Advanced
Study on Influences and Elimination of Test Temperature on PDC Characteristic Spectroscopy of Oil-Paper Insulation System
Study on Influences and Elimination of Test Temperature on PDC Characteristic Spectroscopy of Oil-Paper Insulation System
Journal of Electrical Engineering and Technology. 2015. May, 10(3): 1107-1113
Copyright © 2015, The Korean Institute of Electrical Engineers
This is an Open-Access article distributed under the terms of the Creative Commons Attribution Non-Commercial License (http://creativecommons.org/licenses/by-nc/3.0/)which permits unrestricted non-commercial use, distribution, and reproduction in any medium, provided the original work is properly cited.
  • Received : July 09, 2014
  • Accepted : November 25, 2014
  • Published : May 01, 2015
Download
PDF
e-PUB
PubReader
PPT
Export by style
Article
Author
Metrics
Cited by
TagCloud
About the Authors
Xiao Liu
Corresponding Author: State Key Laboratory of Power Transmission Equipment and System Security and New Technology, Chongqing University, China. (liuxiaocqu@163.com)
Ruijin Liao
State Key Laboratory of Power Transmission Equipment and System Security and New Technology, Chongqing University, China.
Yandong Lv
Alstom Grid Technology Center Co. Ltd, Shanghai, China.
Jiefeng Liu
State Key Laboratory of Power Transmission Equipment and System Security and New Technology, Chongqing University, China.
Jun Gao
State Key Laboratory of Power Transmission Equipment and System Security and New Technology, Chongqing University, China.
Jian Hao
State Grid Chongqing Electric Power Co. Electric Power Research Institute, Chongqing, China.

Abstract
Test temperature is an important factor affecting the measurement results of dielectric response of field power transformers. In order to better apply the polarization and depolarization current (PDC) to the condition monitoring of oil-paper insulation system in power transformers, the influences and elimination method of test temperature on PDC characteristic spectroscopy (PDC-CS) were investigated. Firstly, the experimental winding sample was measured by PDC method at different test temperatures, then the PDC-CS was obtained from the measurement results and its changing rules were discussed, which show that the PDC-CS appears a horizontal mobility with the rise of temperature. Based on the rules, the “time temperature shift technique” was introduced to eliminate the influence of test temperature. It is shown that the PDC-CS at different test temperatures can be converted to the same reference temperature coincident with each other.
Keywords
1. Introduction
The safe operation of power transformers is of great significance. According to relevant statistics, operation faults of transformers are mainly caused by the failure of insulation system [1 , 2] . The main insulation system of power transformer containing oil and paper will degrade under a combined action of thermal, electrical, mechanical and chemical stresses during transformer routine operation [3 , 4] . Therefore, accurate assessment for insulation condition of power transformers turn out to be significant, based on which, effective strategies like maintenance or replacement then can be taken.
Correlative data [5] have indicated that the lifetime of transformer insulation is determined by the solid insulation (insulation paper and pressboard). In other words, the evaluation of insulation cellulose condition will be the key to access the aging states of transformers. So far, three kinds of traditional diagnosis methods for transformer oil-paper insulation aging status have been recognized widely as the follows: Dissolved Gas Analysis (DGA) [6] , test of furfural content in the oil [7] , and test of degree of polymerization of insulation cellulose [8] . However, there are obvious deficiencies about these methods. For example, due to the oil replacement for transformers, the method of physical-chemical inspection focused on insulation oil may not reflect the facts. On the other side, although DP can reflect the most reliable aging status of insulation cellulose, it will damage insulation system in turn and needs removing the transformer covers to get test samples.
In recent years, new diagnosis methods including Return Voltage Method (RVM) [9] , Polarization and Depolarization Current (PDC) [10 , 11] , Frequency Domain spectroscopy (FDS) [12] based on dielectric response, have drew much attention with the advantages of no sampling and non-invasive measurement, etc. Contrasting the above methods with each other, we can see that: RVM method can’t distinguish the different influences of insulation oil and paper on characteristic spectroscopy which makes it difficult in practical application; FDS method performs without the problems in RVM, but it takes too much time for measurement limited to field test; PDC method with advantages of short test time and abundant information of insulation is very suitable for noninvasive diagnosis of field transformer oil-paper insulation ageing status which will be discussed in this paper.
