Advanced
Algorithm for Fault Detection and Classification Using Wavelet Singular Value Decomposition for Wide-Area Protection
Algorithm for Fault Detection and Classification Using Wavelet Singular Value Decomposition for Wide-Area Protection
Journal of Electrical Engineering and Technology. 2015. May, 10(3): 729-739
Copyright © 2015, The Korean Institute of Electrical Engineers
This is an Open-Access article distributed under the terms of the Creative Commons Attribution Non-Commercial License (http://creativecommons.org/licenses/by-nc/3.0/)which permits unrestricted non-commercial use, distribution, and reproduction in any medium, provided the original work is properly cited.
  • Received : September 07, 2013
  • Accepted : November 17, 2014
  • Published : May 01, 2015
Download
PDF
e-PUB
PubReader
PPT
Export by style
Article
Author
Metrics
Cited by
TagCloud
About the Authors
Jae-Won Lee
College of Information and Communication Engineering, Sungkyunkwan University, Korea. ({daniel701, kimwonki87}@hanmail.net,fivebal2@naver.com)
Won-Ki Kim
College of Information and Communication Engineering, Sungkyunkwan University, Korea. ({daniel701, kimwonki87}@hanmail.net,fivebal2@naver.com)
Yun-Sik Oh
College of Information and Communication Engineering, Sungkyunkwan University, Korea. ({daniel701, kimwonki87}@hanmail.net,fivebal2@naver.com)
Hun-Chul Seo
School of IT Engineering, Yonam Institue of Digital Technolgy, Korea. (hunchul12@yc.ac.kr)
Won-Hyeok Jang
Dept. of Electrical and Computer Engineering, University of Illinois at Urbana-Champaign, USA. (wjang7@illinois.edu)
Yoon Sang Kim
School of Computer and Science Engineering, Korea University of Technology and Education, Korea. (yoonsang@koreatech.ac.kr)
Chul-Won Park
Dept. of Electrical Engineering, Gangneung-Wonju National University, Korea. (cwpark1@gwnu.ac.kr)
Chul-Hwan Kim
Corresponding Author: College of Information and Communication Engineering, Sungkyunkwan University, Korea. (hmwkim@hanmail.net)

Abstract
An algorithm for fault detection and classification method for wide-area protection in Korean transmission systems is proposed. The modeling of 345-kV and 765-kV Korean power system transmission networks using the Electro Magnetic Transient Program - Restructured Version (EMTP-RV) is presented and the algorithm for fault detection and classification in transmission lines is developed. The proposed algorithm uses the Wavelet Transform (WT) and Singular Value Decomposition (SVD). The Singular value of Approximation coefficient ( SA ) and part Sum of Detail coefficient ( SD ) are introduced. The characteristics of the SA and SD at the fault conditions are analyzed and used in the algorithm for fault detection and classification. The validation of the proposed algorithm is verified by various simulation results.
Keywords
1. Introduction
It is critical to secure transmission lines against faults to maintain stable operation of power systems. Fault detection, classification, and the location of transmission lines are very important tasks in protecting electric power systems. Fast fault detection is needed to protect the system components from the harmful effects of a fault. Fault-type classification is needed to analyse the original signal with appropriate signal processing schemes such as the Wavelet Transform (WT). The WT is a mathematical tool used in a wide variety of fields for signal and image processing applications [1] . WT is also useful in power system transient analysis, as it is based on the time and frequency domain simultaneously [2] . WT can be used on a broad frequency range rather than a specific frequency domain, which makes WT very useful for analysing the transient phenomena in a power system. For this reason, WT has been applied in protection algorithms to detect, classify, and locate faults in power systems. Although WT has good features, typically, it is not used alone in analyses of power system transients, because the transformed signals still contain a large amount of data which requires further processing.
