Development of a Reclosing Scheme for Reduction of Turbine Generator Shaft Torsional Torques: A Decision Method to Achieve Optimal Reactor Capacity
Development of a Reclosing Scheme for Reduction of Turbine Generator Shaft Torsional Torques: A Decision Method to Achieve Optimal Reactor Capacity
Journal of Electrical Engineering and Technology. 2014. Jul, 9(4): 1145-1153
Copyright © 2014, The Korean Institute of Electrical Engineers
  • Received : April 08, 2013
  • Accepted : January 16, 2014
  • Published : July 01, 2014
Download
PDF
e-PUB
PubReader
PPT
Export by style
Article
Author
Metrics
Cited by
TagCloud
About the Authors
Yun-Sik Oh
College of Information and Communication Engineering, Sungkyunkwan University, Korea. (fivebal2@naver.com)
Hun-Chul Seo
School of IT Engineering, Yonam Institue of Digital Technolgy, Korea (hunchul12@yc.ac.kr)
Jeong-Jae Yang
Korea Power eXchange. (jjyang@kpx.or.kr)
Chul-Hwan Kim
Corresponding Author: College of Information and Communication Engineering, Sungkyunkwan University, Korea. (hmwkim@ hanmail.net)

Abstract
It is well known that line switching operations like reclosing are able to cause transient power oscillations which can stress or damage turbine generators. This paper presents a reclosing scheme to reduce the shaft torsional torques of turbine generators by inserting an additional reactor. A novel method to determine optimal reactor capacity to minimize the torsional torque generated in a turbine generator is also proposed. In this paper, the turbine generator shaft is represented by a multi-mass model to measure torsional torques generated in the shaft between the turbine and the generator. Transmission systems based on actual data from Korea are modeled to verify the proposed scheme using ElectroMagnetic Transient Program (EMTP) software. The simulation results clearly show the effectiveness of the proposed scheme and torsional torque can be minimized by applying the proposed scheme.
Keywords
1. Introduction
Most faults occurring in transmission lines are temporary in nature; it is therefore very important to rapidly restore the power system using a reclosing operation [1 - 5] . However, line switching operations including reclosing can cause transient power and current oscillations that can affect the rotating shaft of a turbine generator. Such operations can result in transient mechanical forces on both the rotating and stationary components of the turbine generator. These forces can damage the turbine generator shaft; in the worst cases, even to the point of causing shaft breakage [6 - 12] . Thus, development of effective reclosing schemes that consider the effect on the turbine generator is necessary.
The impact on the turbine generator can be evaluated by the sudden power change ΔP generated by the switching operation. An IEEE Committee recommends that a ΔP value equal to 0.5 per unit be considered an acceptable screening level for evaluating steady-state switching if a turbine generator is operating under the allowable load condition [13] . If the ΔP value generated by a switching operation is less than 0.5 per unit, the loss-of-life of the turbine generator would generally be expected to be negligible and can be quantified as less than 0.01% per incident. Conditions that can cause higher ΔP values are related to angular phase differences between the two separate systems: as the angular difference between two systems increases, ΔP also increases. Reclosing operations should thus be prevented when the angular difference is high between the two systems. This is generally achieved with a synch-check relay [14 - 15] .
Many researchers have investigated schemes for reducing turbine generator shaft torsional torques [16 - 18] . Field discharge resistors are applied to interrupt generator excitation for the duration of the fault. Also, new selective reclosing schemes have been developed which reclose the faulted phase only after determining that the fault is temporary. One such scheme uses a compensating capacitor to improve the stability of the system and thus reduce the turbine generator shaft torsional torques. These schemes are generally effective, but do not include methods to find the optimum capacity of each element. Hence, this paper focuses on finding the optimum capacity of each element as well as presenting a scheme for reducing turbine generator shaft torsional torques and that is the main objective of this paper.
In this paper, we present a reclosing scheme to reduce the shaft torsional torques in a turbine generator by inserting an additional reactor into the system. A novel method to determine optimum reactor capacity is also proposed to minimize the torsional torque generated in the turbine generator. The optimal reactor capacity is derived by considering an additional ΔP and secondary shaft torsional torque in the turbine generator due to an additional switching operation. In Section 2, the sudden power change ΔP is discussed specifically. In Section 3, a reclosing scheme using an additional reactor is presented. Then, the optimal reactor capacity is discussed in Section 4. Simulations are performed in Section 5 under various conditions to examine the proposed scheme. Finally, conclusions are discussed.
