonics current oscillation in the SHAPF based on the magnetic flux compensation is that the APF is unstable to the inter-harmonics. If the “negative equivalent resistance” of the series transformer is larger than the system damping, APF is unstable to the inter-harmonics in theory. Limited by the capacity of the actual inverter, the inverter output current can not track the system current to infinity. Then the inter-harmonics oscillation happens. Though the conclusion of this paper is based on the period average algorithm LPF, the conclusion is also correct when adopt other LPF algorithms, such as Butterworth filter, and Bessel filter, et al.
This paper proposes the voltage feed-forward control to solve the inter-harmonics current oscillation problem. The validity and feasibility of the voltage feed-forward control are verified by both the simulation and experiment results.
BIO
Zhang Jian-gong He was born in Hubei, China, in 1975. He received the B.S. degree in electrical engineering from Wuhan University of Hydraulic and Electric, Wuhan, China, in 1999, and the M.S. degree in electrical engineering from Huazhong University of Science and Technology (HUST), Wuhan, China, in 2006. Currently, He is with the China Electric Power Research Institute (CEPRI), Wuhan City, Hubei Province, China. His research interests include power system electromagnetic compatibility and the electromagnetic environment of power systems.
Liu Jian-ben He received the B.S. and Ph.D. degrees in electrical engineering from Huazhong University of Science and Technology (HUST), Wuhan, China, in 2007 and 2013, respectively. He is currently working as an engineer in the China Electric Power Research Institute (CEPRI), Wuhan City, Hubei Province, China. His research interests include power electronics, harmonic suppression and reactive power compensation technology.
Dai Shao-jun She received the B.S. degree in electrical engineering from Huazhong University of Science and Technology (HUST), Wuhan, China, in 2009. She is currently working in Electric Power Economic and Tech- nological Research Institute of State Grid Wuhan Power Supply Company, as an assistant engineer. Her working content includes power system planning, scientific and technical literatures translation.
Chen Qiao-fu He received the B.S. and M.S. degrees from Huazhong University of Science and Technology (HUST), Wuhan, China, in 1968 and 1982, respectively. He is currently a professor of HUST. His research interests are flexible ac transmission systems (FACTS), harmonic suppres- sion and active power filters, transformers, reactors, and fault current limiters. Mr. Chen is a member of the transformer subcommittee of the China Society of Electrical Engineering and is a member of the transformer standard of China.
He Jun-jia He was born in Hunan, China, in 1968. He received the B.S. and Ph.D. degrees from Huazhong University of Science and Technology (HUST), Wuhan, China, in 1990 and 1995, respectively. He was a research student with Nagoya University, Na- goya, Japan, from October 1999 to September 2001. Since 2001, he has been a professor with HUST. His current research interests include high-power pulsed technology and high voltage engineering.
Chang G W
,
Wang Hung-Lu
,
Chuan Gen-Sheng
2009
“Passive Harmonic Filter Planning in a Power System With Considering Probabilistic Constraints,”
IEEE Trans. Power Delivery
24
(1)
208 -
218
EI-saadany E F
,
Salama M M A
,
Chikhani A Y
2002
“Passive Filter Design for Harmonic reactive Power Compensation in Single-phase Circuits Supplying Nonlinear Loads,”
IEE Proceedings: Generation, Transmission and Distribution
147
(6)
373 -
380
Wu Longhui
,
Zhuo Fang
,
Zhang Pengbo
,
Li Hongyu
,
Wang Zhaoan
2007
“Study on the Influence of Supply-Voltage Fluctuation on Shunt Active Power Filter,”
IEEE Trans. Power Delivery
22
(3)
1743 -
1749
Yang Huayun
,
Ren Shiyan
2008
“A Practical Series-Shunt Hybrid Active Power Filter Based on Fundamental Magnetic Potential Self-Balance,”
IEEE Trans. Power Delivery
23
(4)
2089 -
2096
DOI : 10.1109/TPWRD.2008.923114
Akagi Hirofumi
,
Kondo Pypta
2010
“A Transformerless Hybrid Active Filter Using a Three-level Pulsewidth Modulation (PWM) Converter for a Medium-Voltage Motor Drive,”
IEEE Trans. PowerElectron
25
(6)
1365 -
1374
Shuai Zhikang
,
Luo An
,
John Shen
,
Wang Xiao
2011
“Double closed-loop control method for injectiontype hybrid active power filter,”
IEEE Trans. Power Electron
26
(9)
2393 -
2403
DOI : 10.1109/TPEL.2010.2103368
Li Dayi
,
Chen Qiaofu
,
Jia Zhengchun
,
Ke Jianxing
2004
“A novel active power filter with fundamental magnetic flux compensation,”
IEEE Trans. Power Delivery
19
(2)
799 -
805
DOI : 10.1109/TPWRD.2003.823194
Li Dayi
,
Chen Qiaofu
,
Jia Zhengchun
,
Zhang Changzheng
2006
“A High-Power Active Filtering System With Fundamental Magnetic Flux Compensation,”
IEEE Trans. Power Delivery
21
(2)
823 -
830
DOI : 10.1109/TPWRD.2006.871009
Zhang Yu
,
Chen Qiaofu
,
Tian Jun
,
Li Xin
,
Li Jianhui
2009
“Controllable Reactor Based on Transformer Winding Current Regulating,”
Proceedings of the CSEE
29
(18)
113 -
118
Jun Tian
,
Qiaofu Chen
,
Lu Cheng
,
Changzheng Zhang
2009
“A novel shunt hybrid active power filter based on magnetic flux compensation,”
International Journal of Electronics
96
(10)
1071 -
1084
DOI : 10.1080/00207210902977814
Bingruo Xie
,
Qiaofu Chen
,
Jun Tian
,
Lu Cheng
,
Jin Wang
2007
“Analysis and improvements of the filtering characteristic of the series hybrid APF based onfundamental magnetic flux compensation,”
Proceedings of IEEE ICEMS2007 Conference
Seoul,Korea
Jiang Bin
,
Yan Gangfeng
,
Zhao Guangzhou
2000
“Study on a detecting method for harmonic currentsin single-phase circuit,”
Transactions of China Electrotechnical Society
15
(6)
65 -
69
Tong Liqing
,
Qian Zhaoming
,
Peng Fangzheng
2009
“Synchronous reference frame harmonic detectionmodeling and digital realization,”
Proceedings of the CSEE
29
(19)
111 -
117