Thus, fault-type classification has been performed with several other methods, such as traveling waves [3 - 4] , adaptive Kalman filtering [5] , discrete wavelet transform [6 - 7] , fuzzy logic, neural networks [8] , a fusion of different artificial network techniques, and combinations of wavelet and hyperbolics [9] . Neural networks have disadvantages in that they require a considerable amount of training effort to obtain good performance, especially under various operating conditions such as system-loading level, fault resistance, and source impedance. Another disadvantage of neural-based networks is that the results of training may not cover some cases, as the starting point is chosen at random and can end up in minimum times [10 - 13] . Wavelet Singular Entropy (WSE) using WT with Singular Value Decomposition (SVD) and Shannon’s information entropy theory have been proposed [14 - 16] . SVD can be useful to decompose large amounts of data into small square matrices.
In this paper, an algorithm that includes fault detection and classification is proposed for wide-area protection. An algorithm for fault detection and classification is presented based on Wavelet Singular Value Decomposition (WSVD) combined with WT and SVD [17] . Singular value of Approximation coefficients ( SA ) containing low frequency components and part Sum of Detail coefficients ( SD ) containing high frequency components derived from WSVD are defined, and the mother wavelet is selected as a characteristic of WSVD. The characteristics of SA and SD are analysed in various fault conditions to detect the faults and classify between those faults. An algorithm is proposed based on the results of SA and SD to detect and classify various faults. The various simulation results are performed and the results are analysed. In summary, we propose an algorithm which can detect and classify faults in transmission system using WSVD for wide-area protection.
2. Modeling of Wide-Area Transmission System in Korea
The nationwide electrical power transmission network in Korea was modelled using the EMTP-RV. The system parameters used in modelling are the real system data in the PSS/E files provided by KEPCO and KPX [18] .
The nominal voltages of the power transmission network in Korea are composed of 154 kV, 345 kV, and 765 kV. The target network is all the transmission lines of 345 kV and 765kV in 2008 [19 - 22] . The transmission lines of 154 kV are treated as a load. The modelled system is operated based on the peak load condition in summer 2008. The total load is 54,647 MVA (The Active Power is 54,300 MW and the Reactive Power is 6,150 MVar). The total generation is 57,001 MVA (55,070 MW and 14,713 MVar) and the loss of transmission lines over 154 kV is about 2 %.
Fig. 1 shows the wide-area transmission system of Korea modelled by EMTP-RV [20] . Simulations are performed in steady state for 10 seconds in order to validate the performance of the modelled network. Frequencies are measured at the nine buses: Dongseoul No. 1, Sinsiheung No. 3, Asan No. 3, Sinjechun No. 3, Chungyang No. 3, Seodaegu No. 3, Uiryung No. 3, Singoangju No. 3, and Bukbusan No. 3s.
PPT Slide
Lager Image
Power system network modeled by EMTP-RV.
In the simulated results, the lowest frequency is 59.9931 Hz at Uiryung No. 3, and the highest frequency is 60.0002 Hz at Seodaegu No. 3. As the frequencies vary within less than 0.01 Hz, we can confirm that the modelled network operates in a stable state.
3. Characteristic Analysis of Disturbance Using Wavelet Singular Value Decomposition
- 3.1 Wavelet transform
The WT is able to extract time and frequency information at the same time from the original signal [23 - 26] . The Discrete Wavelet Transform ( DWT ) of a signal is defined as:
PPT Slide
Lager Image
where ψ [ k ] is mother wavelet,
PPT Slide
Lager Image
is a scale parameter, and
PPT Slide
Lager Image
is the time shift of ψ [ k ] [26] .
The Results of DWT depend on the mother wavelet. One characteristic of the mother wavelet is that the mean value is zero within a certain period of time. The Daubechies 4 (db4) wavelet is usually used as a mother wavelet for transient analysis in power systems.
The WT consists of successive pairs of low-pass and high-pass filters. For each pair, the high-scale and low-frequency components are called approximation coefficients of WT, while the low-scale and high-frequency components are called detail coefficients. The approximation coefficient and detail coefficient constitute the WT-coefficient matrix [24] .
