Cost-Effective APF/UPS System with Seamless Mode Transfer
Cost-Effective APF/UPS System with Seamless Mode Transfer
Journal of Electrical Engineering and Technology. 2015. Jan, 10(1): 195-204
Copyright © 2015, The Korean Institute of Electrical Engineers
This is an Open-Access article distributed under the terms of the Creative Commons Attribution Non-Commercial License (http://creativecommons.org/ licenses/by-nc/3.0/)which permits unrestricted non-commercial use, distribution, and reproduction in any medium, provided the original work is properly cited.
  • Received : December 30, 2013
  • Accepted : August 24, 2014
  • Published : January 01, 2015
Download
PDF
e-PUB
PubReader
PPT
Export by style
Article
Author
Metrics
Cited by
TagCloud
About the Authors
Woo-Cheol Lee
Corresponding Author: Dept. of Electrical, Electronic and Control Engineering, Hankyong National University, Korea. Institute for information technology convergence. (woocheol@ hknu.ac.kr)

Abstract
In this paper, the development of a cost-effective active power filter/uninterruptible power supply (APF/UPS) system with seamless mode transfer is described. The proposed scheme employs a pulse-width-modulation (PWM) voltage-source inverter and has two operational modes. First, when the source voltage is normal, the system operates as an APF, which compensates for the harmonics and power factor while boosting the DC-link voltage to be ready for the disturbance, without an additional DC charging circuit. A simple algorithm to detect the load current harmonics is also proposed. Second, when the source voltage is out of the normal range (owing to sag, swell, or outage), it operates a UPS, which controls the output voltage constantly by discharging the DC-link capacitor. Furthermore, a seamless transfer method for the single-phase inverter between the APF mode and the UPS mode is also proposed, in which an IGBT switch with diodes is used as a static bypass switch. Dissimilar to a conventional SCR switch, the IGBT switch can implement a seamless mode transfer. During the UPS operation, when the source voltage returns to the normal range, the system operates as an APF. The proposed system has good transient and steady-state response characteristics. The APF, charging circuit, and UPS systems are implemented in one inverter system. Finally, the validity of the proposed scheme is investigated with simulated and experimental results for a prototype APF/UPS system rated at 3 kVA.
Keywords
1. Introduction
Owing to the widespread automation of critical processes throughout industry, the importance of precise voltage control and voltage stability has increased dramatically. Sensitive loads are greatly affected by power quality disturbances in electric systems. Supplying an unreliable input power to these devices causes severe losses to customers. Types of input power disturbance include voltage sag / swell and outage caused by a fault in the interconnected power system [1 , 2] .
The traditional approach has been to use an on-line uninterrupted power supply (UPS) and a dynamic voltage restorer (DVR), possibly with a back-up generator [3] . This is an expensive solution considering that the UPS battery has a lifetime of 2-5 years and is less reliable than the incoming utility power. Generally, if the maximum temperature rating of a capacitor is 85 °C or 105 °C, the lifetime of the capacitor is approximately 5-7 years or 8-10 years, respectively [4 , 5] . A DVR for voltage sag does not require an energy storage unit, whereas a DVR for voltage interruption does. One disadvantage is the compensation delay time between the point at which the disturbance begins and that at which the disturbance is compensated for, which is critical to system performance [6] . The major parts of this compensation delay are the detection delay of the voltage sag or interruption and the turn-off time of the thyristor switch. In most cases, an anti parallel thyristor switch has been used as a static bypasses switch (SBS), which requires time to turn off. Therefore, it is impossible to implement seamless transfer from the grid-tied mode to the off-grid mode when a fault (sag, swell, or outage) occurs [7 , 8] . The transition between the grid-tied mode and the off-grid mode is achieved only when a grid voltage is normal and during zero-crossing of the source voltage or output voltage. If a fault is detected, the thyristor switch will open at the positive zero-crossing. The time needed to transition from the grid-tied mode to the off-grid mode is no more than one utility period [7] . In the proposed paper, an IGBT switch with diodes, instead of the conventional SCR switch, was used to implement the seamless mode transfer.
