An Analytical Solution for Voltage Stability Studies Incorporating Wind Power
An Analytical Solution for Voltage Stability Studies Incorporating Wind Power
Journal of Electrical Engineering and Technology. 2015. May, 10(3): 865-876
Copyright © 2015, The Korean Institute of Electrical Engineers
This is an Open-Access article distributed under the terms of the Creative Commons Attribution Non-Commercial License (http://creativecommons.org/licenses/by-nc/3.0/)which permits unrestricted non-commercial use, distribution, and reproduction in any medium, provided the original work is properly cited.
  • Published : May 01, 2015
Download
PDF
e-PUB
PubReader
PPT
Export by style
Article
Author
Metrics
Cited by
TagCloud
About the Authors
Yu-Zhang Lin
National Key Laboratory of Power System in Shenzhen, Graduate School at Shenzhen, Tsinghua University, Shenzhen 518055, China. (shilb@sz.tsinghua.edu.cn)
Li-Bao Shi
Corresponding Author: National Key Laboratory of Power System in Shenzhen, Graduate School at Shenzhen, Tsinghua University, Shenzhen 518055, China. (shilb@sz.tsinghua.edu.cn)
Liang-Zhong Yao
China Electric Power Research Institute, Qinghe, Beijing 100192, China. (yaoliangzhong@epri.sgcc.com.cn)
Yi-Xin Ni
National Key Laboratory of Power System in Shenzhen, Graduate School at Shenzhen, Tsinghua University, Shenzhen 518055, China. (shilb@sz.tsinghua.edu.cn)
Shi-Yao Qin
China Electric Power Research Institute, Qinghe, Beijing 100192, China. (yaoliangzhong@epri.sgcc.com.cn)
Rui-Ming Wang
China Electric Power Research Institute, Qinghe, Beijing 100192, China. (yaoliangzhong@epri.sgcc.com.cn)
Jin-Ping Zhang
China Electric Power Research Institute, Qinghe, Beijing 100192, China. (yaoliangzhong@epri.sgcc.com.cn)

Abstract
Voltage stability is one of the most critical security issues which has not yet been well resolved to date. In this paper, an analytical method called PQ plane analysis with consideration of the reactive power capability of wind turbine generator and the wake effect of wind farm is proposed for voltage stability study. Two voltage stability indices based on the proposed PQ plane analysis method incorporating the uncertainties of load-increasing direction and wind generation are designed and implemented. Cases studies are conducted to investigate the impacts of wind power incorporation with different control modes. Simulation results demonstrate that the constant voltage control based on reactive power capability significantly enhances voltage stability in comparison of the conventional constant power factor control. Some meaningful conclusions are obtained.
Keywords
1. Introduction
In the recent decades, a few serious power system contingencies occurring around the world pertinent to voltage collapse have drawn wide attentions for electrical engineers [1 - 2] . Over the years, a variety of analyzing methods have been proposed to give insight into the mechanism and assessment of voltage stability. However, due to the complexity of this issue, it is difficult for these attempts to provide the comprehensive and time-saving solutions.
The existing analyzing methods can be classified into two categories: static and dynamic. So far, the static methods, which can give instructive information for power system planning, operation and control with ignorance of transient behavior, are widely applied in utilities. Especially, the conventional PV and QV curves based analysis methods [3 - 6] , which are applied to investigate the relationships between voltage and active or reactive power in a specific load increasing direction, are very useful in determining voltage stability margin and developing remedial action strategies. However, such methods are only applicable for certain increasing modes and cannot provide a full view of voltage stability. On the other hand, the utilized continuation power flow technique is rather time-consuming. Furthermore, with the integration of large-scale renewable energy sources, especially for wind power, the new challenges and issues to the voltage stability will appear in the smart grid environment. Three factors, the variability and intermittency of wind energy, the wind turbine generator (WTG) models, and the pattern of grid-connection, should be taken into account for voltage stability studies incorporating wind power [7 - 9] . In a nutshell, how to effectively conduct the voltage stability analysis incorporating intermittent wind power and develop more powerful analysis tool become very imperative and necessary.