- 3.2 Singular value decomposition
Singular Value Decomposition (SVD) is a powerful and effective tool to extract special features in linear algebra. SVD is a factorization of the matrix. For any matrix
PPT Slide
Lager Image
, matrix A can be decomposed as:
PPT Slide
Lager Image
where U is an m × m orthonormal eigenvector matrix of AAT , and V is an n × n orthonormal eigenvector matrix of ATA . Then, Σ is an m × n matrix that can be written as:
PPT Slide
Lager Image
Here, S diag( σ 1 ,··· σr ) = is a diagonal matrix by, r × r and σ is called a singular value that is calculated by SVD. SVD has information about the magnitude of the signal, which be used for analysis [26 - 27] .
- 3.3 Wavelet singular value decomposition
Wavelet Singular Value Decomposition (WSVD) is a type of wavelet transform with SVD [17] . The approximation and detail coefficients a1 and d1 are calculated through the decomposition and reconstruction process on the level 1 DWT with the signal x from a moving window of size n . The sizes of the x , a1 , and d1 become n as well. The Singular value of Approximation ( SA ) is a singular value to be calculated by (4) using a1 . The Sum of the absolute value of Detail ( SD ) is calculated by (5) and (6) using d1 .
PPT Slide
Lager Image
PPT Slide
Lager Image
PPT Slide
Lager Image
Here, i is the starting time of sampling of the moving window, and lf is the filter size according to the mother wavelet. In order to suppress the negative effect of the DWT filter caused by applying the moving window techniques, SD1 is calculated to remove the value at both ends of d1 during the calculation. The value of d1 is calculated by a decomposition and reconstruction process of the level 1 DWT of the signal s[n] using Daubechies 4 (db4) as the mother wavelet based on a moving window with a size of 24 (a half cycle). In this process, assuming that the size of the filter is 8 and the high-pass filters are HD1, HD2, ···· and HD8, then d1 [1] - d1 [6] and d1 [19]- d1 [24] do not have a pattern in d1 because of the influence of duplicated signals for convolution multiplication. However, d1 [7] - d1 [18] have a pattern in d1 because they are not impacted by the signal duplication for convolution multiplication. Fig. 2 shows a sine waveform of one cycle as an original signal. a1 and d1 are the results of the decomposition and reconstruction process of db4 with the level 1 DWT. The d1 curve shows fluctuation at both ends.
PPT Slide
Lager Image
a1 and d1 for a sinusoidal signal
- 3.4 Analysis of fault-type characteristics based on WSVD
The various faults are simulated in the model of the 345kV transmission system shown in Fig. 3 . We model 345kV transmission system using EMTP-RV. Lines applied to the system are non-transposed constant parameter model and average parameters of ACSR 480mm 2 – 4 bundled lines, usually used in 345kV transmission system of Korea, are utilized. Fig. 3 and Table 1 indicate the transmission system model and parameters of line used, respectively.
PPT Slide
Lager Image
345kV transmission system model
Line parameters
PPT Slide
Lager Image
Line parameters
The simulation conditions are as follows:
  • 1) Fault types:- Single line-to-ground (SLG)- Double line-to-ground (DLG)- Line-to-line short circuit (DLL)- Three-phase fault (3Φ)
  • 2) Distances of faulting position from bus 1 [km]- 5, 10, 15, 20, 40, 60, 80, 100, 120, 140, 160, 180, 200, 220, 240, 260, 280, 285, 290, 295
  • 3) Fault inception angles [°]- 0, 30, 45, 60, 90, 120, 135, 150, 180
  • 4) Fault resistances [Ω]- Line-to-ground fault: 20, 50, 100- Line-to-line fault: 0, 50, 100- Three-phase line-to-line fault: 0
The measured original signals are each phase voltage measured at bus 1 or bus 2 after the faults. The sampling frequency is 2.88 kHz, the size of a moving window is 24 (half cycle), and the mother wavelet is db4, which is generally used for analysing transience in electrical power systems [26 - 28] . Figs. 4 and 5 show the SA and SD of each simulated fault. In Figs. 4 and 5 , (a) shows SLG, (b) shows DLL, (c) shows DLG, and (d) shows three-phase fault (3Φ).