It is worth mentioning that the test temperature is one of the most important factors affecting measurement results of dielectric response [13 , 14] . That is to say, PDC measurement results onsite will be possibly different at different time one day, and in different seasons due to the changing temperatures. So it needs further research on this issue, otherwise the application of PDC method will be hard. Many scholars have done relevant research. Reference [15] discovered that dielectric response measurement is greatly affected by test temperature, which will result in inaccurate state assessment of oil-paper insulation. It is shown in [16] that with rising temperature, conductivity and polarization/depolarization current of oil-paper insulation gradually increase. Analogously, the effect of test temperature on PDC measurement was studied in [17] with the conclusion that with the rise of test temperature, polarization/depolarization current of test object also gradually increase and decay more quickly with test time passing by. However, the study didn’t mention how to eliminate the influence of test temperature. Reference [18] proposed a new method calling “stable depolarization charge quantity” to access aging status of oil-paper insulation which had similar conclusions with [17] . But it also hasn’t studied the influence of test temperature on “stable electric quantity depolarization” and its elimination method.
Going further with the current studies, this paper focuses on the influence and elimination of test temperature on PDC characteristic spectroscopy of oil-paper insulation. The following work have been done: firstly, experimental sample was measured by PDC method under different test temperatures; then, the PDC-CS was obtained from the test results by a new method and the influence of test temperature on it was exposed; lastly, a method called “time temperature shift technique” was introduced to eliminate the influence of test temperature on the PDC-CS.
2. Preparation of Test Sample and PDC Measurement
- 2.1 Preparation of oil-paper insulation
The test object-winding model was shown in Fig. 1 .
PPT Slide
Lager Image
Geometric construction of measured winding
The copper plate was wrapped by ten layers of insulation paper, and the insulation paper was wrapped by three sections of aluminum foils to get a good measurement result. Insulation materials used in the experiment included 25# transformer oil from Karamay Sinkiang, insulation paper made from ordinary cellulose each with a thickness of 75μm and winding from Chongqing ABB.
- 2.2 Process of PDC measurement
The process of PDC test was conducted as follows: firstly, the winding sample was placed in fresh oil for impregnation, then it was put into a flask which, in the next, was kept in oil bath with initial temperature of 40℃. After sample reached the target temperature, the flask was sealed and kept for two days until the moisture content between insulation oil and paper reached balance. After that, PDC measurement was carried out with the parameter setting: measurement voltage was set as U 0 =200V, and polarization and depolarization time were both set to 5000s. The winding sample was measured by PDC-Analyser-1MOD from company ALFF ENGINEERING in Switzerland. After measurement, high and low voltage electrodes of winding were shorted to release the residual charges in sample. Then, test temperature was raised and kept at 55℃ also for two days. Analogously, the above steps were repeated for the next measurement. As a rule, test temperature was 15℃ higher than the former one for each new measurement. Through the process, we got PDC measurement results of sample at different test temperatures of 40℃, 55℃, 70℃, 85℃ and 100℃.
3. Test results and analysis
- 3.1 PDC measurement results of winding sample with different test temperatures
Fig. 2 shows the polarization and depolarization current of winding sample with different test temperatures. It can be seen that test temperature has great effect on measurement results. With the rise of test temperature, polarization and depolarization current gradually increase with faster attenuation and higher stable value in the end of the test. Moreover, the depolarization current appears an inflection point at high temperature. The rules above can be explained by: with rising temperature, average kinetic energy, movement speed, and migration rate of polarization and conductive particles in samples increase, leading the increase of the sample conductivity [15 , 19] .
PPT Slide
Lager Image
PDC curves with different test temperatures
- 3.2 Acquisition of PDC-CS and the influences of test temperature
Since there aren’t obvious rules between test temperature and PDC measurement results directly, one or more characteristic quantities should be obtained from the measurement results for the further study.
Reference [20] proposed a characteristic parameter-“depolarization charge quantity” to access the aging status of transformer oil-paper insulation defined as Eq. (1).
PPT Slide
Lager Image
Some research had been taken on the influence of aging on the PDC-CS with the conclusion that depolarization charge quantity- Qdep ( t ) appears exponential growth with oil-paper insulation gradually aging. However, the quantitative connection of test temperature and Qdep ( t ) was not discussed. So Qdep ( t ) will be chosen as a characteristic quantity to study the influence and elimination of test temperature on PDC measurement.
Before discussing test temperature, a new characteristic parameter will be first introduced. Referring to the definition of Qdep ( t ) in Eq. (1), computing the integral for polarization current gets the polarization charge quantity - Qp ( t ) shown as Eq. (2).
PPT Slide
Lager Image
Compared with Qdep ( t ), Qp ( t ) carries more insulation information by the reason of polarization current contenting both conduction current and polarization current. This new characteristic parameter can play an important role in accessing oil-paper insulation condition of power transformers, meanwhile, provide a comparison to the former one to verify the effectiveness of the elimination method for the influences of test temperature.