In this paper, an analytical method called as PQ Plane analysis, is proposed for voltage stability studies incurporating wind power. Two factors, the reactive power capability of WTG and the wake effect of wind farm, are paid special attention to during the modelling of wind farms of doubly-fed induction generator (DFIG) type. The stability boundary and voltage distribution are derived and shown on the PQ plane. Furthermore, a set of indices are defined to indicate the voltage security situation of a load bus. The proposed method is derived in a single-load-infinite-bus system, and can be easily expanded to complex power systems by applying Thevenin Equivalent Circuits [10] or the newly proposed Coupled Single-Port Circuits [11] . Some preliminary and meaningful conclusions are drawn.
The rest of the paper is organized as follows: In Section 2, the static modelling of wind farm involving the reactive power capability of DFIG and the wake effect is discussed. The PQ plane analysis method incorporating wind generation is proposed and detailed in Section 3. The case studies with different simulation scenarios are carried out in Section 4. The conclusions and research prospects can be found in Section 5.
2. Modelling of Wind Farms for Voltage Stability Studies
In this section, a static model of wind farm of DFIG type is proposed with consideration of reactive power capability and wake effect.
- 2.1 Active power output of wind farms with consideration of wake effect
The active power output of a DFIG Pwt with respect to the wind speed v can be expressed as [12]
PPT Slide
Lager Image
where vci , vco , vr and Pwtr are cut-in speed, cut-out speed, rated speed and rated active power, respectively.
In conventional model of wind farm, the wind speed each wind turbine captures is assumed to be the same. Actually, in practical wind farms, the wind turbines located downwind gain a lower wind speed than those located upwind, in that the kinetic energy of wind is partly consumed by the latter ones. Such aforementioned situation is called as wake effect. A lot of wake effect models have been developed to date with specific applicability. In this paper, the Jensen Model [13] , as illustrated in Fig. 1 is applied to describe the wake effect in a wind farm located on flat terrain. In accordance with the Jensen model, the wind speed behind a wind turbine vwake with respect to the distance from the wind turbine plane x can be presented as
PPT Slide
Lager Image
The wake effect of wind turbines
PPT Slide
Lager Image
where v 1 is the original wind speed; Rwt is the wind turbine radius; ξx is the damping coefficient; and ξT is the thrust coefficient of the wind turbine. ξx can be obtained by
PPT Slide
Lager Image
where kw is the turbulence intensity, which can be estimated empirically; σwake and σ 0 are mean-square deviation of natural turbulence and turbulence caused by WTGs, respectively.
For a wind farm with nrow rows and ncol columns in a chessboard-pattern layout, the distance between two adjacent rows of WTGs is drow , the wind speed in the i th row can be calculated by
PPT Slide
Lager Image
where v 1 is the wind speed in the first row (the original wind speed), and ξd is the damping coefficient between two adjacent rows of WTGs, which is given by
PPT Slide
Lager Image
Then the active power output of a single DFIG in the i th row Pwt,i can be calculated based on Eq. (1). Ignoring the losses in the collection systems, the total output of a wind farm equipped with DFIG is
PPT Slide
Lager Image
Fig. 2 illustrates the active power output of a wind farm with and without considering the wake effect.
PPT Slide
Lager Image
Active power output of wind farms with respect to wind speed
- 2.2 Reactive power capability curve of DFIG
The equivalent circuit of a DFIG is given in Fig. 3 , in which the stator voltage
PPT Slide
Lager Image
, stator current
PPT Slide
Lager Image
, rotor voltage
PPT Slide
Lager Image
and rotor current
PPT Slide
Lager Image
are restricted by
PPT Slide
Lager Image
Equivalent circuit of DFIG
PPT Slide
Lager Image
PPT Slide
Lager Image
where s is the slip ratio.
From (7) and (8), we have
PPT Slide
Lager Image
PPT Slide
Lager Image
PPT Slide
Lager Image
where matrix Y , G and B can be derived from the parameters of the equivalent circuit.
The complex power outputs of the stator and rotor are expressed as
PPT Slide
Lager Image
PPT Slide
Lager Image
If the losses in the boosting transformer are negligible, the total power output can be given by
PPT Slide
Lager Image
where Ps is the stator active power; Qs is the stator reactive power; Pr is the rotor active power; Qgc is the grid-side convertor reactive power.