2. Sudden Power Change, ΔP
- 2.1 Power transfer equation
The power transferred between the two systems in Fig. 1 is represented by (1) [19] .
PPT Slide
Lager Image
Equivalent circuit of the transmission system
PPT Slide
Lager Image
where VS and VR are the voltage magnitudes at the sending and receiving ends, respectively; XL is the path impedance and δ is the angular phase difference between the two systems.
In (1), the path impedance XL includes the reactance of the machine, transformer and transmission line. Normally, the voltage magnitude at both ends and the path impedance are fixed. Thus, it can be said that transferred power is a function of the angular difference between the two systems.
- 2.2 Mathematical approach of ΔP
Fig. 2 shows the P- δ curve based on Eq. (1). In the steady-state, the operating point remains at (a), where the electrical power output is equal to the mechanical power input. When a fault occurs, power output drops to the “during fault” curve. Then, because the mechanical power input exceeds the electrical power output, the rotor angle accelerates until breakers open at (c). If the fault is cleared at (c), power output moves to the “Post-fault” curve and reaches point (e). When the reclosing operation is performed to restore the system at this point, a sudden power change ΔP occurs. This power change can stress or damage the turbine generators.
PPT Slide
Lager Image
P-δ curve according to the system conditions
ΔP is defined mathematically by the following expression:
PPT Slide
Lager Image
where Ppre which is located on ‘pre-fault’ curve in Fig. 2 is the maximum power output at the instant of switching and the Ppost which is located on ‘post-fault’ curve in Fig. 2 is the initial power output of the unit before the switch. Based on the Eq. (1), ΔP is represented by
PPT Slide
Lager Image
We can substitute Eq. (4) for Eq. (3) because VS , VR and δ before the switching are similar to those at the instant of switching.
PPT Slide
Lager Image
In Eq. (4), α is larger than β and ( α - β ) has a positive value because XL,pre is smaller than XL,post. Therefore, it is clear that ΔP increases as the angular difference between the two systems, δ , increases. This indicates that the reclosing operation should be prevented when the angular difference between the two systems δ is overly large.
- 2.3 IEEE screening guide
ΔP is a very important factor in assessing the impact of a reclosing operation on the turbine generator shaft. Based on this quantity, an IEEE Committee has published a screening guide for protection engineers to estimate if a particular switching event is severe enough to require greater study in consultation with the turbine generator manufacturer [13] . According to the report, a ΔP value of less than 0.5 per unit can be considered negligible in terms of the impact on the turbine generator.
3. Reclosing Scheme for the Reduction of Turbine Generator Shaft Torsional Torques
- 3.1 Reduction of ΔP via the insertion of an additional reactor
As shown in Section 2, the ΔP generated during a switching operation such as a reclosing operation can result in damage to the turbine generator. It is therefore necessary to reduce the impact on the turbine generator by decreasing the ΔP.
As was seen in (4), the angular difference ΔP can be quite large during a reclosing operation, in excess of 0.5 per unit, a typical IEEE screening guide value. In such a condition, we can reduce the ΔP by controlling the path impedance XL following the switching operation. Because ΔP is inversely proportional to the path impedance XL , the ΔP can be reduced by inserting an additional reactor that increases the total path impedance [20] .
Eq. (5) presents ΔP when an additional reactor is inserted during reclosing, showing that ΔP can be reduced by inserting an additional reactor and thus increasing the total path impedance.
PPT Slide
Lager Image
where the Xreactor is a reactance of an additional reactor.
Fig. 3 shows the P- δ curve with the addition of another reactor during reclosing. In the case without any additional reactors, the power point on the P- δ curve changes from (e) to (f) during reclosing. On the other hand, the power point changes from (e) to (f') when an additional reactor is inserted, reducing ΔP by as much as the distance between (f) and (f').
PPT Slide
Lager Image
P-δ curve when an additional reactor is inserted during reclosing
- 3.2 Reclosing scheme including the insertion of an additional reactor
Fig. 4 shows a block diagram of the reclosing scheme including an additional reactor. In the figure, the reclosing scheme with an additional reactor is applied to circuit 2, the faulted circuit. As indicated in Fig. 4 , this scheme first recloses CB2, connected to the additional reactor, to reduce the impact on the turbine generator. After a specific time delay, CB2 is tripped and CB1 closed to avoid steadystate losses caused by keeping the reactor in continuous service. In Fig. 4 , voltages required for controller are easily collected by potential transformers.