Fig. 3 shows the varying pattern of PDC-CS of Qp ( t ) and Qdep ( t ) with different time and test temperatures(logarithm for abscissa, and linearity for ordinate).
PPT Slide
Lager Image
Calculated and fitted values of polarization and depolarization charge quantity with different temperatures
We can see that with test temperature rising, Qp ( t ) varies little in test period 10 0 ~10 2 s, but increases in 10 2 ~5×10 3 s significantly. While Qdep ( t ) increases in the whole period of depolarization, and also increase much more quickly in 10 2 ~5×10 3 s. This is because polarization and depolarization current become slow to decay in 10 2 ~5×10 3 s.What’s more, both Qp ( t ) and Qdep ( t ) increase faster with higher test temperature and appear a horizontal mobility with the rise of temperature. Superior to polarization and depolarization current, the PDC-CS collects more insulation information along with a period of test time, and will be more reliable compared to a series of test points. So, the PDC-CS is influenced by test temperature more strongly and regularly.
According to [21] , the relaxation currents can be modeled by exponentials. As the integral of relaxation currents, the PDC-CS also meets the general model. Table 1 and Table 2 show the fitting relationship between Qp ( t ) and Qdep ( t ) and test time under different test temperatures which meet the exponential function with the goodness of fit up to 0.99.
Fitting relation between polarization charge quantityQp(t) and test temperature
PPT Slide
Lager Image
Fitting relation between polarization charge quantity Qp(t) and test temperature
Fitting relation between depolarization charge quantityQdep(t) and test temperature
PPT Slide
Lager Image
Fitting relation between depolarization charge quantity Qdep(t) and test temperature
- 3.3 Elimination method for influences of test temperature on PDC-CS
In the research of aging characteristics and aging mechanism of transformer oil-paper insulation, reference [22] found an idea called “time- temperature superposition [23] ”, which can be used as a guidance to improve the thermal aging model of oil-paper insulation by introducing the second order kinetics model. Based on the above thoughts and the change rule discussions of PDC-CS in section 3.2, a method of eliminating the influences of test temperature will be introduced, called “time temperature shift technique”.
Firstly, the Qp ( t ) curve under 40℃ is chosen as the master curve -“S 1 ”. Then, the rest of the Qp ( t ) curves under 55℃, 70℃, 85℃ and 100℃ are moved along time axis to S 1 horizontally, so does the treatment of the Qdep ( t ) curves. Through the translation, different curves almost coincide with each other. The combination of these curves form a new feature curve called “S 2 ”. In this way, differences of the PDC-CS caused by test temperatures have been basically eliminated. The curves before and after translation are shown in Fig. 4 .
PPT Slide
Lager Image
Formation of master curve of PDC characteristic spectroscopy
For the purpose of forming the new feature curve S 2 , a variable-“time temperature shift factor” is defined as:
PPT Slide
Lager Image
Where: tref is the time corresponding to a certain point on PDC-CS after translation; tT is the time corresponding to the same point before shift. In other words, αT is equivalent to the change of length of curves for the horizontal translation. The following will focus on the compute of αT by the example of Qp ( t ). The “time temperature shift factor” with 40℃ is defined as α 40 =1. Based on the change of time axis in Fig. 4(a) during the translation, computing the ratio of the time of one point in the curve before and after move, gets the “time temperature shift factor” αT as: α 55 =1.2656, α 70 =3.5473, α 85 =11.8059, α 100 =37.1810, which are shown in Fig. 4(a) .
Fitting αT with test temperature gets the exponential relationship as Fig. 5 shows, from which, the PDC-CS under any test temperature can be formed to the new feature curve to be classified into the same reference temperature. Conversely, once providing αT at any test temperature and the PDC-CS with reference temperature so called the master curve, the PDC-CS with all test temperatures can be figured out. So this method eliminates the influence of test temperature on PDC-CS and improves the reliability of transformer oil-paper insulation condition assessment.
PPT Slide
Lager Image
Fitting relation between time temperature shift factor and test temperature
It is worth mentioning that, through the method “time temperature shift technique”, the time horizon of the PDC-CS is expanded from 10 0 ~5×10 3 s to 10 0 ~10 5 s, which means, without any increase in test time, it can be realized to collect more information of PDC-CS. It is of great advantage to field test.
Obviously, before applying the PDC-CS- Qp ( t ) and Qdep ( t ) into condition assessment of field transformer oil-paper insulation, a large quantity of essential data of PDC features at different test temperatures should be collected and “time temperature shift factor” αT need to be further modified to ensure the accuracy.