PPT Slide
Lager Image
Variation of the SA by fault type
PPT Slide
Lager Image
Variation of the SD by fault type
In the case of SLG, the variations of SA have the same trend as the original voltage signal. The voltage of the faulty phase is decreased, while that of the healthy phases is increased. The difference value between the faulty and the healthy phase is almost double compared with the normal conditions, as shown in Fig. 4(a) . The magnitude of SD at the faulty phase is generally higher than that of the healthy phase. In the case of DLL, the magnitudes of the original voltages at the faulty phases are smaller than that in the healthy phase. The magnitude of SD at the fault phases increase rapidly, as shown in Fig. 5(b) . As shown in Fig. 4(c) , the result of DLG is very similar to that of DLL, but the magnitude of the healthy phase in case of DLG experiences small variance caused by the faulty phase. In the case of a 3Φ fault, the original voltage magnitude of the faulty phases is decreased rapidly, but the results are relatively low. The magnitudes are shown according to the fault resistance and the fault inception angle. The variation of SA is shown in Fig. 4(d) , and the SD is shown in Fig. 5(d) .
- 3.5 Characteristic analysis of generator loss
Simulations of generator loss are performed by tripping the Busan C/C, Ulsan C/C, Ulsan T/P, and Kori N/P. The simulation conditions include the tripping generator group, with a maximum voltage of phase and a minimum voltage of phase a, and a total of 42 simulations are conducted. Each group of selected generators is connected to the bus of each generator group, which include 8 units of Busan C/C, 6 units of Ulsan C/C, 3 units of Ulsan T/P, and 4 units of Kori N/P. The measuring point of voltage is the North Busan 3S bus, and the signals are processed with WSVD.
Fig. 6 shows the variation of SA and SD caused by generator loss. SA shows a similar pattern to that of DLL or 3Φ fault. SD shows the results to be discriminated with SA that are different from those with a 3Φ fault. However, the maximum variation rates of each phase are similar.
PPT Slide
Lager Image
Variation of SA and SD by generator loss
- 3.6 Characteristic analysis of load shedding
Simulations of load shedding are performed by tripping the loads at North Busan 3S and New Ulsan 3S buses from 5% to 40 % by 5% increments. A total of 32 simulations are performed, considering the magnitude of voltage at the closing point. The measuring point for the voltage signal is at North Busan 3S, and the signals are processed with WSVD.
Fig. 7 shows the variation of SA and SD by load shedding. SA increases by 0.01 p.u. due to the load shedding of 350 MVA. SD shows the results between DLL and 3Φ fault. The variations of SD are doubled compares to the normal state.
PPT Slide
Lager Image
Variation of SA and SD by load shedding
4. Algorithm for Fault Detection and Classification
- 4.1 Method of the fault detection
The characteristics of SA and SD according to the fault types were analysed in Section 3. Based on the characteristics, SD is selected to detect faults. This is because the variation of SD is more severe than that of SA when a fault occurs.
Fig. 8 compares the results of WSVD transformation of the 345-kV phase voltage signal and that of the same signal with SNR 100 of Additive White Gaussian Noise (AWGN). SA and SD for the signal only remain unchanged, while those for the signal with AWGN show variations. Apparently, SD fluctuates much more than SA when noise is added. Fig. 9 shows the differential value of SD with 1 cycle. The maximum differentiated value is 0.6. Therefore, the threshold value to detect a fault in the 345-kV transmission line, α, is set to 1 with some margin. The value can be adjusted by considering conditions of the power system and operational requirements.
PPT Slide
Lager Image
WSVD signal added AWGN (Additive White Gaussian Noise)
PPT Slide
Lager Image
Differential value of SD added AWGN
- 4.2 Method of fault-type classification
Several indices are defined to classify fault types based on the aforementioned characteristics of SA and SD : NSA (Normalized maximum SA ; ΔSA ), AR (Ranked SA ), NSD (Normalized maximum SD ; ΔSD ), and NSS (Normalized Settled SD ; ΔSD ). The zero sequence voltage V0 is introduced to determine whether the fault is symmetric or asymmetric.