PPT Slide
Lager Image
Block diagram of the reclosing scheme using an additional reactor
CB1 and CB2 are controlled by a controller with a synch-check function to limit the impact associated with reclosing under Live-Bus/Live-Line (LBLL) conditions. A flowchart of the controller algorithm is shown in Fig. 5. The controller starts after the leader end is reclosed after a fixed deadtime and first checks LBLL and synchronism conditions. The magnitude and phase angle of the voltage at both ends as well as the magnitude of the line voltage are needed to verify the conditions that allow the reclosing of the follower end. If the LBLL and synchronism conditions are satisfied, CB2 (connected to the reactor) is closed and the timer is initiated. After the timer expires, CB2 is tripped and CB1 is closed to restore the system completely. There will be some little time delay inevitably to reclose the circuit breakers shown in Fig. 4 because of calculation procedure in controller. However, the time delay can be ignored in this scheme because performance of the proposed scheme is not dictated by a moment of reclosing and the time delay is not too much to guarantee the performance of that.
PPT Slide
Lager Image
Flowchart of the controller algorithm for the reclosing scheme using an additional reactor
4. Method to Determine the Optimal Reactor Capacity
- 4.1 Disadvantage of the reclosing scheme using an additional reactor
The reclosing scheme using an additional reactor has the advantage of reducing ΔP during the initial reclosing operation. However, if the circuit connected to the reactor is left in the circuit, steady-state losses due to the reactor are inevitable. Thus, the reactor should be removed from service after a specific time delay. To remove the reactor from a circuit, an additional switching operation is needed. This causes an additional ΔP and secondary shaft torsional torque in the turbine generator. Fig. 6 shows fluctuations in power output both with and without an additional reactor; ΔP is reduced in the case including the additional reactor compared with the case that does not include one. However, it is apparent that an additional ΔP is generated when removing the reactor.
PPT Slide
Lager Image
Fluctuations in power output according to time and existence of the reactor
The ΔP generated by removing the reactor is proportional to the capacity of the reactor and it is expressed by Eq. (6). It can be concluded that the larger the capacity of the reactor, the greater the Δ Premove is.
PPT Slide
Lager Image
- 4.2 Optimal reactor capacity
The reclosing scheme using an additional reactor has disadvantages as well as advantages. Although the reclosing ΔP can be effectively reduced with an additional reactor, the advantages of the reclosing scheme disappear if large torsional torques are generated when the reactor is removed. It is therefore clear that we should also take into account the additional ΔP that is generated by removing reactor.
Considering the advantages and disadvantages of the additional reactor, the optimal reactor capacity is the value at which the ΔP generated by inserting a reactor is equal to that generated by removing a reactor, thereby balancing each ΔP. The torsional torque generated by removing a reactor can be limited to less than the torque generated by its insertion by applying the optimal reactor capacity; this allows us to simply reduce the impact on the turbine generator. Fig. 7 depicts the curves used for obtaining the optimal reactor capacity. The optimal reactor capacity is the point at which the two curves intersect.
PPT Slide
Lager Image
Curves for obtaining the optimal reactor capacity
The optimal reactor capacity can be expressed mathematically. Eq. (7) shows the optimal reactor capacity. In (7), it is assumed that the voltage magnitude of each state is the same. It is too difficult to find the optimal reactor capacity in (7) because there are too many variables associated the optimal reactor capacity; to accomplish this more expediently, in this paper we use ElectroMagnetic Transient Program (EMTP), an analytical program for transient phenomena, to find the optimal reactor capacity [21 - 22] .
PPT Slide
Lager Image
where Xop is the optimal reactor capacity.
5. Simulation
- 5.1 Simulation model
Fig. 8 shows models of the KEPCO 154 and 345 kV transmission systems used to verify the reclosing scheme and optimal reactor capacity. The systems are modeled using the EMTP-RV software package, based on actual data from Korea.
PPT Slide
Lager Image
Transmission system model
Fig. 9 depicts the multi-mass model of the turbine generator used to simulate the mechanical torques generated in a turbine generator shaft. Generally, the turbine generator is modeled as a single mass; however, a multi-mass model is necessary to perform time-domain simulations for the shaft torsional torques. The multi-mass model shown in Fig. 9 is composed of six masses with five shafts connecting each mass; those represent the exciter (EXC), the generator(GEN), two low pressure turbines (LPA and LPB), an intermediate pressure turbine (IP) and a high pressure turbine(HP).
