Harmonic Distortion Contribution for the Transmission Loss Allocation in Deregulated Energy Market: A New Scheme for Industry Consumer
Harmonic Distortion Contribution for the Transmission Loss Allocation in Deregulated Energy Market: A New Scheme for Industry Consumer
Journal of Electrical Engineering and Technology. 2015. Jan, 10(1): 1-7
Copyright © 2015, The Korean Institute of Electrical Engineers
This is an Open-Access article distributed under the terms of the Creative Commons Attribution Non-Commercial License (http://creativecommons.org/licenses/by-nc/3.0/)which permits unrestricted non-commercial use, distribution, and reproduction in any medium, provided the original work is properly cited.
  • Received : October 02, 2013
  • Accepted : August 18, 2014
  • Published : January 01, 2015
Download
PDF
e-PUB
PubReader
PPT
Export by style
Article
Author
Metrics
Cited by
TagCloud
About the Authors
Syarifuddin Nojeng
Centre of Electrical Energy System (CEES) Dept. of Electrical Engineering, Universiti Teknologi Malaysia, UTM, Malaysia. (syarifuddinnojeng @yahoo.co.id)
Mohammad Yusri Hassan
Corresponding Author: Centre of Electrical Energy System (CEES) Dept. of Electrical Engineering, Universiti Teknologi Malaysia, UTM, Malaysia. (yusrih@fke.utm.my)
Dalila Mat Said
Centre of Electrical Energy System (CEES) Dept. of Electrical Engineering, Universiti Teknologi Malaysia, UTM, Malaysia. (syarifuddinnojeng @yahoo.co.id)
Md.Pauzi Abdullah
Centre of Electrical Energy System (CEES) Dept. of Electrical Engineering, Universiti Teknologi Malaysia, UTM, Malaysia. (syarifuddinnojeng @yahoo.co.id)
Faridah Hussin
Centre of Electrical Energy System (CEES) Dept. of Electrical Engineering, Universiti Teknologi Malaysia, UTM, Malaysia. (syarifuddinnojeng @yahoo.co.id)

Abstract
The industry has rapidly growth and energy supply technology advanced are become main factor which to contribute of the harmonic losses. This problem is one aspect that may affect the capability of the transmission line and also to the efficiency of electricity. This paper proposes a new scheme to allocate the cost pertaining to transmission loss due to harmonics. The proposed method, called as Generalized Harmonic Distribution Factor, uses the principle of proportional sharing method to allocate the losses among the transmission users especially for industry consumers. The IEEE 14- and 30 bus test system is used to compare the proposed method with existing method. The results showed that the proposed method provided a scheme better in allocating the cost of transmission loss, which could encourage the users to minimize the losses.
Keywords
1. Introduction
Recently, the issue of harmonic losses is always disputable in the deregulated power system. The industry rapidly growth and energy supply technology advanced are main contribute for the harmonic distortion [1] . Many industry consumers that use electronic devices, including the use of reactive power compensation devices such as static compensator variables and UPS, are the main factors on the emergence of harmonic pollution on the distribution network [2] . For instance, Korean will be development of the infrastructure battery charging for electric vehicles which can be to contribute of the harmonic distortion [3] . The utility companies usually install the mitigation equipment to maintain the quality of power supplied. Once this equipment is installed, its cost must be recovered from the consumers who have caused the power quality (PQ) problem, i.e. harmonic distortion [4] . The consumer will pay according to the amount of stress (usage) that their equipment causes onto the mitigation equipment [5] .
The IEEE Standard 519-1992 [6] has become a standard of PQ associated with the harmonic distortion caused by the source or load. This standard establishes a maximum limit of 5% of the Total Harmonic Distortion ( THD ) factor for the current and voltage [7] . The THD indicates the amount of content of the harmonic components either in current or voltage waveform.
Many approximate models and algorithms have been introduced in the literature that tried as accurate as possible to identify and allocate the cost of losses to each participant in the transmission network. In several papers have been exploited of the harmonic focused on the loss allocation due to the harmonic distortion. Power quality problem is one aspect that may affect the ability of the facility within the power system and also the efficiency of electricity distribution from generation sources to the consumer [8] .
The development of loss allocate scheme for harmonic distortion is to determine what harmonic loss should be accurate in PCC for all ICs. The system operator concentrates on solving the technical problems of finding proper incentive signals for transmission owner, while the load effort to encourage harmonic reduction.