The majority of power disturbances are voltage sags that occur because of lightning strikes, accidents, and equipment failure in the distribution grid feeding the plant [9 - 11] . Therefore, several voltage sag immunity standards such as SEMI F47, CEBMA Curve, and IEC 61000-4-11,-34 were created to improve equipment reliability [12 - 14] . The existing standards and recommendations provide guide lines to limit the maximum magnitude and duration of the voltage sag.
Fig. 1 shows SEMI F47, a more recent specification developed for the semiconductor industry without using batteries. This standard recommends that semiconductor equipment be designed to operate during a 50% voltage sag for 0.2 s, a 30% voltage sag for 0.5 s, and a 20% voltage sag for 1 s. However, the CBEMA standard only recommends that they operate during a 30% voltage sag for 0.5 s. Most sag problems consist of voltage drops of 20-50% and sag duration times of 0.2 s [12] .
PPT Slide
Lager Image
SEMI F47 voltage sag curve.
In this paper, a cost-effective APF/UPS system with seamless mode transfer, which can compensate for voltage drop/swell and outage during a short period of time as well as compensate for the power factor and harmonics of the load current, is proposed.
Compared with conventional APF and UPS systems, the proposed APF/UPS system has the following advantages.
  • 1) When the source voltage is normal, it operates as an APF that controls the power factor, compensates for the harmonics of the load current, and charges the DC-link capacitor to be ready for the disturbance, without an additional DC charging circuit and batteries. Moreover, the system employs a newly proposed and simple algorithm to detect the load current harmonics.
  • 2) When the source voltage is out of range (sag, swell, or outage), the system operates as a UPS that controls the output voltage constantly by discharging the DClink capacitor. When the source voltage returns to the normal range, the system resumes its operation as an APF.
  • 3) The APF, UPS, and charging circuit can be implemented in an integrated inverter system.
  • 4) A seamless transfer method of a single-phase inverter between the APF mode and the UPS mode is possible. Furthermore, an IGBT switch with diodes, instead of a conventional SCR switch, was used as the SBS. This improves the seamless mode transfer.
  • 5) The proposed seamless transfer algorithm is applicable to single-phase grid-interactive inverters between the grid-connected and stand alone modes.
  • 6) Therefore, a cost-effective method to compensate for the harmonics and power factor of the load current as well as the voltage drop is proposed.
2. System Control
Fig. 2 shows a circuit diagram of a single-phase APF/UPS system with an LC filter and an SBS. The conventional UPS system has an anti parallel thyristor switch as the SBS; however, it requires at most a half cycle to turn off the switch. Therefore, it is impossible to implement seamless transfer between the APF and UPS systems.
PPT Slide
Lager Image
Circuit diagram of single-phase APF/UPS system with LC filter and static bypass switch.
In the proposed APF/UPS system, an IGBT switch with diodes is used as the SBS, meaning that the IGBT switch is turned on and off according to the current gate signal.
The APF mode of the system controls the harmonics, charges the DC-link capacitor, and controls the power factor through current injection. The basic theory of the boost converter is the same as that of a single-phase PWM converter. The hardware of a single-phase PWM converter is the same as that of the APF. Therefore, there is no need for an additional DC charging circuit.
In the UPS mode, the system compensates for the output voltage when the source voltage is out of range by discharging the DC-link capacitor. The capacitor ( C1 ) is needed to make the output voltage a sinusoidal waveform.