PPT Slide
Lager Image
Multi-mass model of the turbine generator used in the 154 and 345 kV transmission systems
The multi-mass models of the turbine generators in both the 154 and 345 kV systems are equal. The parameters associated with the turbine generator are shown in Table 1 and 2 [23] . The parameter values shown in Tables 1 and 2 are based upon the physical dimensions of the shaft system and its material properties. The most important parameter in Table 1 and 2 is the spring constant and it pertains to the elastic connection between adjacent masses and is directly involved with a torsional interaction.
Parameters of the turbine generator in the 154 kV system
PPT Slide
Lager Image
Parameters of the turbine generator in the 154 kV system
Parameters of the turbine generator in the 345 kV system
PPT Slide
Lager Image
Parameters of the turbine generator in the 345 kV system
- 5.2 Simulation conditions
In this paper, we perform the simulation in three parts. First, ΔP and torsional torques according to different angular differences between the two systems are calculated. Second, when the reclosing scheme using an additional reactor is applied, ΔP and torsional torques are calculated according to various reactor capacities. Last, we find the optimal reactor capacity via the method presented in Fig. 7 . The results are compared with reactor capacity causing the minimum torsional torque.
We present the torsional torque between the GEN and LPB only because it is generally the largest. Torsional torques in this paper are calculated by Eq. (8) [24] .
PPT Slide
Lager Image
where Tmax and Tmin are the maximum and minimum torques generated in the shaft, respectively.
Fig. 10 shows a simple example of the maximum and minimum torque.
PPT Slide
Lager Image
Shaft torque generated between GEN and LPB
- 5.3 Simulation results
We represent ΔP as per unit quantity. ΔP in per unit can be calculated by Eq. (9).
PPT Slide
Lager Image
where SMVA is the rated power of the turbine generator.
Fig. 11 shows the ΔP and torsional torques in the 154 and 345 kV transmission systems according to various angular differences. In the 154 and 345 kV systems, when the lines marked as being in fault in Fig. 8 are out of service, the maximum possible angular differences in credible operating conditions are 28° and 40°, respectively. We therefore choose the possible range of the angular differences to be below those angles.
PPT Slide
Lager Image
ΔP and torsional torque according to various angular differences
From the results shown in Fig. 11 , it is easily seen that the ΔP and torsional torque increase as the angular difference is increased. Therefore, a reclosing operation should be avoided when the angular difference is large because of the impact on the turbine generator. Protection against a reclosing operation for large angular differences can be achieved by applying a synch-check relay. The ΔP values generated in the 345kV system are much greater than those in the 154kV system, making it particularly advantageous to apply the reclosing scheme using an additional reactor in the 345kV system.
Fig. 12 illustrates the ΔP insert and torsional torque in the 154kV and 345kV transmission systems according to various reactor capacities when the reclosing scheme using an additional reactor is applied to them. When the reclosing scheme using an additional reactor is applied to both the 154kV and 345kV systems, the Δ Pinsert and torsional torque are significantly reduced compared with when the proposed reclosing scheme is not applied. The results clearly show that we can decrease the ΔP to less than 0.5 per unit by using the proposed scheme.
PPT Slide
Lager Image
ΔP(insert) and torsional torque according to various reactor capacities and angular conditions
In Fig. 12 , Δ P insert is reduced as the reactor capacity is increased. However, the torsional torque reduces to a minimum at a specific capacity, then begins to increase slightly with increasing reactor capacity. This is because Δ P remove occurs when the reactor is removed after a time delay. The specific capacity, which corresponds to the optimal reactor capacity, can be found using the decision method shown in Fig. 7 .
The optimal reactor capacities obtained using the proposed decision method are shown in Fig. 13. From the results in the subfigures, we can see that the optimal reactor capacities are not fixed. This is because the optimal reactor capacity depends on many variables, as indicated in Eq. (7). Those variables vary with the configuration and condition of the system.
PPT Slide
Lager Image
Optimal reactor capacity according to various angular conditions
Table 3 details the optimal reactor capacity results. In Table 3 , the A and B results indicate the optimal reactor capacities obtained using the proposed method and those that result in the minimum torsional torque, respectively. These two simulation results are nearly the same for all cases. From the results shown in Table 3 , it can be concluded that the proposed method is effective in finding the optimal reactor capacity.