Among the four variables,
PPT Slide
Lager Image
,
PPT Slide
Lager Image
,
PPT Slide
Lager Image
/ s and
PPT Slide
Lager Image
,
PPT Slide
Lager Image
is determined by the grid voltage, and the other three variables have certain limits for security reasons, which would determine the reactive power capability. With a given
PPT Slide
Lager Image
, to analyze the effect of
PPT Slide
Lager Image
limit, the output should be expressed with respect to
PPT Slide
Lager Image
. By substituting (10) into (12) and (13), we have
PPT Slide
Lager Image
PPT Slide
Lager Image
where Zs = Rs + jXs ; Zr = Rr / s + jXr ; Zm = jXm . From (14), (15) and (16), the total power output can be derived and expressed as
PPT Slide
Lager Image
From (17), with given Vs , Ir and s , it can be drawn as an ellipse on the PQ plane. As the absolute value of imaginary part of Zm + Zs is much larger than that of the real part, the center of the ellipse is very close to negative Q-axis.
Similarly, with a given
PPT Slide
Lager Image
, to analyze the effect of
PPT Slide
Lager Image
limit, the output should be expressed with respect to
PPT Slide
Lager Image
. By substituting (11) into (13), we have
PPT Slide
Lager Image
From (12), (14) and (18), the total power output can be derived and expressed as
PPT Slide
Lager Image
Fig. 4 shows the reactive power capability determined by limits of the stator current and rotor current. The solid line given in Fig. 4 denotes the reactive power capability with respect to the active power output.
PPT Slide
Lager Image
Reactive power capability determined by the stator current limit and the rotor current limit
As mentioned above, the slip ratio s is assumed to be constant. In actual operation of DFIGs, however, the rotational speed of the wind turbine changes with the wind speed to capture the maximum power. A commonly-applied speed control law is given as follows [15] :
PPT Slide
Lager Image
where nmin is the minimum speed; n 1 is the synchronous speed; n max is the maximum speed; kopt is the power adjustment coefficient; P 1 , P 2 and P 3 are three demarcation points, respectively.
As the slip ratio changes, the shape of the reactive power capability curve will change. The corresponding solution procedures are given as follows:
  • 1) Assign the initial active powerP0=0 and the incrementΔP; Leti=1;
  • 2)Pi=P0+iΔP;
  • 3) Calculate rotational speedniaccording to Eq. (20);
  • 4) Calculate slip ratiosi;
  • 5) Calculate the reactive power upper limitQmax,iand lower limitQmin,iaccording to Eq. (17) and (19) respectively;
  • 6) IfQmax,i≤Qmin,iorPi≥1, go to Step 7; else,i=i+1, go to Step 2;
  • 7) Plot the reactive power capability curve.
The reactive power capability curves with different s are given in Fig. 5 . It can be seen that as the slip ratio decreases or the rotational speed increases, the operation region expands and the reactive power capability increases. The actual reactive power capability curve is made up of points in different curves. When P < P 1 and P 2 P < P 3 , the actual reactive power capability curve will overlap curves with s =0.3 and s =0 respectively. In other areas, it crosses a set of curves with constant s as the slip ratio keeps changing.
PPT Slide
Lager Image
Capability curves with different constant s and with the speed control law
- 2.3 Reactive power capability curve of wind farm and voltage control strategies
With the consideration of the wake effect, the total power output of wind farm of DFIG-type can be calculated according to the following procedures:
  • 1) Assign the initial wind speedv0=0 and the incrementΔv; Letk=1;
  • 2)vk=v0+kΔv;
  • 3) Calculate the wind speedsvkiaccording to Eqs. (4) and (5);
  • 4) Calculate the active output of DFIGs in each rowPwt,kiaccording to Eq. (1);
  • 5) Calculate the active output of the whole wind farmPwf,kaccording to Eq. (6);
  • 6) Calculate the rotational speeds of DFIGs in each rownkiaccording to Eq. (20);
  • 7) Calculate the slip ratios of DFIGs in each rowski;
  • 8) Calculate the reactive power upper limitQwtmax,kiand lower limitQwtmin,kiof DFIGs in each row according to Eqs. (17) and (19), respectively;
  • 9) Calculate the reactive power upper limitQwfmax,kiand lower limitQwfmin,kiof the whole wind farm according to the following Equations
PPT Slide
Lager Image
PPT Slide
Lager Image
  • 10) Ifvi≥vco, go to Step 11; else,i=i+1, go to Step 2;
  • 11) Plot the reactive power capability curve.