- 2.1 Control of APF and boost converter
The notations used in Figs. 3 and 4 are as follows:
  • Vg, ig: Source voltage and current
  • Vo, ild: Output voltage and load current
  • ild1, ild2: RL load and diode rectifier load
  • V1dc, i1dc: DC-link voltage and current
  • i1, ic: Inverter and capacitor current
  • ild_ds, ild_qs: Load current in the stationary reference frame
  • ild_de, ild_qe: Load current in the synchronous reference frame
  • ild_de_Hflt, ild_qe_Hflt: Harmonic load current in the synchronous reference frame
  • ild_Hflt: Detected harmonic load current
  • Vdc_ref: Reference DC voltage
  • I1_ref: Reference AC current
  • V1_ref: Reference AC voltage
  • Gioloop: Open-loop Transfer function of the current controller in the APF mode
  • Gicloop : Closed-loop transfer function of the current controller in the APF mode
  • Go(s): Transfer function of the load and the filter capacitor
  • Φ(s)IN: Closed loop transfer function of the current controller in the grid-tied mode
  • Gvoloop: Open-loop transfer function of the controller in the grid-tied mode
  • Gvcloop: Closed loop transfer function of the controller in the grid-tied mode
  • Vgrms: rms value of the grid voltage
PPT Slide
Lager Image
Block diagram of active power filter in grid-tied mode: (a) Detection block of harmonics of load current; (b) Control block diagram of APF; (c) Filter inductor current controller
PPT Slide
Lager Image
Simulation results in the case of compensation for load harmonics and power factor: (a) Source voltage and current. (b) Output voltage and current. (c) Detected harmonic load current. (d) Inverter current.
The block diagram of the APF in grid-tied mode is shown in Fig. 3 . Fig. 3(a) shows the detection block of the harmonics of the load current, which uses a d-q transformation with an all-pass filter. The system generates a virtual phase with a phase lag of 90° from the measured load current [15] . The virtual phase ild_qs is obtained from the measured load current ild_ds = -ild by using the allpass filter in the discrete-time domain as follows:
PPT Slide
Lager Image
where
PPT Slide
Lager Image
The load current ild is measured and processed in the synchronous de-qe reference frame. Given that the to-beextracted currents are dc on both the de and qe axes, filtering of the signal with the synchronous de-qe reference is insensitive to any phase errors introduced by low-pass filters. To extract the load current harmonics from the synchronous de-qe reference, implementation of a highpass filter is realized as (1-LPF). Implementation of the low-pass filter used in the controller is realized with a cutoff frequency of 20 Hz [16] . Detection of the source voltage also requires the use of a d-q transformation with an all-pass filter. The all-pass filter generates a virtual phase with a 90° phase lag from the measured source voltage.
The control block diagram of the APF in the grid-tied mode is shown in Fig. 3(b) . The figure shows the doubleloop feedback control system, which consists of an inner AC-current loop and an outer DC-voltage loop. The filter inductor current controller and DC-link voltage controller are used to force the input current to follow the referenced current waveform and to regulate the output voltage, even under the condition of a sudden load change. In general, the current controller is designed so that the power factor at the supply terminal is close to one. That is, the supply voltage vg and current ig are required to be as closely inphase as possible. Furthermore, a detected harmonic load current ild_Hflt is added to the current controller to compensate for the harmonic load current.
Fig. 3(c) shows the filter inductor current controller [7 , 17] . The closed loop transfer function of the current controller in the grid-tied mode is described as follows:
PPT Slide
Lager Image
PPT Slide
Lager Image
where kp2 and kI2 are the integral and proportional coefficients, respectively, of the current controller ( PI2 ). The transfer function of the load and the filter capacitor impedance of the inverter, G 0 (s), is described as
PPT Slide
Lager Image
where RL is the equivalent resistance of the load. The parameters are as follows: RL = 14.2 Ω and C1 = 100 μF.
Substituting (4) into (3) yields
PPT Slide
Lager Image
If the PI gain is adequate, Eq. (5) shows that the inverter in the APF mode is stable. The open loop transfer function of the current controller in the APF mode is obtained as
PPT Slide
Lager Image
The closed loop transfer function of the current controller in the APF mode is obtained as
PPT Slide
Lager Image
The parameters of the output voltage regulator are designed as follows: Kp2 =6.5 and Ki2 =1.22. The phase margin of the compensated current loop gain is 73°.
Fig. 4 shows the simulation results in the case of compensation for the load harmonics and power factor.
In the simulation, Vg , and Ig are the grid voltage and current, respectively; Vo and Ild are the output voltage and current, respectively; Ild_Hflt is the detected harmonic load current; and I1 is the inverter current. In Fig. 4(a) , the grid current is sinusoidal, and the power factor is controlled to be unity because the APF compensates for the load harmonics and the power factor [18 , 19] .