NSA is the ratio of the absolute value of SA in normal conditions to that of the maximum change of SA for a cycle after a fault calculated in (7). The (8) calculates the last NSA to select the faulty phase. If the value is bigger than the threshold β , it becomes 1, but it is otherwise 0.
NSD is the ratio of the absolute value of SD in normal conditions to that of the maximum change of SD for a cycle after a fault, as shown in (9). The threshold values associated with NSD are δ = 0.001, γ = 0.5, and ζ = 0.75. The threshold value δ identifies line-to-line faults, γ double line-to-ground faults, and ζ three-phase faults from generator loss.
NSS is the ratio of the absolute value of SD in normal conditions to that of the maximum change of SD for a cycle after a fault, as shown in (10). η is the threshold value associated with NSS , and is set at 0.75. It identifies three-phase fault from generator trips.
β, δ, γ, ζ, and η used as threshold values that are related to the ratio values of SA and SD , and they are not directly associated with the transmission system.
PPT Slide
Lager Image
PPT Slide
Lager Image
PPT Slide
Lager Image
PPT Slide
Lager Image
- 4.3 Algorithm for fault detection and fault-type classification
The proposed algorithm detects and classifies the fault using the methods described in Sections 1 and 2. 12 types of fault are numbered as shown in Table 2 . Figs. 10 and 11 describe the proposed algorithm, and pe in the figures is the sample number for one cycle.
The variable value of each fault type
PPT Slide
Lager Image
The variable value of each fault type
PPT Slide
Lager Image
Main Flow Chart of the algorithm for fault detection and fault type classification using WSVD
PPT Slide
Lager Image
Algorithm for fault detection and type classification using WSVD
5. Simulation and Discussions
- 5.1 Simulation conditions
The various faults are simulated in the 345kV transmission system presented in Fig. 3 , to verify the algorithms. A total of 56,744 simulations are conducted, until the failed cases become 20 times.
Simulation conditions consist of various fault distances, fault types, fault resistances, and fault inception angles, as follows:
  • - Fault distance: randomly selected, between 1~299 km from bus 1, with a unit of 1 km
  • - Fault type: randomly selected
  • - Fault resistance: randomly selected, between 1 and 100 Ω, with a unit of 1 Ω
  • - Fault inception angle: randomly selected, by starting a fault at random time within 1 cycle, with a unit of 0.1 ms
Faults are simulated using EMTP. The results from EMTP were converted to a format compatible to MATLAB, and WSVD was performed in MATLAB.
- 5.2 Simulation results of fault detection and classifycation
Fig. 12 shows the simulation results of fault classifycation for various fault types. Table 3 shows the results of the simulations. It shows the times of simulation and failure, and success rate of the fault type classification for each fault type. SLG, DLL, and 3Φ fault classified 100% correctly. However, the success rate of DLL classification was 99.88%. The total success rate of fault classification is 99.96%.
PPT Slide
Lager Image
Results of fault classification for the various fault types
Verification result of faults classification
PPT Slide
Lager Image
Verification result of faults classification
The most failed cases for the fault type classification are DLG faults with the distance of 23 km and 277 km from the bus. The three phase voltage, SA and SD of this case are shown in Fig. 13 . In the cases of the DLG fault, if the distance is 23 or 277 km, it shows that the SA of the faulted phase does not rapidly decrease, hence β of the faulted phase becomes less than 1. As a result of NSA1 , the algorithm classifies the SLG fault. However, the fault would be detected, if the detecting period becomes 2 cycles.