Fig. 6 shows the reactive power capability of a wind farm with/without consideration of the wake effect as well as the conventional constant power factor control strategy.
PPT Slide
Lager Image
Reactive power capability of a wind farm
From Fig. 6 , with conventional control strategy, there is a large amount of reactive reserve unutilized, especially when the active power output is relatively low. To make full use of the reactive reserve for the sake of voltage security enhancement, the constant voltage control mode is applied in this paper. When there is an amount of reactive reserve, the voltage at the point of common coupling (PCC) is maintained at 1 p.u.; when the reactive reserve is depleted, the reactive output of the wind farm is maintained at the maximum value. The corresponding comparative analysis between the two control modes can be found in Section 4.
3. PQ Plane Analysis
As mentioned above, the conventional PV and QV curves based analysis methods only reflect the voltage stability in specific load-increasing directions, which are difficult to provide the full picture of voltage stability. In this section, an analytical method called the PQ plane analysis is proposed for voltage stability analysis and assessment incorporating wind generation.
- 3.1 Voltage stability region and voltage profiles
The single-load-infinite-bus system as shown in Fig. 7 is employed as benchmark to address the proposed method. The symbols
PPT Slide
Lager Image
,
PPT Slide
Lager Image
,
PPT Slide
Lager Image
, P , Q , R and X represents the infinite bus voltage, transmission line current, load bus voltage, active load, reactive load, transmission line resistance and reactance, respectively. According to circuit principles, we have
PPT Slide
Lager Image
Single-load-infinite-bus system
PPT Slide
Lager Image
From the definition of complex power, the current can be expressed as
PPT Slide
Lager Image
By substituting (24) into (23), we have
PPT Slide
Lager Image
From (25), we can get
PPT Slide
Lager Image
PPT Slide
Lager Image
Further, we can derive
PPT Slide
Lager Image
Eq. (28) can be converted into
PPT Slide
Lager Image
With a constant V , the locus of Eq. (29) is a circle on the PQ plane, with the center
PPT Slide
Lager Image
and radius
PPT Slide
Lager Image
In this paper, the loci of the power system operating points with the specific constant V on the PQ plane are called the constant voltage lines, which shows the range of load that corresponds to secure voltage.
From (28), the voltage stability boundary can also be derived. Rewrite the equation with respect to V , we have
PPT Slide
Lager Image
On the voltage stability boundary, there is only one solution for V . Thus, the discriminant of Eq. (32) should be equal to zero:
PPT Slide
Lager Image
Accordingly, we can get the equation of voltage stability boundary:
PPT Slide
Lager Image
The discriminant of Eq. (34) equals to zero, indicating that the voltage stability boundary is a parabola on the PQ plane.
Fig. 8 displays the voltage stability boundary and a set of constant voltage lines pertinent to the single-load-infinite-bus system in which X is much larger than R . It can be seen that the stability boundary is a parabola. The parts inside the parabola are the stability region. The constant voltage lines are circles tangent to the stability boundary, i.e. the stability boundary is the envelope of all constant voltage lines.
PPT Slide
Lager Image
Voltage stability boundary and constant voltage lines
For a load bus, only the first quadrant of PQ plane as shown in Fig. 9 needs to be elaborately studied. It can be seen from Fig. 9 that the voltage constant lines do not intersect in the first quadrant. As the load increases, the operating point moves closer to the stability boundary and the bus experiences a voltage dip. Furthermore, it can also be found that the information provided by PV and QV curves based analysis methods is easily included in PQ plane. For instance, the PV curve based analysis method assumes that the load increases with a given power factor cos φ , and calculates the active power margin to the stability boundary ΔPL . On the PQ plane, the load increasing direction is represented as the direction of
PPT Slide
Lager Image
, and ΔPL is the length of AC. The QV curve based analysis methods assumes that there is a synchronous condenser installed at the load bus and investigates the relationship between V and Q while maintaining P constant. On the PQ plane, the increasing direction is represented as the direction of
PPT Slide
Lager Image
, and the reactive power margin ΔQc is the length of AD.