Fig. 4(b) shows the waveforms of the output voltage and the load current. The figure shows that 50% of the diode rectifier load and 50% of the RL load are applied. Fig. 4(c) shows the detected harmonic load current from Fig. 3(a) . Fig. 4(d) shows the inverter current; its waveform is opposite to that of the harmonic load current owing to the compensation of the latter.
- 2.2 Control of UPS and Inverter
The control block diagram of a UPS in the off-grid mode is shown in Fig. 5(a) , where PI2 refers to the integral and proportional coefficients of the current controller ( PI2 ). L 1 is the equivalent filter inductor, and K1 to K3 are the feedback coefficients of the filter inductor current ( i1 ), the output voltage ( ν o ), and the load current ( iL ), respectively. The output voltage controller is used to regulate the output voltage, where the reference voltage ( νref ) is a sinusoidal waveform and is given by the digital signal processor (DSP).
PPT Slide
Lager Image
Block diagram of UPS in off-grid mode: (a) Control block diagram of UPS. (b) Simplified control block diagram
Fig. 5(b) shows the simplified control block diagram, where K2 is the feedback coefficient of the grid voltage [20] [21] . The open-loop transfer function of the controller in the off-grid mode is described as follows:
PPT Slide
Lager Image
The closed-loop transfer function of the controller in offgrid mode is described as follows:
PPT Slide
Lager Image
where A1 refers to the integral and proportional coefficients of the voltage controller ( PI1 ) [22 , 23] . The parameters of the output voltage regulator are designed as follows: Kp1 = 1.2 and Ki1 =4.8.
- 2.3 Phase-locked loop and voltage detection
Fig. 6 shows the block diagram of the digital PLL and sag detection block diagram.
PPT Slide
Lager Image
Digital phase-locked-loop and sag detection block diagram
The virtual phase
PPT Slide
Lager Image
can be obtained from the measured source voltage
PPT Slide
Lager Image
= - V g by using the all-pass filter in the discrete-time domain as follows:
PPT Slide
Lager Image
PPT Slide
Lager Image
By using a synchronous rotating reference frame, the rms value of the source voltage is obtained as follows:
PPT Slide
Lager Image
PPT Slide
Lager Image
If Vgrms_err is beyond 15% of the absolute source voltage (reference, 0.15× V*g_rms ), the source voltage sag is detected.
- 2.4 Seamless transfer between APF and UPS
In order to realize seamless transfer from the APF mode to the UPS mode, an algorithm for instantaneous detection of the grid voltage is needed.
When a drop in the grid voltage is detected for one sampling period, the SBS is turned off immediately, and the system is transferred to the UPS mode. The beginning of the output voltage reference starts at the grid voltage of the grid voltage drop.
When the system is transferred from the UPS mode to the APF mode in order to realize seamless transfer, the load voltage must match the magnitude, frequency, and phase of the grid voltage well before connecting to the utility.
The detailed process of the seamless transfer between the two modes is illustrated in the following subsections [8] .
- 2.4.1 APF mode to UPS mode
  • a) Detect the voltage drop on the utility.
  • b) Deactivate the APF mode, turn off the SBS, and separate the output voltage from the utility immediately.
  • c) Confirm that the SBS is completely off and then transition to the UPS mode. In the case of a voltage drop, synchronizeνo_refwithνg. In the case of a black out, synchronizeνo_refwith the clock signal.
  • d) The beginning of the output voltage reference starts at the grid voltage at the grid voltage drop.
All changes in the reference current, reference voltage, and SBS occur at a voltage drop and black out. After confirmation that the SBS is completely shut down, a transition is made to the UPS mode. The detection of the grid voltage plays an important role in this transfer [15] .
- 2.4.2 UPS mode to APF mode
  • a) Detect that the grid is operating under the nominal condition.
  • b) Adjustνo_refto match the frequency and phase of the grid voltage. The time required to adjust the reference is less than several times the grid period.