PPT Slide
Lager Image
The failed case of the fault type classification (DLG, Distance of fault: 23km, Fault Resistance: 54Ω)
6. Conclusion
Modelling of the 345-kV and 765-kV Korean nationwide power system network in EMTP-RV has been described based on real data in PSS/E files provided by KEPCO and KPX. Based on the modelled system, an algorithm for wide-area protection in the Korean transmission system has been proposed. The proposed algorithm consists of fault detection and classification. The method for fault detection and classification using WSVD was also discussed. Various simulation conditions were performed to analyse the characteristics at each fault in the 345-kV transmission model system. The characteristics in various fault conditions using WSVD were analysed. With the analysis results, NSA, AR, NSD, and NSS were designated with proper values for fault detection and classification. All algorithms for wide area protection, including fault detection and fault type classification are validated through various simulation conditions. The algorithms of fault detection and type classification work perfectly in the simulations.
By using the proposed algorithm, national wide monitoring and supervising system can be monitoring and classifying of the faults in national wide-area transmission network as a new way redundantly with the SCADA (Supervisory Control and Data Acquisition) and EMS (Energy Management System) in order to be more reliable operation when the signal can be acquired by PMU on national wide.
Acknowledgements
This research was supported by Basic Science Research Program through the National Research Foundation of Korea (NRF) funded by the Ministry of Education, Science and Technology (No. NRF-2013R1A1A2009294)
BIO
Jae-Won Lee was born in Korea, 1954. He received his B.S. in electrical and computer engineering from Sungkyunkwan University, Suwon, Korea in 1975 and M.S. degree in engineering from Yonsei University, Seoul, Korea in 1989. He is now working toward his Ph.D. degree at Sungkyunkwan University in Korea. He was in charge of facility design, operation and management at Plant Engineering for 25 years. Currently, he is working as a Principal Engineer at Seoul EM Co., Ltd in Korea. His research interests include power system protection, analysis and system design. Mr. Lee is a Registered Professional Engineer in Korea and APEC Engineering Associations.
Won-Ki Kim was born in Korea, 1987. His research interests include power system transients, protection and stability. He received his B.S and M.S degrees in School of Electrical and Computer Engineering from Sungkyunkwan University, Korea, 2010 and 2012.
Yun-Sik Oh was born in Korea, 1987. At present, he is working on his Ph. D thesis at Sungkyunkwan University. His research interests include power system transients, protection and stability. He received his B.S and M.S degrees in School of Electrical and Computer Engineering from Sungkyunkwan University, Korea, 2011 and 2013.
Hun-Chul Seo was born in Korea, 1982. He received his B.S and M.S degrees in School of Electrical and Computer Engineering from Sungkyunkwan University, Korea, 2004 and 2006. He worked for Korea Electrical Engineering & Science Institute, Seoul, Korea, as a researcher in power system division from 2006 to 2009. He was a post-doctoral fellow in the dept. of electrical engineering, Yeungnam University, Korea, from Sep. 2013 to Jan. 2014. From Mar. 2014, he is an assistant professor with the School of IT Engineering, Yonam Institute of Digital Technology, Korea. His research interests include power system transients, protection and stability.
Won-Hyeok Jang He received his B.S. and M.S. in Electrical and Computer Engineering from Sungkyunkwan University, Suwon, Korea in 2008 and 2010, respectively. He is now working toward his Ph.D. degree at University of Illinois at Urbana-Champaign. He is a Research Assistant in Electrical and Computer Engineering Department, University of Illinois at Urbana-Champaign. His research interests include power system modeling and analysis.
Yoon Sang Kim obtained B.S., M.S., and Ph.D. degrees in Electrical Engineering from Sungkyunkwan University, Seoul, Korea, in 1993, 1995, and 1999, respectively. He was a member of the Postdoctoral Research Staff of Korea Institute of Science and Technology (KIST), Seoul, Korea. Likewise, he was a Faculty Research Associate in the Department of Electrical Engineering, University of Washington, Seattle. He was a Member of the Senior Research Staff, Samsung Advanced Institute of Technology (SAIT), Suwon, Korea. Since March 2005, he has been a professor at the School of Computer and Science Engineering, Korea University of Technology Education (KOREATECH), Cheonan, Korea. His current research interests include Virtual simulation, Power-IT technology, and device-based interactive application. Dr. Kim was awarded the Korea Science and Engineering Foundation (KOSEF) Overseas Postdoctoral Fellow in 2000. He is a member of IEEE, IEICE, ICASE, KIPS, and KIEE.