PPT Slide
Lager Image
Voltage stability boundary and constant voltage lines in and nearby the first quadrant
- 3.2 Discussions of PV curve based analysis method
According to Fig. 9 , for the conventional PV curve based analysis, when there is an error between the actual load-increasing direction and the assumed direction, an error of the load margin will occur. Moreover, even if the calculated load margin ΔPL of two systems are same, they may have different performance in other given load-increasing directions. Fig. 10 shows the stability boundaries of two systems with different parameters: SLIB 1 and SLIB 2 . Their stability boundaries intersect in the first quadrant. Assume that the two systems have the same initial operating point A. With a certain assigned load-increasing direction, they all reach B point, the point of intersection of their stability boundaries as shown in Fig. 10 . Obviously, they share the same load margin ΔP 1, 2, AB . If the load increases along
PPT Slide
Lager Image
, the margin of SLIB 1 ΔP 1, AC is smaller than that of SLIB 2 ΔP 2, AC ; if the load increases along
PPT Slide
Lager Image
, however, the results are exactly the opposite. Hence, it can be found that the load margin of SLIB 1 varies more intensely with respect to the load-increasing direction variations. And it also can be concluded that SLIB 2 is more stable than SLIB 1 from a voltage stability viewpoint.
PPT Slide
Lager Image
Conventional PV curve based analysis
- 3.3 Voltage stability indices
In this section, two voltage stability indices based on PQ plane analysis incorporating the uncertainties of load-increasing direction and wind generation are proposed. Assume that the power factor angle of the load increment φ is a random variable subject to a certain probability distribution φ ~ Dφ with a mean φμ and a variance φσ . The load margin in the direction of φ can be calculated by solving the following equations:
PPT Slide
Lager Image
Two solutions can be obtained from (35), and only the solution named Pmargin in the first quadrant is retained. As Pmargin is a function of φ :
PPT Slide
Lager Image
It must subject to a certain probability distribution Pmargin ~ DPmargin . In our work, the mean and variance of Pmargin are calculated approximately to avoid the heavy computational burden. According to probability theories, with given φμ and φσ , Pmargin μ and Pmargin, σ can be estimated respectively by
PPT Slide
Lager Image
PPT Slide
Lager Image
where f’ ( φμ ) and f’’ ( φμ ) can be estimated by difference quotients. Assign a small increment, and substitute φ = φμ φ and φ = φμ φ into Eq. (36) to get f ( φμ φ ) and f ( φμ φ ). Then f’ ( φμ ) and f’’ ( φμ ) can be calculated by
PPT Slide
Lager Image
PPT Slide
Lager Image
The coefficient of variation of Pmargin can be calculated by
PPT Slide
Lager Image
We define Pmargin,μ and Pmargin,CV as voltage stability indices, called the Mean Margin to Voltage Instability (MMVI) and the Variation Margin to Voltage Instability (VMVI) respectively. MMVI represents the expectation of the load margin. The larger the index, the more secure the system. VMVI represents the variance of the load margin. The larger the index, the less robust the system is to the randomness of the load.
Conventionally, the solutions of voltage stability analysis mainly focus on how the current state is to the stability boundary. In fact, voltage violation is also an important issue that needs to be considered in practical operation. As the initial operating point and the load-increasing direction vary, there does not exist a fixed relationship between the distance to voltage instability and the distance to voltage violation. It is necessary, therefore, to define separate indices to indicate the risk of voltage violation. Fortunately, it is convenient to implement by using voltage constant lines on the PQ plane. By setting a voltage lower bound Vmin , and plotting the corresponding constant voltage line on the PQ plane, the secure region can be determined, as given in Fig. 11 . By solving the following equations:
PPT Slide
Lager Image
Margin to voltage instability and margin to voltage violation
PPT Slide
Lager Image
The margin to voltage violation with an initial operating point A and load-increasing direction
PPT Slide
Lager Image
can be obtained.
Similarly, the solution P’margin is a function of φ :
PPT Slide
Lager Image
Replacing function f by function g in Eq. (37) through (41), the mean and variance coefficient of P’margin μ , P’margin, CV can be derived. We define P’margin μ as the Mean Margin to Voltage Violation (MMVV) and P’margin, CV the Variation Margin to Voltage Violation (VMVV) to conduct the voltage stability evaluation.