Simulation results of the optimal reactor capacity
PPT Slide
Lager Image
Simulation results of the optimal reactor capacity
6. Conclusion
This paper presents a reclosing scheme to reduce the shaft torsional torque in a turbine generator, accomplished by inserting an additional reactor into the circuit. A novel method to determine the optimal reactor capacity, able to minimize the torsional torque generated in turbine generator, is also proposed. The optimal reactor capacity can be derived by considering an additional ΔP and secondary shaft torsional torque in the turbine generator due to an additional switching operation which is a disadvantage of the scheme using an additional reactor.
The proposed scheme is simulated in models based on actual data in Korea 154kV and 345kV transmission line. Simulation results show that the proposed reclosing scheme using an additional reactor can significantly reduce the torsional torque generated in the shaft of a turbine generator under high angular difference system conditions, a condition that can cause large impacts on turbine generators. Moreover, the torsional torque is minimized by applying the optimal reactor capacity. Therefore, we can protect the turbine generator from the impact of a reclosing operation effectively. Practically, it is hard to apply this scheme in entire transmission lines because it takes cost. But, if it is applied to only where transmission lines are in proximity to generation facilities or a large angular separation is more likely to happen, we can protect turbine generators more efficiently by using the proposed scheme.
BIO
Yun-Sik Oh was born in Korea, 1987. At present, he is working on his Ph. D thesis at Sungkyunkwan University. His research interests include power system transients, protection and stability. He received his B.S and M.S degrees in School of Electrical and Computer Engineering from Sungkyunkwan University, Korea, 2011 and 2013.
Hun-Chul Seo was born in Korea, 1982. He received his B.S and M.S degrees in School of Electrical and Computer Engineering from Sungkyunkwan University, Korea, 2004 and 2006. He worked for Korea Electrical Engineering & Science Institute, Seoul, Korea, as a researcher in power system division from 2006 to 2009. He was a post-doctoral fellow in the dept. of electrical engineering, Yeungnam University, Korea, from Sep. 2013 to Jan. 2014. From Mar. 2014, he is an assistant professor with the School of IT Engineering, Yonam Institue of Digital Technolgy, Korea. His research interests include power system transients, protection and stability.
Chul-Hwan Kim was born in Korea, 1961. In 1990 he joined Cheju National University, Cheju, Korea, as a full-time Lecturer. He has been a visiting academic at the University of BATH, UK, in 1996, 1998, and 1999. Since March 1992, he has been a professor in the School of Electrical and Computer Engineering, Sungkyunkwan University, Korea. His research interests include power system protection, artificial intelligence application for protection and control, the modelling/protection of underground cable and EMTP software. He received his B.S and M.S degrees in Electrical Engineering from Sungkyunkwan University, Korea, 1982 and 1984, respectively. He received a Ph.D in Electrical Engineering from Sungkyunkwan University in 1990. Currently, he is a director of Center for Power IT(CPIT) in Sungkyunkwan University.
Jeong-Jae Yang was born in Korea, 1961. He received his B.S in Electrical Engineering Department from Keon- Kuk University, Korea in 1989. He has been with KPX, as a head of department of power system protection. His special fields of interest are the power system protection including the automatic reclosing and various relaying system.