Chul-Won Park was born in Korea in 1961. He received his B.S., M.S. and Ph.D. degrees in Electrical Engineering from Sungkyunkwan University(SKK), Seoul, Korea, in 1988, 1990, and 1996, respectively. From 1989 to 1993 he was an associate researcher at Lucky GoldStar Industrial Systems. From 1993 to 1996, he was a senior researcher at PROCOM system and lecturer at S.K.K. University. At present, he is a professor in the Department of Electrical Engineering at Gangneung-Wonju National University, since 1997. His research interests include smart grid, power IT, IED, power system modeling and control, and computer application in power system. He is a member of the KIEE. Dr. Park was awarded Paper Prize of KIEE in 2010.
Chul-Hwan Kim was born in Korea, 1961. In 1990 he joined Cheju National University, Cheju, Korea, as a full-time Lecturer. He has been a visiting academic at the University of BATH, UK, in 1996, 1998, and 1999. Since March 1992, he has been a professor in the School of Electrical and Computer Engineering, Sungkyunkwan University, Korea. His research interests include power system protection, artificial intelligence application for protection and control, the modelling / protection of underground cable and EMTP software. He received his B.S and M.S degrees in Electrical Engineering from Sungkyunkwan University, Korea, 1982 and 1984, respectively. He received a Ph.D in Electrical Engineering from Sungkyunkwan University in 1990. Currently, he is a director of Center for Power IT (CPIT) in Sungkyunkwan University.
References
Mudathir F. A. , Hashim H. 2009 “Wavelet Transforms: Practical Applications in Power Systems” Journal of Electrical Engineering & Technology 4 (2) 168 - 174    DOI : 10.5370/JEET.2009.4.2.168
Xu X. , Kezunovi M. 2002 “Automated feature extraction from power system transients using wavelet transform” IEEE Trans. on Power Delivery 17 19994 - 1998
Thomas W. P. , Christopulo C. 1992 “Ultra-high speed protection of series compensated lines,” IEEE Transactions on Power Delivery 7 139 - 145    DOI : 10.1109/61.108900
M. Thomas Jamil , Moinuddin M. S. , Kumar P. 1999 “Fuzzy approach to fault classification for transmission line protection,” Proc. IEEE Tencon 99 Conf. 2 1046 - 1050
Girgis A. , Sallam A. A. , El-Din A. Karim 1998 “An adoptive protection scheme for advanced series compensated (ASC) transmission lines,” IEEE Transaction on Power Delivery 13 (2) 414 - 420
Zheng-you H.E. , Yu-mei C.A.I. , Qing-quan Q. 2005 ‘A study of wavelet entropy theory and its application in electric power system fault detection [J]’ Proc. CSEE 5
Megahed A. I. , Moussa A. M. , Bayoumy A. E. 2006 ‘Usage of wavelet transform in the protection of series-compensated transmission lines’ IEEE Trans. Power Deliv. 21 (3) 1213 - 1221
Das B. , Reddy J. V. 2005 “Fuzzy-logic-based fault classification scheme for digital distance protection,” IEEE Transactions on Power Delivery 20 609 - 616    DOI : 10.1109/TPWRD.2004.834294
Mahanty R. N. , Dutta Gupta P. B. 2007 “A fuzzy logic based Fault classification approach using current samples only,” Int. J. Elect. Power Syst. Res. 77 501 - 507    DOI : 10.1016/j.epsr.2006.04.009
Hagh M.T. , Razi K. , Taghizadeh H. 2007 “Fault Classification and Location of Power Transmission lines using artificial neural network” The 8th International Power Engineering Conference (IPEC 2007) 1109 - 1114