  • c) Once the amplitude and phase of the load voltage and the grid voltage are equal (in one period), the UPS mode is turned off, and the SBS is turned on.
  • d) After the SBS is turned on, the APF/UPS system is transferred to the APF mode.
To boost the DC-link voltage and compensate for the harmonics and power factor, the reference grid current is increased slowly from zero to the desired value (in both magnitude and phase). When the grid is operating under a nominal condition, and the amplitude and phase of the load voltage and grid voltage are equal, the UPS mode is turned off, and the SBS is turned on. After confirming that the SBS is on, the system is transferred to the APF mode [24] .
Fig. 7 shows block diagrams of the APF mode and the UPS mode. The transfer between the two modes is performed by a change in the reference signal. The seamless transfer can be easily realized by a DSP.
Fig. 7(a) shows that the APF/UPS system operates as an APF that compensates for the harmonics of the load current, controls the power factor, and charges the DC-link capacitor. When the source voltage is out of range, the system turns off the SBS and transfers to the UPS mode. Fig. 7(b) shows that the system operates as a UPS that controls the output voltage constantly. When the source voltage returns to the normal range, the system waits for five cycles to confirm synchronization, after which the SBS is turned on and the operation mode is changed from UPS to APF. Therefore, a transition from the UPS mode to the APF mode as soon as the source voltage is returned to the nominal value is impossible.
PPT Slide
Lager Image
Block diagrams of the APF and UPS modes: (a) APF mode; (b) UPS mode.
- 2.5 Design of DC-Link capacitance
To design the DC-link capacitance, the compensation energy, power, and capacitance are expressed as follows:
PPT Slide
Lager Image
PPT Slide
Lager Image
PPT Slide
Lager Image
where Vdc DC-Link = 442 V, and, VGrid_Peak = 208×sqrt(2)
Fig. 8(a) shows the capacitance depending on the compensation time under the 3-kVA load condition. The system needs a capacitor of 5,471 or 10,942 μ F to compensate for 0.1 s or 0.2 s, respectively. Fig. 8(b) shows the rating depending on the compensation time when the capacitance is 9,900 μ F. In a real situation, a capacitance of 9,900 μ F instead of 10,942 μ F is used. Therefore, the compensation time is less than 0.2s. If the system compensates for 0.1s or 0.2s, it can supply a power of 5.4 kVA or 2.7kVA, respectively.
PPT Slide
Lager Image
DC-link capacitance depending on compensation time at a rating of 3 kVA: (a) Capacitance versus compensation time; (b) Rating versus the compensation time.
If a supercapacitor is used instead of a conventional electrolytic capacitor for boosting the DC-link voltage, then the compensation time is easily enhanced without additional hardware.
3. Experimental Results
To verify the proposed strategy, the algorithm was implemented with a DSP (TMS320C33). A single 32-bit floating-point DSP with a single-cycle execution time of 13.3 n s was used. The laboratory prototype with IGBT modules was a 3-kVA APF/UPS system, and the switching period of the PWM was 91 μs. Moreover, a single-phase diode rectifier and R-L load were included to show the characteristics of harmonic load current elimination and power factor correction. The system parameters are listed in Table 1 .
System Parameters
PPT Slide
Lager Image
System Parameters
The nominal input voltage was 208 V. Voltage sags were simulated with a tap-changing transformer and switching devices, enabling various voltage sag levels to be generated. In this paper, the source voltage drops from 208 V to 104 V in a sag event. The DC-link voltage was boosted to 442 V.
Fig. 9 shows a prototype of the proposed APF/UPS system. The prototype is composed of a DC-link capacitor (1), an LC filter (2), a static IGBT switch (3), IGBT inverter modules (4), a sensing board (5), a DSP board (6), and gate drivers (7).
PPT Slide
Lager Image
Prototype of proposed APF/UPS system.