To assess the impact of local wind integration on voltage stability, the single-load-infinite-bus system with wind power integration as shown in Fig. 12 is employed during analysis. The wind generation is connected to the grid at the load bus with Pwind + jQwind power injection. In this test system, the total active and reactive loads are
PPT Slide
Lager Image
Single-load-infinite-bus system with wind power integration
PPT Slide
Lager Image
The way to incorporate wind power in PQ Plane Analysis
PPT Slide
Lager Image
PPT Slide
Lager Image
To plot voltage stability boundary and constant voltage lines on the PQ plane based on the net load P and Q , a shift with value of ( Pwind , Qwind ) is added to implement the required solutions.
4. Case Studies
Based on the aforementioned single-load-infinite-bus test system shown in Fig. 7 , two simulation scenarios involving the studies on the relationship between power system parameters and voltage stability and the impacts of wind farm of DFIG type on voltage stability are designed for case studies. Some meaningful conclusions are drawn based on the studies.
- 4.1 Impacts of key parameters of power system on voltage stability
Impacts of transmission line ratio of reactance X and resistance R Keeping the infinite bus voltage E and the transmission line modulus of impedance | Z | constant, the stability boundaries with different X / R are plotted in Fig. 14 . It can be seen that the opening direction of the parabola rotates clockwise as X / R reduces.
PPT Slide
Lager Image
Voltage stability boundaries with different X/R
Fig. 15 shows the influence of X / R on stability boundaries in and nearby the first quadrant. Because of the rotation of the parabola, the part in the first quadrant becomes steeper, and the boundaries with different X / R intersect. This situation may cause the problem as discussed in Section 3.2. Table 1 shows the results of MMVI, VMVI and Δ Qc with different X / R . The initial load is set to be 0, and cos φ =cos( π /6)=0.866. Other factors of systems are kept constant. It can be seen that the MMVI gradually reduces as increase of X / R . The VMVI and X / R have a positive correlation, indicating that the variation of load margin reduces as X / R becomes larger. Furthermore, the larger Δ Qc does not necessarily result in larger load margin, and that is what we need to be careful with when applying the conventional QV analysis.
PPT Slide
Lager Image
Voltage stability boundaries with different X/R in and nearby the first quadrant
MMVI, VMVI and ΔQcwith differentX/R
PPT Slide
Lager Image
MMVI, VMVI and ΔQc with different X/R
To understand the impact of X / R on voltage profiles, the changes of constant voltage lines must be studied. Fig. 16 plots the constant voltage lines with different X / R , from which we can see that the center of the circle rotates clockwise as decrease of X / R .
PPT Slide
Lager Image
Constant voltage lines with different X/R
Fig. 17 shows the influence of X / R on constant voltage lines in and nearby the first quadrant. All of the lines intersect at a common point. Obviously, it can be inferred that the tendencies of MMVV and VMVV are similar to those of the MMVI and VMVI.
PPT Slide
Lager Image
Constant voltage lines with different X/R in and nearby the first quadrant
Impacts of infinite bus voltage E and transmission line modulus of impedance | Z |
Fig. 18 shows the voltage stability boundaries with different E or | Z |. As increase of E or decrease of | Z |, the stability region expands evenly in all directions, and no intersection occurs. The MMVI, VMVI and Δ Qc values with different E are given in Table 2 , from which we can see that MMVI increases steadily with the change of E , while VMVI remains unchanged.
PPT Slide
Lager Image
Voltage stability boundaries with different E or |Z|
MMVI, VMVI and ΔQcwith differentE
PPT Slide
Lager Image
MMVI, VMVI and ΔQc with different E
Table 3 and Table 4 show the results of MMVV, VMVV and Δ Qc, VV (reactive margin to voltage violations) with different E and | Z | respectively. It can be seen that as increase of E or decrease of | Z |, the MMVV shows an increasing trend. The VMVV decreases as increase of E , and it remains unchanged as decrease of | Z |. This means that the high E value can reduce the risk of serious voltage violations, but low | Z | value would not have similar influence.
MMVV, VMVV and ΔQc, VV, VVwith differentE
PPT Slide
Lager Image
MMVV, VMVV and ΔQc, VV, VV with different E
MMVV, VMVV and ΔQc, VVwith different |Z|
PPT Slide
Lager Image
MMVV, VMVV and ΔQc, VV with different |Z|
- 4.2 Impacts of wind power integration on voltage stability
- 4.2.1 Impacts of the wake effect
Fig. 19 displays the changes of MMVI and VMVI with respect to the wind speed. The initial load is set to be 0, and power factor of load interment is set to be 0.9. From Fig. 19 we can see that the shape of the MMVI curve is similar to the output curve shown in Fig. 2 : the higher wind speed results in higher voltage stability margin, but the wake effect slows this tendency. In the range of medium wind speed (10-15m/s), the calculated MMVI with the wake effect taken into account is much lower than that without consideration of the wake effect. On the other hand, it can be found that the VMVI is not sensitive to wind speed variation no matter whether the wake effect is considered. The curves of MMVV and VMVV are highly similar to those of MMVI and VMVI and are not given here.