This paper proposes a new method to determine of the harmonic contribute for transmission losses allocate. After the introduction in section I, the problem description an overview of transmission loss allocation in presented in section II. Section III explains and formulates the proposed method. A test case based on the 14-bus system is provided in Section IV. Results and discussions are provided in Section V. Section VI presents concluding remarks.
PPT Slide
Lager Image
Single line diagram with several industry consumers (IC) connected to point of common coupling (PCC).
2. Problem Description
Total Harmonic Distortion (THD) is an index that commonly used to determine the level of wave distortion. This parameter is power quality level on an equipment or system. The index of THD, which is shown in Eqs. (5-6), is the ratio of the number of rms value of each individual harmonic waves and fundamental wave, and is used to indicate the level of harmonic generation. There are two types of THD is namely; voltage and current THD. Basically, the electric power supply must provide good power quality like constant voltage magnitude and frequency. Meanwhile, by using electronic devices and non-linear load non-sinusoidal, which can result in poor power quality. It can cause of electrical disturbances like transients, sags, swells, harmonics, and even disruption in power supply [4] . And also, can be to increase of losses in line due harmonic component for line flow.
Generally, transmission losses commonly contribute between 3-5% of the total power losses in network [9] . Therefore, it is a major problem in the efficiency of generation cost. Several methods have been developed and introduced in the literature to identify the losses caused by each component in the electricity market. In the context of loss, the determination of transmission loss allocate ( TLA ) should be as accurate as possible to all users. A widely used approach in TLA is the proportional method Pro-rata method is a technique to solve the problem of the TLA [10] , which uses the principle of proportional sharing ( PSP ) [11] . The approach is based on the concept of the exact power that has been developed through the analysis of the circuit [12] . While, based on the load flow analysis, the method proposed based on Z-bus matrix of the network [13] . Then, to obtain accurately, the author in [14] proposed an approach using neural networks and other methods using the modified nodal equations to identify the actual power loss allocation for the generator and the load [15] . Meanwhile, [16] proposed a loss allocation method based on circuit theory. A new method was verified by [17] for allocating the user’s loss contribution in each branch, called as Equivalent Bilateral Exchange (EBE). The EBE method assumes that the users of the network have their own contribution on the system based on the contribution of currents power.
Finally, a satisfactory TLA scheme should have the following features; charging the user for the actual usage of the grid; providing to new scheme for consumer and power plants about scheme best that can relieve transmission congestion and losses; predictable; simple and easy to implement and can ensure recovery of the total transmission revenue [18] .
3. Proposed Method
In the proposed method, the system loss was calculated by using load flow analysis. By defining the line impedance of system as:
PPT Slide
Lager Image
and the power equation:
PPT Slide
Lager Image
thus, the transmission losses from bus-i to bus-j can be expressed as:
PPT Slide
Lager Image
where:
PPT Slide
Lager Image
and,
PPT Slide
Lager Image
Where:
  • Sij= Power flow from bus i to bus j
  • Sji= Power flow from bus j to bus i
Basically, the level of power quality due to harmonic load can be divided into two types; load without distortion, where the load does not contain distortions, and the load with distortion. The utility total harmonic distortion factor for current (THDI U ) is defined as:
PPT Slide
Lager Image
The utility total harmonic distortion factor for voltage (THDV U ) is defined as:
PPT Slide
Lager Image
Meanwhile, the total transmission losses with harmonic component can be written as:
PPT Slide
Lager Image
By defined the contribution of harmonic for each load j at Demand (D) as MWkloss,D , therefore we obtain:
PPT Slide
Lager Image
Where;
PPT Slide
Lager Image
And,
PPT Slide
Lager Image
Where:
C h j = harmonic share load-j of the total harmonic in load.
Let be the harmonic factor for each Demand (D) as follows;
PPT Slide
Lager Image
Let, we define fTHD,DN as harmonic component due load-N, can be expressed as follows :
PPT Slide
Lager Image
We defined the total harmonic loss component as ;
PPT Slide
Lager Image
Can be re-writing as:
PPT Slide
Lager Image
and
PPT Slide
Lager Image
Therefore, the general formulation of transmission loss allocation with consideration of total harmonic distortion ( THD ) factor for the users can be written as:
PPT Slide
Lager Image
Where:
LhDj as transmission loss allocate with harmonic contain for each load j. And ChjMWhloss,D as the harmonic loss contribute due load –j or demand-D.