- 3.1 APF mode (DC boost and harmonic compensation)
Fig. 10 shows the start-up in the APF/UPS system when the DC-link voltage increases from 290 Vdc to 442 Vdc under the no-load condition. In this figure, Ch 3 and Ch 4 show that the DC-link voltage follows the reference voltage of 442 V. Although the inverter current ( i1 ) is 0 before start-up, when the DC-link voltage is increased from 290 Vdc to 442 Vdc, an inverter current of approximately 7-8 to 3-4 A is detected, respectively. After Vdc reaches 442 V, an inverter current of approximately 2 A is detected.
PPT Slide
Lager Image
Start-up in APF/UPS system when the DC-link voltage is increased from 290 to 442 Vdc under no-load condition: Ch 1. Vg: source voltage (250 V/div). Ch 2. i1: output current (10 A/div). Ch 3. Vdc_ref: reference DC-link voltage (100 V/div). Ch 4. Vdc: DC-link voltage (100 V/div).
Fig. 11 shows the experimental results when 50% of the diode rectifier load and 50% of the RL load are applied. The source current is sinusoidal, and the power factor is controlled to be unity because the APF compensates for the harmonic load current and the power factor.
PPT Slide
Lager Image
Experimental results in APF mode: Ch 1. Vg: source voltage (250 V/div). Ch 2. ig: source current (20 A/div). Ch 3. Vo: output voltage (250 V/div). Ch 4. ild: load current(20 A/div).
- 3.2 UPS mode
Fig. 12 shows the experimental results when the load changes from the no-load condition to 100% of the diode rectifier load. Although a diode rectifier load was applied to the system, the output voltage of the UPS was controlled to be sinusoidal and was synchronized with the grid voltage.
Fig. 12(b) shows zoomed-in waveforms under the steady state condition.
PPT Slide
Lager Image
Experimental results when the load changes from the no-load condition to 100% of the diode rectifier load: (a) Transient waveforms; (b) Zoomed-in waveforms in steady state. Ch 1. Vg: source voltage (250 V/div). Ch 2. Vo: output voltage (250 V/div). Ch 3. I1: inverter current (20 A/div). Ch 4. Ild: load current (20 A/div).
- 3.3 APF/UPS mode transfer (50% voltage sag)
Fig. 13 shows the experimental results when 100% of the R-L load is applied. Fig. 13(a) shows when the IGBT and diodes were used as a static bypass switch. When the source voltage drops by up to 50%, the APF/UPS system cannot adequately operate as an APF system. In this case, the voltage drop is of greater concern than the harmonic current. Thus, the operational mode must be switched from APF to UPS. The system increases the output voltage up to the nominal value as soon as a voltage drop occurs. When the source voltage is returned to the nominal value, several cycles are required to adjust the output voltage to match the grid voltage in both frequency and phase. When the output voltage and grid voltage are synchronized for five cycles, the SBS is turned on, and the operational mode is changed from UPS to APF. However, if the time to confirm synchronization of the output voltage and grid voltage is reduced, the transfer time can be reduced. Fig. 13(b) shows that when the SCR switch was used as the SBS, the output voltage was not fully increased to the nominal value within a half cycle.
PPT Slide
Lager Image
Experimental results during voltage sag from 207 V to 104 V: (a) When the IGBT and diode were used as a static bypass switch; (b) When the SCR switch was used as a static bypass switch. Ch 1. Vg: source voltage (250 V/div). Ch 2. ig: source current (50 A/div). Ch 3. Vo: output voltage (250 V/div). Ch 4. ild: load current (50 A/div).
- 3.4 APF/UPS mode transfer (in case of outages)
Fig. 14(a) shows the experimental results during blackouts when the rectifier load was applied. Similar to the case of Fig. 13(a) , a seamless transfer from the APF to the UPS was implemented. When a voltage interruption occurred, the output voltage was somewhat distorted. The input voltage causes this effect because the blackouts were created by turning off the no fuse breaker (NFB). Fig. 14(b) shows the results of a long blackout. When the DC-link voltage drops to less than 320 V, the system outputs 110 V ac to prolong the backup time until the DC-link voltage reaches 160 V dc . This is because most power electronic devices can operate at input conditions of 220 to 110 V ac . If the system outputs 220 V ac , the DC-link voltage should be greater than 320 V dc . However, if the system outputs 110 V ac , the DC-link voltage should be greater 160 V dc . Therefore, the system can prolong the backup time until the DC-link voltage reaches 160 V dc .