PPT Slide
Lager Image
Impacts of the wake effect on voltage stability
- 4.2.2 Impacts of the voltage control strategies based on reactive power capability of wind farm
In this section, the conventional constant power factor control strategy and the constant voltage control strategy based on the reactive power capability discussed in Section 2 are applied for comparisons. In the constant-voltage control mode, the power factor cos φwind =0.955.
Fig. 20 shows the voltage stability boundaries in different control modes and different wind speeds. When v =19 m / s , the stability boundaries of the two control modes overlap each other, because the active power output reaches the maximum and there is no reactive power reserve left. As a result, the reactive output stays at the maximum no matter which control strategy is implemented. However, in a relatively low wind speed, the studies pertinent to different control strategies are significant. When v =8 m / s , the stability boundary corresponding to constant voltage control is shifted towards the positive Q-axis direction compared with the one corresponding to constant power factor control. In the first quadrant, the shift considerably expands the stability region, and increases the stability margin. In fact, in the region nearby the load-increasing direction, the stability margin is close to that with the wind speed of 19 m / s , i.e. the stability margin variation resulting from the wind speed variation is largely mitigated. The load margin gap between the high and low wind speeds situations is greatly narrowed by implementing constant voltage control strategy, so that the MMVI can maintain a relatively high value in a wide wind speed range. Fig. 22 demonstrates another advantage of applying the constant voltage control strategy: the VMVI drops greatly in the range of low wind speed, indicating that the risk of serious voltage instability problem is reduced in a large extent.
PPT Slide
Lager Image
Voltage stability boundaries in different control modes and different wind speeds
PPT Slide
Lager Image
MMVI with respect to wind speed in different control modes
PPT Slide
Lager Image
VMVI with respect to wind speed in different control modes
The voltage violation issue can be studied in a similar way. The constant voltage lines in different control modes and different wind speeds are shown in Fig. 23 . The impact of constant voltage control strategy on constant voltage lines is even greater: the security region with constant voltage mode and a wind speed of 8 m / s entirely covers the security region with constant power factor mode the speed of 19 m / s .
PPT Slide
Lager Image
Constant voltage lines in different control modes and different wind speeds
This phenomenon is shown more clearly in Fig. 24 . With the constant voltage control, the value of MMVV in the low wind speed even surpasses that in the high wind speed. Moreover, Fig. 25 shows that the system performs better in low wind speeds. In summary, compared with the conventional constant power factor control strategy, the constant voltage control strategy significantly improves power system’s voltage security in the range of low wind speed.
PPT Slide
Lager Image
MMVV with respect to wind speed in different control modes
PPT Slide
Lager Image
VMVV with respect to wind speed in different control modes
5. Conclusion
In this paper, an analytical approach for voltage stability evaluation incorporating wind power on PQ plane is proposed and studied in a single-load-infinite-bus system. A set of indices are defined with consideration of the load uncertainties. Based on the proposed method, the case studies are performed to investigate the impacts of power system key parameters and wind power integration on voltage stability. Furthermore, the impact analysis of wind farms with different control strategies is conducted. Some important and meaningful conclusions are obtained from the simulation results.
Future work involving the application to large-scale complex power system with remedy action strategies taken into account is under way by the authors to further enhance the model and method proposed.
Acknowledgements
This work is sponsored by State Grid Corporation of China under the contract State Grid Research 304(2013), by the National Basic Research Program of China, 973 program (2013CB228203) and the Research Project of Science and Technology from Shenzhen Development and Innovation Committee (ZDSY20120619141142918).
BIO
Yu-Zhang Lin He received B.S and M.S degrees in Electrical Engineering from Tsinghua University, China, in 2012 and 2014, respectively. His research interests are power system vulnerability analysis with voltage stability constrained incorporating wind power.