While, fTLA is transmission loss based on TLA methods, for example:
1. Pro-rata [17] :
PPT Slide
Lager Image
Therefore, using Eqs. (17) and (18), we obtained:
PPT Slide
Lager Image
2. Incremental Transmission Losses (ITL)
PPT Slide
Lager Image
3. Z-Bus Method [14] :
Similarly, using Eq. (17) for Z bus method, we obtained:
PPT Slide
Lager Image
The component of function in (17) is called as “Generalized Harmonic Distribution Factor ( GHDF )” where fTLA = function of the Transmission Loss Allocation method caused by line parameter R, and ChjMWhloss,D is the contribution of losses for each load due harmonic [21] .
According to IEEE std 1459-2000 , the established maximum limit of THD would be 5% [6] . This means that each load should pay an additional charge if THD in load more than 5% (for instance: industry consumer).
PPT Slide
Lager Image
where:
  • TLAload= Transmission loss allocated to load.
  • TLATHD5%= Transmission loss allocated to demand withTHDload is 5%.
then:
PPT Slide
Lager Image
By setting the THD5% as THDref which is based on IEEE std 1459-2000 , then the net total harmonic distortion for the load with 5% THD will be equal to zero or can be written mathematically as:
PPT Slide
Lager Image
Therefore Eq. (24) substitute to (8), the total transmission losses with harmonic component in Eq. (8) can be obtain as follows:
PPT Slide
Lager Image
Meanwhile, if the THD load is not equal to THDref then the total harmonic distortion THD can be written as:
PPT Slide
Lager Image
Hence,
PPT Slide
Lager Image
4. Case Study and Discussion
The proposed method was tested on the IEEE14-bus system. The proposed method was compared with the original Z method with and without harmonic by transmission utilities as described in Section 4, to investigate its ability to provide a better economic signal to transmission system users. In this case study, the proposed method was tested on the IEEE 14-bus systems and the IEEE 30-bus systems as shown in Figs. 2 and 3 .
PPT Slide
Lager Image
The IEEE 14 bus test system
PPT Slide
Lager Image
Transmission losses allocation due to harmonic content, estimated using the IEEE-30 bus systems.
By using three methods: each Pro-average method, ITL method and Z method bus then Z method gives better results. The third method results are shown in Table 1 . For example on bus 1, two methods of pro rata and ITL provides value 0 while the bus Z method losses are by 7 MW. Similarly, on the bus 8. Then based on Table 2 , the method considered more accurate Z bus, hence become to consider used for compare the proposed method.
Compare of transmission loss allocation without harmonic distortion using the IEEE-14 bus systems.
PPT Slide
Lager Image
Compare of transmission loss allocation without harmonic distortion using the IEEE-14 bus systems.
Compare of transmission loss allocation with harmonic distortion of each load using the IEEE-14 bus systems
PPT Slide
Lager Image
Compare of transmission loss allocation with harmonic distortion of each load using the IEEE-14 bus systems
In Table 2 , can be seen that the transmission cost allocation is conditional, where:
  • Case-1: Assume there are three loads of industry costumer withTHDL3, L4 and L9 equal to 5% ( according toIEEE std). Based on pro-rata method, the obtainedTLAshould be equal. This means that transmission owner will be charged according to pro-rata method original.
  • Case-2: Assume there are three loads of industry costumer withTHDis L3 5%, L4 (7.5%) and L9(10%). Therefore, based on pro-rata method, the owner of the transmission line will pay more according to THD rate. This means that transmission users will be charged due to the additional cost.
  • Case-3: L3, L4 and L9 have THD of 7.5%,10% and 15% according toIEEE std. Based on pro-rata method, the users will pay more for theTLAcompared to the payment in case-2. In this case, L3, L4 and L9 have higherTHDcontent, therefore they will getTLAmore than for the load in Case-1 and Case-2.
By using Eq. (25) above, that when the THD 5%, then we obtain that:
PPT Slide
Lager Image
By the above equation in (28), then power losses are calculated according to the method used TLA . This proposal was then tested on the IEEE 30 bus system as shown in Fig 3 . Based on the proposed method, at 10% THD for example in L2 load will has resulted losses of 0.284 MW and increase it if the THD load becomes 15% so on. The result will give a value significantly when the THD levels greater will increase in load. While for THD 5%, transmission losses is equal between existing methods with propose.