Wang H. , Keerthipala W. W. L. 1998 “Fuzzy-neuro approach to fault classification for transmission line protection,” IEEE Transactions on Power Delivery 13 (4) 1093 - 1104    DOI : 10.1109/61.714467
Dash P. K. , Samantaray S. R. , Panda G. 2007 “Fault classification and section identification of an advanced series-compensated transmission line using support vector machine,” IEEE Transactions on Power Delivery 22 (1) 67 - 73    DOI : 10.1109/TPWRD.2006.876695
Gracia J. , Mazon A. J. , Zamora I. 2005 “Best ANN ructures for fault location in single and double circuit transmission lines” IEEE Trans. on power Delivery 20 (4) 2389 - 2395    DOI : 10.1109/TPWRD.2005.855482
Zhengyou H. , Xian W. , Qingquan Q. 2004 “Automatic Fault Detection for Power System using Wavelet Singular Entropy” 2004 International Conference on Intelligent Mechatronics and Automation 433 - 437
Silva K. M. , Souza B. A. , Brito N. S. D. 2006 “Fault detection and classification in transmission lines based on wavelet transform and ANN” IEEE Trans. Power Delivery 21 (4) 2058 - 2063    DOI : 10.1109/TPWRD.2006.876659
Zhengyou H. , Ling F. , Sheng L. , Zhiqian B. 2010 “Fault Detection and Classification in EHV Transmission Line Based on Wavelet Singular Entropy” IEEE Trans. On Power Delivery 25 (4) 2156 - 2163    DOI : 10.1109/TPWRD.2010.2042624
Tse N.C.F. 2006 “Practical application of wavelet to power quality analysis” IEEE Power Engineering Society General Meeting, 2006
2009 "Index Parameter of the Power Transmission System in 2009" System Operation Dept.
Kim Yoon Sang , Kim Chul-Hwan , Ban Woo-Hyeon , Park Chul-Won 2013 “A Comparative Study on Frequency Estimation Methods” Journal of Electrical Engineering &Technology 8 (1) 70 - 79    DOI : 10.5370/JEET.2013.8.1.070
Park Chul-Won , Shin Dong-Kwang , Kim Chul-Hwan , Kim Hak-Man , Kim Yoon Sang 2011 “Study on Advanced Frequency Estimation Technique using Gain Compensation” Journal of Electrical Engineering & Technology 6 (4) 439 - 446    DOI : 10.5370/JEET.2011.6.4.439
Oh Yun-Sik , Seo Hun-Chul , Yang Jeong-Jae , Kim Chul Hwan 2011 “Development of a Reclosing Scheme for Reduction of Turbine Generator Shaft Torsional Torques: A Decision Method to Achieve Optimal Reactor Capacity” Journal of Electrical Engineering & Technology 9 (4) 1145 - 1153
Yeo Sang-Min , Jang Won-Hyeok , Kim Chul-Hwan 2013 “Algorithm for Fault Location Estimation on Transmission Lines using Second-order Difference of a Positive Sequence Current Phasor” Journal of Electrical Engineering& Technology 8 (3) 499 - 506    DOI : 10.5370/JEET.2013.8.3.499
Bao. P , Xiaohu Ma 2005 “Image Adaptive Watermarking using Wavelet Domain Singular Value Decomposition,” IEEE Trans. on Circuits and Systems for Video Technology 15 (1) 96 - 102    DOI : 10.1109/TCSVT.2004.836745
Kim Chul-Hwan , Kim Hyun , Ko Young-Hun , Sung HyunByun , Aggarwal R.K. , Johns A.T. 2002 “ A novel fault-detection technique of high-impedance arcing faults in transmission lines using the wavelet transform” IEEE Trans. on power Delivery 17 (4) 921 - 929    DOI : 10.1109/TPWRD.2002.803780
Pham V. L. , Wong K.P. 1999 “Wavelet-transform-based algorithm for harmonic analysis of power system waveforms” Generation, Transmission and Distribution, IEE Proceedings 146 (3) 249 - 254    DOI : 10.1049/ip-gtd:19990316