Li-Bao Shi He received Ph.D. degree in Electrical Engineering from Chongqing University, China, in 2000. His research interests are wind power in power systems, power system restoration control, computational intelligence in power system optimal operation and control, EMS/DMS, and power system stability analysis.
Liang-Zhong Yao He received the PhD degree in 1993 in electrical power system engineering from Tsinghua University, China. He is currently the Vice President of State Grid Electric Power Research Institute, China. His research interests are wind power in power systems.
Yixin Ni She received her B. Eng., M. Eng. And Ph.D. degrees all from Tsinghua University, China. She was a former professor and director of National Power System Lab, Tsinghua Univ. and is currently with the Graduate School at Shenzhen, Tsinghua University. Her research interests are in power system stability and control, HVDC transmission, FACTS, and power markets.
Shi-Yao Qin He received master degree in TaiYuan University of Science and Technology in 2003. His research interests are wind power simulation, planning, test technology.
Rui-Ming Wang He received master degree in North China Electric Power University in 2003. His research interests are wind power simulation, planning, test technology.
Jin-Ping Zhang He received master degree in HuaZhong University of Science and Technology in 2000. His research interests are wind farm and wind turbine test technology.
References
Donalek P. 2005 “Causes of the 2003 major grid blackouts in North America and Europe, and recommended means to improve system dynamic performance,” IEEE Transactions on Power Systems 20 (4) 1922 - 1928    DOI : 10.1109/TPWRS.2005.857942
Makarov Y. V. 2005 “Blackout prevention in the United States Europe and Russia,” Proceedings of the IEEE 93 (9) 1942 - 1955    DOI : 10.1109/JPROC.2005.857486
Kundur P. 1994 “Power system stability and control,” McGraw-Hill New York
1987 “Planning against voltage collapse” 55 - 75
1998 Reactive Power Reserve Work Group Technical Subcommittee Western Systems Coordinating Council, “Voltage stability criteria undervoltage load shedding strategy and reactive monitoring Methodology”
Taylor C. W. 1994 “Power system voltage stability” McGraw-Hill New York
Vittal E. , O'Malley M. , Keane A. 2010 “A Steady-State Voltage Stability Analysis of Power Systems with High Penetrations of Wind” IEEE Transactions on Power Systems 25 (1) 433 - 442    DOI : 10.1109/TPWRS.2009.2031491
Ben-Kilani K. , Elleuch M. 2013 “Structural Analysis of Voltage Stability in Power Systems Integrating Wind Power” IEEE Transactions on Power Systems 28 (4) 3785 - 3794    DOI : 10.1109/TPWRS.2013.2258043
Hossain M. J. , Pota H. R. , Mahmud M. A. , Ramos R.A. 2012 “Investigation of the Impacts of Large-Scale Wind Power Penetration on the Angle and Voltage Stability of Power Systems” IEEE Systems Journal 6 (1) 76 - 84    DOI : 10.1109/JSYST.2011.2162991
Chebbo A.M. , Irving M.R. , Sterling M.J.H. 1992 “Voltage collapse proximity indicator: behaviour and implications” IEE Proceedings: Generation, Transmission and Distribution 139 (3) 241 - 252    DOI : 10.1049/ip-c.1992.0037
Yunfei W. 2011 “Voltage Stability Monitoring Based on the Concept of Coupled Single-Port Circuit,” IEEE Transactions on Power Systems 26 (4) 2154 - 2163
Sun Y. , Wu J. , Li G. 2007 “Influence research of wind power generation on power systems,” Power System Technology 31 (20) 55 - 62
Jensen N. O. 1983 “A note on wind generator interaction,” RISO National Laboratory Roskilde
Lund T. , Sørensen P. , Eek J. 2007 “Reactive power capability of a wind turbine with doubly fed induction generator,” Wind Energy 10 (4) 379 - 394    DOI : 10.1002/we.228
Ackermann T. 2005 “Wind power in power systems,” Wiley Chichester
Haque M. H. 2002 “Determination of Steady-State Voltage Stability Limit Using P-Q Curve,” IEEE Power Engineering Review 22 (4) 71 - 72
Vijayan P. , Sarkar S. , Ajjarapu V. 2009 “A novel voltage stability assessment tool to incorporate wind variability,” Proceedings of Power & Energy Society General Meeting Calgary, Alberta, Canada