References
1992 “Single phase tripping and auto reclosing of transmission lines-IEEE Committee Report” IEEE Trans. Power Delivery 7 182 - 192    DOI : 10.1109/61.108906
Ahn S. P. , Kim C. H. , Aggarwal R. K. , Johns A. T. 2001 “An Alternative Approach to Adaptive Single Pole Auto-Reclosing in High Voltage Transmission Systems Based on Variable Dead Time Control” IEEE Trans. On Power Delivery 16 (4) 676 - 686    DOI : 10.1109/61.956756
Aggarwal R. K. , Song Y. H. , Johns A. T. 1993 “Adaptive Three-phase Autoreclosure for Double-circuit Transmission Systems using Neural Networks” Proc. 1993 IEE Advances in Power System Control, Operation and Managements Conf. 389 - 392
Bo Z. Q. , Aggarwal R. K , Johns A.T. 1997 “A novel technique to distinguish between transient and permanent faults based on the detection of current transients” APSCOM-97. Fourth International Conference on (Conf. Publ. No. 450) 1 216 - 220
. Prikler L , Kizilcay M. , Ban G. , Handl P. “Improved secondary arc model based on identification of arc parameters from staged fault test records” Proc. 14th PSCC Sevilla, Spain Jun. 24-28, 2002
Mitsche J. V. , Rusche P. A. 1980 “Shaft Torsional Stress Due to Asynchronous Faulty Synchronization” IEEE Transactions on Power Apparatus and Systems PAS-99 (5) 1864 - 1868    DOI : 10.1109/TPAS.1980.319835
Abolins D. , Lambrecht J. , Joyce S. , Rosenberg L. T. 1976 “Effect of Clearing Short Circuits and Automatic Reclosing on Torsional Stress and Life Expenditure of Turbine-Generator Shafts” IEEE Transactions on Power Apparatus and Systems PAS-95 (1) 14 - 25
Dunlop R. D. , Horwitz S. H. , Joyce J. S. , Lambrecht D. 1980 “Torsional Oscillations and Fatigue of Steam Turbine-Generator Shafts Caused by System Disturbances and Switching Events” presented at the 1980 Session Paris
Baldwin M. S. , Daugherty R. H. 1977 “Transmission Line Switching and its Effect on Generators” a paper presented at the Missouri Valley Electric Assn. meeting Kansas City
1997 “Fourth Supplement to A Bibliography for The Study of Subsynchronous Resonance Between Rotating Machines and Power System” Power Systems, IEEE Transactions on PWRS-12 (3) 1276 - 1282
1991 “Third Supplement to a Bibliography for the Study of Subsynchronous Resonance Between Rotating Machines and Power Systems Power Systems, IEEE Trans PWRS-6 (2) 830 - 834
IEEE Std. C37.102-1995, “Guide for AC Generator Protection”
1980 “IEEE Screening Guide for Planned Steady-state Switching Operations to Minimize Harmful Effects on Steam Turbine-Generators” IEEE Transactions on Power Apparatus and Systems PAS-99 1519 - 1521    DOI : 10.1109/TPAS.1980.319576
2012 IEEE Std. C37.104-2012, “IEEE Guide for Automatic Reclosing of Circuit Breakers for AC Distribution and Transmission Lines”
2009 “Advantages and Disadvantages of EHV Automatic Reclosing”
Faried Sherif Omar , Billinton Roy , Aboreshaid Saleh , Foruhi-Firuzabad Mahmud 2000 “Effect of Adaptive Short Time Compensation on the Stochastic Behavior of Turbine-Generator Shaft Torsional Torques” IEEE Transactions on Energy Conversion 15 (3) 305 - 311    DOI : 10.1109/60.875497
El-Serafi M. , Faried S. O. 1990 “Effect of Field Discharge Resistors on Turbine-Generator Shaft Torsional Torques” IEEE Transactions on Energy Conversion 5 (1) 129 - 136    DOI : 10.1109/60.50824
El-Serafi M. , Faried S. O. 1994 “Effect of Adaptive Reclosing on Turbine-Generator Shaft Torsional Torques” IEEE Transactions on Power Systems 9 (4) 1730 - 1736    DOI : 10.1109/59.331424
Anderson P. M. “Power System Protection” Power Math Associates, Inc
Hsu Shin-Min , Horton Randy 2007 “Screening Study of Sudden Power Change on Generators due to Transmission Line Re-closing” IEEE Power Engineering Society General Meeting 1 - 8
Yeo S. M. , Kim C. H. 2012 “Analysis of Transient Overvoltages within a 345kV Korean Thermal Plant” Journal of Electrical Engineering & Technology 7 (3) 297 - 303    DOI : 10.5370/JEET.2012.7.3.297
Seo H. C. , Jang W. H. , Kim C. H. , Chung Y. H. , Lee D. S. , Rhee S. B. 2013 “Analysis of Magnitude and Rate-of-rise of VFTO in 550kV GIS using EMTP-RV Journal of Electrical Engineering & Technology 8 (1) 11 - 19    DOI : 10.5370/JEET.2013.8.1.011
1998 “A Study on the Improvement of Auto-Reclosing Scheme for Power Lines”
1985 “Second Benchmark Model for Computer Simulation of Subsynchronous Resonance” IEEE Transactions on Power Apparatus and Systems 104 (5) 1057 - 1066