4. Conclusion
In this paper, transformer winding sample was measured by PDC method at different test temperatures, and the PDC-CS was obtained from original data. Then the influences and elimination of test temperature on the PDC-CS were discussed. The conclusions are made as follows:
(1) Test temperature has great effect on polarization and depolarization current. With the rise of test temperature, polarization and depolarization current gradually increase and come to the stable value more quickly. An inflection point appears in depolarization current at high temperature.
(2) With rising test temperature, in the test period 10 0 ~10 2 s, Qdep ( t ) significantly increases, but Qp ( t ) basically keep unchanged. Qp ( t ) and Qdep ( t ) both increase in the test period 10 2 ~5×10 3 s, which appear a horizontal mobility.
(3) By introducing “time temperature shift factor” αT and constructing the new feature curve, the PDC-CS at any test temperature can be classified into the same reference temperature, thus the influence of test temperature can be eliminated.
Acknowledgements
This work was supported by the Funds for Innovative Research Groups of China (51021005). The authors thank the Alstom Grid Technology Center Co. Ltd for the support in materials as well as all the sponsors/collaborators of the project.
BIO
Xiao Liu He received the B.S. degree in electrical engineering from Chongqing University, Chongqing, China in 2013. He is currently a M.S. candidate in the School of Electrical Engineering, Chongqing University. His major research interests lie in the dielectric response analysis, condition assessment and insulation fault diagnosis of oil-paper insulation system for high voltage apparatus.
Ruijin Liao He received the M.S. and Ph.D. degrees in electrical engineering from Xi’an Jiaotong University, Xi’an, China and Chongqing University, Chongqing, China, respectively. Since 1999 he is a professor of Electrical Engineering School at Chongqing University, China. His major research interests include on-line monitoring of insulation condition and fault diagnosis for high voltage apparatus, and aging mechanism and diagnosis for power transformer.
Yandong Lv She received the B.S. and M.S. degrees from Harbin Institute of Technology, China. She joined Alstom Grid in 2009 and has worked on various optics including dielectric characteristics, aging mechanism, oil-paper insulation system of transformer, and new insulating material research for high voltage apparatus. Before joining Alstom Grid, she worked on the position relevant to the material and components specification for LV and MV apparatus.
Jiefeng Liu He received the B.S. and M.S. degrees in electrical engineering from Yanshan University, Qinhuangdao, China in 2008 and Chongqing University, Chongqing, China in 2011, respectively. He is currently a Ph.D. candidate in the School of Electrical Engineering, Chongqing University, China. His research activities are mainly in the aging mechanism and dielectric response characteristics of transformer oil-paper insulation system.
Jun Gao He received the B.S. degree in electrical engineering from Chongqing University, Chongqing, China in 2012. He is currently a Ph.D. candidate in the School of Electrical Engineering, Chongqing University, China. His major research interests include the dielectric response of oil-paper insulation system for high voltage apparatus, online detection of insulation condition of electrical devices for oil-paper insulation of high voltage apparatus.
Jian Hao He received both the B. Eng. degree and the B. Economic degree respectively in electrical engineering and economics and business administration, Chongqing University, China in 2007. He received the Ph.D. degree in 2012 from Chongqing University. His research activities are mainly in the field of aging mechanism, dielectric response characteristics and online monitoring of oil-paper insulation system.