Based on the above, it will cause an increase in harmonic content losses on the transmission line. As a result, there is an increase in power flow in line caused by harmonics on the user. This condition causes a loss in the generation and transmission owners. For that, in order that the industry and gain the satisfaction and power providers are fair, then the harmonic components can be included in the calculation of the cost of transmission.
With reference to the IEEE std.1459-2000 that defines 5% for THD of current, then the user can be charged additional costs due to harmonic, when has THD greater than 5%.
Further, the estimation results from the use of different IEEE bus systems can be a reference for transmission owners in charging penalties to users who have the load quality below of standard. They can also provide information for determining the transmission charge scheme with considered harmonic content by each user, so that both economic aspect and technical aspects in power systems can be covered.
This proposal can provide a good economic signal to all parties in the deregulated of electricity industry supply in the future, especially for transmission owners. Besides, the industry consumer will be encouraged to improve load quality and energy efficiency.
5. Conclusion
This paper presents a new method to allocate the cost of transmission loss due to harmonics. The proposed method has shown differences in contribution costs in terms of conditions of harmonics in the use of transmission network. Through this method, the customer who uses electricity with higher THD will pay a higher transmission cost than other users. Meanwhile, the user who has THD content according to IEEE std. 1459-2000 (until maximum limit is 5%) does not have to pay an additional charge to transmission owner.
This method also provides an alternative solution in the scheme for the determination of transmission charges for customers with varying load characteristic. Another benefit of this proposed method is that it provides economic signals for electricity industry supply, especially transmission and distribution company. The proposed method is suitable for the pool market in deregulated power system.
Acknowledgements
The authors would like to express gratitude to the Centre of Electrical Energy Systems (CEES) Universiti Teknologi Malaysia, the Government of South Sulawesi and Universitas Muslim Indonesia (UMI), for supporting this research study
BIO
Syarifuddin Nojeng received the B. Eng. in Electrical Engineering from Universitas Hasanuddin in 1988, and M.E.E. from Institut Teknologi Bandung (ITB), Indonesia in 1994. He is currently a Ph.D student at Faculty of Electrical Engineering, Universiti Teknologi Malaysia (UTM), Johor, Malaysia. His current research interests are power system deregulation and transmission pricing.
Mohammad Yusri Hassan (M’09) received his B.Eng. in Electrical and Electronics Engineering from Strathclyde University, UK in 1988, M.E.E. from Universiti Teknologi Malaysia (UTM) in 1993 and PhD from Strathclyde University, UK in 2004. Dr. Hassan is an Associate Professor and Director of Centre of Electrical Energy Systems (CEES) in the Faculty of Electrical Engineering at UTM, Johor, Malaysia. His research interest is in power system economics, transmission pricing and energy management. Dr. Hassan is a member of IEEE.
Dalila Mat Said (M’11) received B.Eng Degree, M.Sc Degree and PhD from Universiti Teknologi Malaysia. She is currently, a Senior Lecturer in the Faculty of Electrical Engineering at Universiti Teknologi Malaysia. Her research interest includes power quality and energy supply reliability. Dr. Said is a member of IEEE.
Md. Pauzi Abdullah (M’05-SM’13) received his B.Eng.in Electrical and Electronics Engineering from Universiti Tenaga Nasional, Malaysia in 2002, M.Sc. and PhD from Strathclyde University, UK in 2003 and in 2007 respectively. Dr. Abdullah currently is a Senior Lecturer in the Faculty of Electrical Engineering at UTM. His research interest is in power system economics and congestion management. Dr. Abdullah is a Senior Member of IEEE.
Faridah Hussin (M’11) received her B. Eng. in Electrical and Electronics Engineering from Strathclyde University, UK in 1987, and M.E.E. from Universiti Teknologi Malaysia (UTM) in 1990. Her research interests include power system economics and transmission congestion management.