PPT Slide
Lager Image
Experimental results during blackouts: (a) Short blackout period; (b) Long blackout period. Ch 1. Vg: source voltage (250 V/div). Ch 2. ig: source current (50 A/div). Ch 3. Vo: output voltage (250 V/div). Ch 4. ild: load current (50 A/div).
4. Conclusion
In this paper, a cost-effective way to compensate for voltage drops was proposed. When the source voltage is normal, the system operates as an APF, which compensates for the harmonics and power factor, while boosting the DClink voltage to prepare for the disturbance. This renders the additional DC charging circuit and batteries unnecessary. A new algorithm to detect the load current harmonics was also proposed.
When the source voltage is out of range (owing to sag, swell, or outage), the system operates as a UPS that controls the output voltage constantly by discharging the DC-link capacitor. Furthermore, instead of the conventional SCR switch, an IGBT switch with diodes was used as the SBP, and a seamless transfer method for the single-phase inverter between the APF mode and the UPS mode was also proposed. The APF, charging circuit, and UPS systems were implemented in a single-phase inverter system. The control algorithm and mathematical models were described, and the simulated and experimental results were presented to verify the performance of the proposed control strategy.
The validity of the proposed scheme was investigated through simulations and experiments with a 3-kVA APF/UPS system.
Acknowledgements
This work was supported by the GRRC program of Gyeonggi province. [(GRRC HANKYONG 2011-B04), Development of Power Conversion Equipment for Energy saving in Smart Distribution Center]
BIO
Woo-Cheol Lee He received the B.S. and M.S. and Ph.D. degrees in electrical engineering from Hanyang University, Seoul, Korea, in 1987, 1989, 2001, respectively. From 1988 to 1998, he was with the R&D Institute, Hyosung Industries Company Ltd., as a Senior Researcher, Seoul, Korea. He was a Visiting Professor in the department of Electrical Engineering at Virginia Polytechnic Institute and State University, Virginia, USA from 2007 to 2009. Since 2002, he has been with Hankyong National University, Ansung, Korea, where he is a Professor with the Department of Electrical, Electronic and Control Engineering. His research interests are in the areas of power converter, APF, UPS, and electrical drives.
References
Woodley N. , Morgan L. , Sundaram A. 1999 “Experience with an inverter-based dynamic voltage restorer,” IEEE Trans. on Power Delivery 14 (3) 1181 - 1186    DOI : 10.1109/61.772390
Lee W. , Lee D. , Lee T. 2010 “New control scheme for a unified power quality compensator-Q with minimum active power injection,” IEEE Trans. on Power Delivery 25 (2) 1068 - 1076
Plastino J. W. , Morsi W. G. 2011 “On the modeling of dynamic voltage restorer for voltage sag mitigation instand-alone power system.” in Proc. IEEE-EPEC Conf. 309 - 314
Kiuchi K. , Yanagibashi M. 1983 “Operating life of aluminum electrolytic capacitor,” IEEE Intelec’83 535 - 540
Zhao K. , Ciufo P. , Perera S. 2010 “Lifetime analysis of aluminum electrolytic capacitor subject to voltage fluctuations,” IEEE ICHQP 1 - 5
Zhan C. , Ramachandaramurthy V. , Arulampalam A. , Fitzer C. , Kromlidis S. , Bames M. , Jenkins N. 2001 “Dy- namic voltage restorer based on voltage space vector PWM control,” IEEE Trans. on Industry Applications 37 1855 - 1863    DOI : 10.1109/28.968201