References
Saha T. K. 2003 “Review of modern diagnostic techniques for assessing insulation condition in aged transformers” IEEE Transactions on Dielectrics andElectrical Insulation 10 (5) 903 - 917    DOI : 10.1109/TDEI.2003.1237337
Setayeshmehr A. , Fofana I. , Eichler C. 2008 “Dielectric spectroscopic measurements on transformer oil-paper insulation under controlled laboratory conditions” IEEE Transactions on Dielectrics and ElectricalInsulation 15 (4) 1100 - 1111    DOI : 10.1109/TDEI.2008.4591233
Ekanayake C. , Gubanski S. M. , Graczkowski A. 2006 “Frequency response of oil impregnated pressboard and paper samples for estimating moisture in transformer insulation” IEEE Transactions on Power Delivery 21 (3) 1309 - 1317    DOI : 10.1109/TPWRD.2006.877632
Liao R.J. , Yang L.J. , Zheng H.B. 2012 “Reviews on oil-paper insulation thermal aging in power transformers” Transactions of China Electrotechnical Society 27 (5) 1 - 12
Ali M. , Eley C. , Emsley A.M. 1996 “Measuring and understanding the ageing of kraft insulating paper in power transformers” IEEE Electrical Insulation Magazine 12 (3) 28 - 34
Rogers R.R. 1978 “IEEE and IEC codes to interpret incipient faults in transformer, using gas in oil analysis” IEEE Transactions on Dielectrics and Electrical Insulation EI-13 (5) 349 - 354    DOI : 10.1109/TEI.1978.298141
Emsley A. M. , Xiao X. , Heywood R. J. , Ali M. 2000 “Degradation of cellulosic insulation in power transformers. Part 2: Formation of furan products in insulating oil” IEE Proceedings Science, Measurement and Technology 147 (3) 110 - 114    DOI : 10.1049/ip-smt:20000259
Hill D.J.T. , Le T.T. , Darveniza M. , Saha T. 1995 “A study of degradation of cellulosic insulation materials in a power transformer, part 2. Tensile strength of cellulose insulation paper” Polymer Degradation and Stability 49 (3) 429 - 435    DOI : 10.1016/0141-3910(95)00100-Z
Kuang Y.C. , Chen G. , Jarmm P. “Recovery voltage measurement on oil-paper insulation with simple geometry and controlled environment” IEEE International Conference on Solid Dielectrics Toulouse, France 5-9 July 2004 739 - 742
Saha T.K. , Purkait P. 2004 “Investigation of polarization and depolarization current measurements for the assessment of oil-paper insulation of aged transformers” IEEE Transactions on Dielectrics andElectrical Insulation 11 (1) 144 - 154    DOI : 10.1109/TDEI.2004.1266329
Saha T. K. , Purkait P. 2004 “Effects of Temperature on Time-domain Dielectric Diagnostics of Transformers” Australian Journal of Electrical and Electronics Engineering 1 (3) 157 - 162
Gubanski S.M. , Boss P. , Csepes G 2003 “Dielectric response methods for diagnostics of power transformers” IEEE Electrical Insulation Magazine 19 12 - 18    DOI : 10.1109/MEI.2003.1203017
Der Houhanessian V. , Zaengl W. S. “Application of relaxation current measurements to on-site diagnosis of power transformers” IEEE Conference on Electrical Insulation and Dielectric Phenomena Minneapolis, America 19-22 October 1997 45 - 51
Setayeshmehr A. , Fofana I. , Akbari A. “Effect of temperature, water content and aging on the dielectric response of oil-impregnated paper” IEEE International Conference on Dielectric Liquids Futuroscope-Chasseneuil, France June 30-July 3 2008 1 - 4
Alwis K. , Burgovne C. 2006 “Time-temperature super-position to determine the stress-rupture of aramid fibres” Applied Composite Materials 13 (4) 249 - 264    DOI : 10.1007/s10443-006-9017-8
Saha T.K. , Purkait P. 2008 “Investigations of temperature effects on the dielectric response measurements of transformer oil-paper insulation system” IEEE Transactions on Power Delivery 23 (1) 252 - 260
Fofana I. , Hemmatjou H. , Meghnefi F. 2011 “Effect of thermal transient on the polarization and depolarization current measurements of oil-paper insulation” IEEE Transactions on Dielectrics and Electrical Insulation 18 (2) 513 - 520    DOI : 10.1109/TDEI.2011.5739457
Liao R.J. , Hao J. , Yang L.J. 2012 “Relationship Between Frequency Domain Characteristic Quantity and Aging Status of Transformer Oil-Paper Insulation” Transactions of China Electrotechnical Society 27 (5) 43 - 49
Ekanayake C. , Gubanski S. M. , Graczkowsk A. 2006 “Frequency response of oil impregnated pressboard and paper samples for estimating moisture in transformer insulation” IEEE Transactions on Power Delivery 21 (3) 1309 - 1317    DOI : 10.1109/TPWRD.2006.877632
Hao J. 2012 “Study on time / frequency domain dieletric spectroscopy and space charge characteristics of transformer oil-paper insulation thermal aging” School of Electrical Engineering of Chongqing University
Saha T. K. , Purkait P. , Muller F. 2005 “Deriving an equivalent circuit of transformers insulation for understanding the dielectric response measurements” IEEE Transactions on Power Delivery 20 (1) 149 - 157
Yang L. J. 2009 “Study on aging characteristics of oil-paper in transformer and its lifetime estimation method” School of Electrical Engineering of Chongqing University
Alwis K. , Burgovne C. 2006 “Time-temperature super-position to determine the stress-rupture of aramid fibres” Applied Composite Materials 13 (4) 249 - 264    DOI : 10.1007/s10443-006-9017-8