References
Talacek Philip J. , Watson Neville R. 2000 “Marginal Pricing of Harmonic Injection” IEEE Transaction on Power System 17 (1) 50 - 56
Aiello M 2006 ‘Theoretical and Experiment Comparison of Total Distortion Factor for The Evaluation of Harmonic and Inter harmonic Pollution of Grid-Connected Photovoltaic System’ IEEE transaction on Power Delivery 2 (3) 1390 - 1397
Kim Kisuk , Song Chong Suk , Byen Gilsung , Jung Hosung , Kim Hyungckul , Jang Gilson 2013 “Power Demand and Total Distortion Analysis for an EV Charging Station Concept Utilizing a Battery Energy Strorage System” J. Electr. Eng. Technol. 8 (5) 1234 - 1242    DOI : 10.5370/JEET.2013.8.5.1234
Hojabri1 Mojgan , Toudeshki Arash 2013 “Power Quality Consideration for Off-Grid Renewable Energy Systems” Energy and Power Engineering 5 377 - 383
Yong Peng , Shun Tao , Qun Xu , Xiangning Xiao 2011 “Harmonic Pricing Model Based on Harmonic Costs and Harmonic Current Excessive Penalty
IEEE std.519-1992, “IEEE recommended practice and requirements for harmonics control in electrical power system” IEEE
Hassan M.Y , Abdullah M.P , Hussin F , Hasimah A.R , Almaktar M.A , Majid M.S 2010 “The impact of transmission loss component on transmission cost recovery in pool electricity markets” International Review of Electrical Engineering 5 (4) 1736 - 1746
Wilsun Xu , Yilu Liu 2000 “A Method for Determining Costumer and Utility Harmonic Contribution at the Point of Common Coupling” IEEE Transaction on Power Delivery 15 (2) 804 - 811
Han Jong-Hoon , Lee Kyebyung , Song Chong Suk , Jang Gilsoo , Byeon Gilsung , Park Chang-Hyun 2013 “A New Assessment for the Total Harmonic Contributionsat the Point J. Electr. Eng. Technol. 8 742 - 750
Farhoodnea M. , Mohamed Azah , Shareef H. , Jabbar Khan R. A. 2010 “An Improved Method for Determining Contribution of Utility and Customer Harmonic Distortions In A Power Distribution System International Journal on Electrical Engineering andInformatics 2 (3)
Il Ming K , Hieyong Ha S , Lee S.W 2010 “Transmission loss allocation algorithm using path integral based on transaction strategy” IEEE Transaction on Power Systems 25 (1) 195 - 205    DOI : 10.1109/TPWRS.2009.2030349
Conejo A.J , Arroyo J.M , Alguacil N , Guijaro A.L 2002 “Transmission loss allocation: A Comparison ofdifferential practical algorithms” IEEE Transaction on Power Systems 13 (3) 571 - 576
Rudnick H , Palma R , Fernandez J.E 1995 “Marginal pricing and supplement cost al location in transmissionopen access” IEEE Transaction Power Systems 10 (2) 1125 - 1142    DOI : 10.1109/59.387960
Bialek J 1996 “Tracing the flow of electricity” IEE Proc. Gener. Transmission and Distrib. 143 (4) 313 - 320    DOI : 10.1049/ip-gtd:19960461
Conejo A. J , Galiana F. D , Kockar I 2001 “Z-bus loss allocation” IEEE Transaction on Power Systems 16 105 - 110    DOI : 10.1109/59.910787
Parastar A , Mozafari B , Pirayesh A , Omidi H 2011 “Transmission loss allocation through modified Z-bus” Energy Conversion and Management (52) 752 - 756
Abdelkader S 2006 “Transmission loss allocation inderegulated electrical energy market” Electric Power System Research 76 962 - 967    DOI : 10.1016/j.epsr.2005.12.014
Reta R , Vargas A 2001 “Electricity tracing and loss allocation methods based on electric concepts” IEE Proc. Gener. Transm. Distrib. 148 518 - 522    DOI : 10.1049/ip-gtd:20010609
Mateus J.C , Franco P.C 2005 “Transmission loss allocation through equivalent bilateral exchange and economicalanalysis” IEEE Transaction on Power Systems 20 1799 - 1807    DOI : 10.1109/TPWRS.2005.856989
Galiana Francisco D. , Conejo Antonio J. , Kockar Ivana 2002 “Incremental Transmission Loss Allocation Under Pool Dispatch” IEEE Transaction on Power Systems 17 (1) 6 - 33
Nojeng S , Hassan M.Y , Abdulah M.P , Hussin F “Transmission loss allocation based on harmonic factor distortion in deregulated electricity supply industry” IEEE conference on Industrial electronics and Application sept, 24-26, 2012