Yao Z. , Xiao L 2010 “Seamless transfer of single-phase grid-interactive inverters between grid-connected and stand-alone modes,” IEEE Trans. on Power Electronics 25 (6) 1597 - 1603    DOI : 10.1109/TPEL.2009.2039357
Tirumala R. , Mohan N. , Walter A. 2002 “Seamless transfer of grid-connected PWM inverters between utility-interactiveand stand-alone modes,” in Proc. IEEE APEC Conf. 1081 - 1086
Koval D. O. , Bocancea R.A. , Yao K. , Hughes M. B. 1998 “Canadian national power quality survey: frequency and duration of voltage sags and surges at industrial sites,” IEEE Trans. on Industry Applications 34 904 - 910    DOI : 10.1109/28.720428
Eto J. , Divan D. , Brumsickle W. E. “Pilot evaluation of electricity-reliability and power-quality monitoringin California’s Silicon Valley with the I-grid system,” Lawrence Berkeley National Laboratories Berkeley, California
McGranaghan M. , Mueller D. , Samotyj M. 2000 “Voltage sags in industrial plants,” IEEE Trans. on Industry Applications 29 (2) 697 - 704
2006 SEMI F47-0706 Standard, “Specification for semiconductor processing equipment voltage sag immunity,”
Information Technology Industry Council (ITI), “ ITI(CBEMA) curve,” Available:
2005 “Electromagnetic compatibility (EMC) - Part 4 - 34: Testing and measurement techniques - Voltage dips, short interruptions and voltage variations immunity tests for equipment with input current more than 16 A per phase,”
Lee S. , C H. 2011 “Novel Fast Peak Detector for Singleor Three-phase Unsymmetrical Voltage Sags,” Journal of Electrical Engineering & Technology 6 (5) 658 - 665    DOI : 10.5370/JEET.2011.6.5.658
Chau M. T. , Luo A. L. , Shuai Z. , Ma F. , Xie N. , Chau V. B. 2012 “Novel Control Method for a Hybrid Active Power Filter with Injection Circuit Using a Hybrid Fuzzy Controller,” Journal of Power Electronics 12 (5) 800 - 812    DOI : 10.6113/JPE.2012.12.5.800
Kim Y. C. , Jin L. J. , Lee J. , Choi J. 2010 “Direct Digital Control of Single-Phase AC/DC PWM Converter System,” Journal of Power Electronics 10 (5) 518 - 527    DOI : 10.6113/JPE.2010.10.5.518
Lee J. H. , Jeong J.K. , Han B. M. , Bae B. Y. 2010 “New Reference Generation for a Single-Phase Active Power Filter to Improve Steady State Performance,” Journal of Power Electronics 10 (4) 412 - 418    DOI : 10.6113/JPE.2010.10.4.412
Kim J. S. , Kim Y. S. 2008 “Single-phase Active Power Filter Based on Rotating Reference Frame Method for Harmonics Compensation,” Journal of Electrical Engineering & Technology 3 (1) 94 - 100    DOI : 10.5370/JEET.2008.3.1.094
Ryan M. J. , Brumsickle W. E. , Lorenz R. D. 1997 “Control topology options for single-phase UPS inverters,” IEEE Trans. on Industry Applications 33 (2)
Guerrero J. M. , Vasquez J. C. , Matas J. , Castilla M. , Garcia de Vicuna L. 2009 “Control strategy for flexible microgrid based on parallel line-interactive UPS systems,” IEEE Trans. on Ind. Electronics 56 (3) 726 - 736    DOI : 10.1109/TIE.2008.2009274
Arias M. , Fernandez A. , Lamar D. G. , Rodriguez M. , Hernando M. M. 2008 “ Simplified voltage-sag filler for line-interactive uninterruptible power supplies,” IEEE Trans. on Ind. Electronics 55 (8) 3005 - 3011    DOI : 10.1109/TIE.2008.918595
Low K.-S. , Cao R. 2008 “Model predictive control of parallel-connected inverter for uninterruptible power supplies,” IEEE Trans. on Ind. Electron. 55 (8) 2860 - 2869    DOI : 10.1109/TIE.2008.918471
Balaguer I. J. , Lei Q. , Yang S. , Supatti U. , Peng F. Z. 2011 “Control for grid-connected and intentional islanding operations of distributed power generation,” IEEE Trans. Ind. Electron. 58 (1) 147 - 157    DOI : 10.1109/TIE.2010.2049709